Digital Breaker Failure

Phase and ground backup protection

for the primary circuit breaker.

A pplicat ions

■ Backup protection for prim ary circuit

breaker

Prot ect ion and Cont rol

■ Tw o step instantaneous and/or tim e delayed

breaker failure

■ Independent tim er per phase for the first step

■ Phase instantaneous overcurrent

■ Ground instantaneous overcurrent

■ Three phase direct trip

■ Fast tripping logic by using a second set of

level detectors per phase and an independent tim er

■ Internal arcing protection

■ Operation failure detection

■ Three settings groups

■14 configurable inputs

■16 outputs (11 configurable)

M onit oring and M et ering

■Current m etering

■Breaker health m onitoring

■Event recorder, last 165 events

■Oscillography, 4 records of 62 cycles

■Phase sequence selection

U ser Int erf aces

■Keypad and display

■17 LED indicators

■3 com m unications ports

■RS232 ports

■Fiber optics available

(2)

D escript ion

The DBF is a digital breaker fail-ure relay that provides phase and ground backup protection if the p r i m ar y ci r cu i t b r eaker f ai l s t o clear a system fault.

Breaker failure protection is criti-cal i n an y b acku p r el ay i n g sch em e. Th i s p r o t ect i o n m u st h av e n o t o n l y sen si t i v i t y an d d ep en d ab i l i t y, b u t al so a h i g h l ev el o f secu r i t y b ecau se i t i s protecting the busbars. The relia-bility m ust also be the sam e as that of a busbar protection relay. By using digital technology the o p er at i o n t i m e o f t h e DBF h as been im proved.

An associated function protects against electrical arcing betw een the contacts of the breaker w hen i t i s o p en ed . Th i s w i l l h el p t o prevent dam age to the breaker. Th i s f u n ct i o n u ses t h r ee v er y sensi ti v e ov er curr ent detector s set to the line capacitive current. Three setting groups are avail-ab l e, w i t h t h e act i v e g r o u p selected by a setting or an input. There are 14 configurable inputs and 16 outputs (11 configurable). Th e DBF m et er s t h e cu r r en t continuously. It also m onitors the breaker health I2t value. It has an event recorder that can store the last 165 events w ith a 1 m s reso-l u t i o n . It can st o r e u p t o 4 o sci l l o g r ap h y r eco r d s w i t h 66 cycles each.

The local user interface includes a keypad and display. There are 17 LED i n d i cat o r s, o n e a t w o colored system alarm , and 16 red co n f i g u r ab l e t o an y o f t h e 32 alarm s available. There are three co m m u n i cat i o n s p o rt s, o n e o n the front panel and tw o on the

Prot ect ion and

Cont rol

Overcurrent Protection

The DBF’s three phase overcur-rent protection (50PBF) consists of single or three-phase breaker failure initiation units w ith inde-pendent pickups and tim e delays. It also has three phase direct trip protection (50XNF), w hich m ay be used for three phase breaker failure initiation w ithout overcur-r en t . Th e DBF al so i n cl u d es g r o u n d ov er cu rr en t p r o t ect i o n (50NBF).

Tw o step breaker failure opera-tion is included w here each step o p er at i o n m ay b e act i v at ed b y single, tw o or three phase over-current functions. Both steps are t i m e d el ay ed an d o ff er a w i d e range of settings.

U si n g i n d ep en d en t t i m er s p er phase for the first step perm its a co r r ect co o r d i n at i o n w i t h t h e second zone in case of evolving f au l t s i n si n g l e-p o l e t r i p p i n g schem es.

Th e f ast t r i p p i n g l o g i c p er m i t s accelerated tripping during three-phase faults. This is particularly u sef u l i n m ai n t ai n i n g p o w er system stability w here selecti ve fast tripping is appropriate.

Internal Arcing Protection

If an electrical arc exists betw een the contacts of an open breaker it can eventually destroy the break-er. Th e DBF u ses t h r ee v er y sensi ti v e ov er curr ent detector s set to the line capacitive current to protect against internal arcing.

Settings Groups

Th r ee g r o u p s o f set t i n g s ar e available for the DBF. The active

Inputs and Outputs

The enhanced m odel DBF has 14 configurable inputs, in groups of 2 and 3 inputs.

Th er e ar e 16 o u t p u t s w i t h t h e follow ing assignm ents:

■1 breaker failure pickup

■2 breaker failure fix tripping

contacts

■1 internal arc contact

■1 alarm contact

■5 spare configurable contacts

■6 latching relay contacts

(option-al)

Th e l o g i c f o r co n f i g u r ab l e outputs consists of a com bination of NOT, AND, and OR gates appli-cable to trips, alarm s and pickups of all the protection and control f u n ct i o n s, i n t er n al p r o t ect i o n status, control, digital inputs, etc. A basic DBF m odel is also avail-ab l e w h i ch i n cl u d es 6 co n f i g u r ab l e i n p u t s an d 10 outputs (5 of w hich are config-urable).

