400
CTM-WAT-003
REV. No. DATE. DESCTIPTION. AUTH.
DRAWING No. REVISION.
ORG. DATE.
SCALE :-
TYPICAL ABOVE GROUND
WATER RETICULATION STANDARD DRAWING
A 13/10/2020
CTM WATER SERVICE
PROVIDERS A
NOT TO SCALE
WW25 OD
WATER MAIN
400
TYPICAL SHORT SERVICE ELEVATION
300 AS REQUIRED BY THE SERVICE PROVIDER
FINISHED SURFACE LEVEL
600 TO 800mm COVER
50mm MIN. 100mm MAX. 300
300
300 MIN. 500 MAX.
PROPERTY BOUNDARY
400
ROAD
150 MAX.
OWNERS
RESPONSIBILITY LIMIT OF COUNCIL
RESPONSIBILITY
25 OD
25 OD MDPE PIPE
PROPERTY BOUNDARY
NOTES
1. ALL CONNECTIONS ARE TO UNDERTAKEN BY THE WATER SERVICE PROVIDER.
2. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS NOTED OTHERWISE.
3. TAPPING BANDS SHALL BE OF THE DOUBLE COLLAR OR OTHER APPROVED TYPE BUT SHALL SPECIFICALLY NOT INCLUDE SINGLE COLLAR WITH U-BOLT TYPES.
4. COVER FOR SERVICE PIPES:
UNDER ROADWAY: 600mm MIN. - 700 MAX.
UNDER FOOTPATH: 450mm MIN. - 550 MAX.
5. POLYETHYLENE PIPES SHALL BE MDPE PN16 TO AS 4130. PVC PIPE TO BE PN16.
6. ALL SERVICE PIPES SHALL BE JOINTED WITH MATCHING FITTINGS COMPLYING WITH AS 1460.1.
7. PROVIDE 80mm DIAMETER CLASS 6 PVCU ENVELOPER PIPE TO ALL SERVICES UNDER ROADWAYS AND CONCRETE FOOTPATHS. ENVELOPER PIPE TO EXTEND 200mm BEYOND BACK OF KERB OR BEYOND ROAD SHOULDER OR EDGE OF CONCRETE FOOTPATH.
8. ANNULAR SPACE BETWEEN ENVELOPER AND SERVICE PIPE TO BE SEALED WITH REMOVABLE TAPE (DENSO 600 OR EQUAL) EXTENDING MINIMUM 100mm ONTO EACH PIPE, IN DOUBLE LAYER.
W W W W W W W
200 200
20mm COPPER PIPE TO WATER MAIN
NSL
PROPERTY BOUNDARY
PROPERTY SERVICES
80Ø PVC-U ENVELOPER
SEE DETAIL B
WATER MAIN WITH TAPPING BAND AND FERRULE TAP. SEE DETAIL A
CONCRETE FOOTPATH
TYPICAL SHORT SERVICE PLAN
LOCATION AS REQUIRED BY WATER SERVICE PROVIDER
PROPERTY BOUNDARY
PROPERTY BOUNDARY
SEE DETAIL B
20 BSP FERRULE TAP WITH POLY ADAPTOR
TAPPING BAND TAPPED 20 BSP
BRASS PLUG TO SUIT
PRESSURE REDUCTION VALVE 500kPa (IF REQUIRED)
20 NB WATER METER WITH MALE TAIL CONNECTIONS
20 NB COPPER PIPE CLASS B WITH COPPER / MI CONNECTOR EACH END
20 BSP GS PLUG
20 NB COPPER 20 BSP FI ELBOW 20 NB COPPER TUBE
CLASS B 600mm LONG 25 OD TO 20 BSP FI
CONNECTOR
20 NB RIGHT ANGLE FxF SHORT HANDLE BALL VALVE
ELEVATION DETAIL B
TOWNSVILLE CITY COUNCIL &
MACKAY REGIONAL COUNCIL
ELEVATION DETAIL A
DETAIL B
CAIRNS REGIONAL COUNCIL
TAPPING BAND TAPPED FOR FERRULE TAP.
REFER NOTE 2
PIPE DRILLED TO SUIT W.F T.P.R.N.R. FERRULE (WITH STANDARD FERRULE BONNET) FOR P.V.C MAINS. FOR C.I. MAINS A 20mm FERRULE COCK IS CONNECTED DIRECTLY TO MAIN
SELECT BACKFILL FERRULE TAP COVER 80 DIA CLASS 6 PVC
80mm PVC VALVE SOCKET 80Ø BSP GALV SCREWED CAP
BRASS PLUG TO SUIT
PRESSURE REDUCTION VALVE 500kPa WATER METER
20mm ISOLATING VALVE
150 MIN.
300
150 MIN. 500 MAX. COVER
WATER SERVICE AND 20mm METER
CRC MRC TCC
ORIGINAL ISSUE