M onit oring and

M et ering

Breaker M onitoring

The breaker status is m onitored continuously. The cum ulative I2t v al u e i s st o r ed an d u sed f o r breaker health m onitoring.

Event Recorder

(3)

Oscillography

Th e DBF sy st em i n cl u d es an oscillography recorder. It can be activated by any of the protective functions pickup or trip or by an ex t er n al i n p u t . Reco r d s h av e a r eso l u t i o n o f 16 sam p l es p er cy cl e. U p t o 4 r eco r d s m ay b e stored w ith up to 66 cycles each, w ith pre-fault cycles adjustable betw een 2 and 10 cycles.

The DBF can store up to 4 oscillography records

Protection Status Self-checking

The DBF perform s self tests both at start up and continuously in the background during operation.

5

U ser Int erf aces

Keypad and Display

The DBF has a 20 button keypad an d a 2 l i n e b y 16 ch ar act er al p h an u m er i c LCD. Th i s al l o w s l o cal u ser i n t er f ace w i t h o u t a com puter.

LED Indicators

The DBF has 17 LED indicator s. One is a tw o color system alarm . Th e o t h er 16 ar e r ed , an d ar e co n f i g u r ab l e t o an y o f t h e 32 alarm s available. Each LED can b e co n f i g u r ed w i t h o r w i t h o u t m em ory.

Communications

The DBF has three com m unica-t i o n s p o r unica-t s, o n e o n unica-t h e f r o n unica-t panel w hich is connected to one o n t h e r ear p an el , an d a t h i r d independent rear panel port. The first tw o ports allow com m u-n i cat i o u-n t h r o u g h GE-LOCA L so ft w ar e, ei t h er l o cal l y w i t h a

laptop com puter, or rem otely to a protection dispatch center. This software allow s the user to visu-alize m easurem ents and status as w ell as the relay’s tim e synchro-nization.

The third port connects the user t o a co m m u n i cat i o n s n et w o r k, through GE-POWER softw are, to t h e p ar t o f a DDS i n t eg r at ed sy st em . Th ese ap p l i cat i o n s ar e p ar t o f GE-N ESIS (Gen er al El ect r i c N Et w o r k Su b st at i o n Integration Software) used by the DDS system .

GE-LOCAL software is provided for DBF com m unication

D im ensions

FRONT VIEW SIDE VIEW

CUTOUT & DRILLING PATTERN

19.00" (483)

3.40" (87)

10.35"

(263) 1.20"

(31)

0.28" Dia. (7) 4 Pl.

18.32" (465) 17.32" (440)

725700A2.dw g 3.52"

(89) 3.00"

(76) 0.26"(7)

(4)

Typical Wiring

B.F. INIT. PHASE A

52/b - A

3 PHASE B.F. INIT.

(5)

D BF Technical Specif icat ions

O U T P U T S Signalling contacts:

Contact Capacity:

M aximum operating voltage: 380 VAC, 250 VDC

Continuous current: 8 A

M ake and carry: 8 A

Breaking capacity: 1760 VA

Tripping Contacts: Contact Capacity:

M aximum Operating Voltage: 440 VAC

Continuous Current: 16A

M ake and Carry: 30 A

Breaking: 4000 VA

IN P U T S Burdens:

Current Circuits: 0.5 VA for In= 5 A 0.1 VA for In= 1 A

DC Burden:

During operation: 12 W

Per each activated input: 8 mA/1W, Vaux: 125 VDC

PA C K A G IN G

Dimensions: 3.40" H x 19" W x 10.35" D (87 mm x 483 mm x 263 mm)

Weight:

Not packaged: 16.08 lbs (6 kg)

Packaged: 18.76 lbs (7 kg)

T Y P E T E S T S

Isolation Test Voltage: 2 kV, 50/60 Hz, 1 min

Surge Test Voltage: 5 kV peak, 0.5 J

Interference: Class III according to IEC 255-22-1

Electrostatic Discharge: Class IV according to IEC 255-22-2

Radio Interference: Class III according to IEC 255-22-3

Fast Transient: Class IV according to IEC 255-22-4

Sinusoidal Vibration: Class II according to IEC 255-21-1

Shock: Class I according to IEC 225-21-2

Radio Frequency Emission:

according to IEC 41B (Sec) 81 and EN55022 class B

Emisitivity: according to EN50081-2(* )

Susceptibility: according to EN50082-2(* )

E N V IR O N M E N T A L Temperature:

Storage: -40°C to +85°C

Operation: -20°C to +55°C

Humidity: Up to 95% w ithout condensing

M E C H A N IC A L C H A R A C T E R IS T IC S

• M etallic package in 19" rack and 2 units high • Frontal M M I w ith LCD and keypad • Six rear terminal blocks

• Protection class IP52 (according to IEC 529)

A P P R O V A L S

Compliant UL - UL listed for USA and Canada

C O M M U N IC A T IO N S

Local Communication:LCD alphanumeric display w ith tw o lines of 16 characters per line

20 button frontal keypad

Remote Communication

(local or remote PC and communication net): M ode: half duplex

Speed: 1200 to 19200 bps

Physical M edia:RS232 (ports 1, 2 and 3) Plastic fiber optic (port 3 optional)

Type of connector: HFBR-4516 Pow er supplied: -8 dBm Receptor’s sensitivity: -39 dBm Wave length: 660 nm Glass fiber optic (port 3 optional)

Type of connector: STA Pow er supplied: -17.5 dBm Receptor’s sensitivity: -24.5 dBm Wave length: 820 nm Synchronization: IRIG-B

• DB9 connector for RS232 ports on the front (1) and on the rear (2)

• DB9 connector for RS232 port on the rear (3), w ith 1 mm plastic fiber optic or 50/125 glass fiber optic option

M E T E R IN G

Frequency: 50/60 Hz

Rated Phase Current: 0.2 - 2.4 Inin steps of 0.01 A Range D

Rated Ground Current: 0.1-1.2 Inin steps of 0.01 A Range D

Auxiliary Voltage: 24 - 48 VDC ± 20% 110 - 250 VDC ±20%

P R O T E C T IO N Thermal Capacity:

Current circuits:

Continuously: 4 x In

During 3 sec: 50 x In

During 1 sec: 100 x In

TIM ERS

1 Phase Timers T1: 0.05 - 2 sec in steps of 0.01 sec

3 Phase Timers T2: 0.05 - 2 sec in steps of 0.01 sec

3 Phase W /O Current Timer T3: 0.05 - 2 sec in steps of 0.01 sec

2nd Stage Timer: 0.05 - 2 sec in steps of 0.01 sec

Internal Arc Timer T4: 0.1 - 2 sec in steps of 0.01 sec

* Specifications subject to change w ithout notice.

Ordering

To order select the basic model and the desired features from the Selection Guide below.

DBF

1 * * * * 1 1 1 * * * A

DBF DBF Digital Breaker Tripping 0 RS232 communications

1 Plastic fiber optic and RS232 communications 2 Glass fiber optic and RS232 communications 3 RS485 and RS232 communications

B Ranges: Phase: In= 1 A (0.2-2.4 A), Ground: In= 1 A (0.2-2.4 A) C Ranges: Phase: In= 5 A (1-12 A), Ground: In= 1 A (0.2-2.4 A) D Ranges: Phase: In= 5 A (1-12 A), Ground: In= 5 A (0.5-6 A) F Ranges: Phase: In= 5 A (0.5-6 A), Ground: In= 1 A (0.2-2.4 A) G Ranges: Phase: In= 5 A (0.5-6 A), Ground: In= 1 A (0.1-1.2 A)

1 P1, P2, P3: M -Link communications protocol 2 P1, P2: M -Link protocol;

P3: M odBus®RTU communications protocol M Spanish language

D English language G 48-125 VDC pow er supply H 110-250 VDC pow er supply

00 Standard model

Special M odels:

MOD 04A: Digital inputs voltage: 48 VDC±20%

MOD 05A: DIV: 110 VDC ±20%

MOD 06A: DIV: 125 VDC ±20% w w w .G Ein d u s t r ia l.c o m / p m

Order online –

Order online –

Referensi

Dokumen terkait

Industri yang bergantung pada kreativitas serta Imaginative Intellectual Property kini semakin berkembang dan menjadi bagian yang penting dalam ekonomi

konveyor pembawa material produksi. Dimana proses urutan starting motor adalah dimulai dari hilir ke hulu, dan sebaliknya proses stop dimulai dari hulu ke

Dengan diketahuinya uji t sebesar 1,181 tersebut berarti hipotesis (Ho) yang diajukan dalam penelitian ini dapat dipertanggungjawabkan, yaitu Tidak ada pengaruh

[r]

Hasil uji BNJ (Tabel 1) menunjukkan bahwa aplikasi mulsa plastik perak menghasilkan berat kering total tanaman tertinggi yang berbeda nyata dengan mulsa jerami padi

Berdasarkan Peraturan Perundang-undangan di atas, jalur penerimaan mahasiswa baru dilakukan melalui Seleksi Nasional Masuk Perguruan Tinggi Negeri (SNMPTN), Seleksi

Tujuan: Untuk mengetahui hubungan antara profil lipid dengan rasio proinsulin- insulin pada individu dengan toleransi gukosa normal.. Metode: Studi potong lintang yang dilakukan

“The promotion of community forestry in many developing countries may increase local adaptive capacity by putting decisions in the hands of the people who feel the efects of