Electric Power Systems L3 - Olof Samuelsson 1
Outline
• Generator models
• Line models
• Transformer models
• Load models
• Single line diagram
• Per unit system
KOMPONEN UTAMA SISTEM TENAGA LISTRIK
1.
GENERATOR SEREMPAK
2.
SALURAN TRANSMISI
3.
TRANSFORMATOR
4.
BEBAN
DIGUNAKAN RANGKAIAN PENGGANTI DARI KOMPONEN-KOMPONEN UTAMA DALAM "MENGANALISIS" SISTEM TENAGA LISTRIK
.
RANGKAIAN PENGGANTI YANG DIGUNAKAN ADALAH RANGKAIAN PENGGANTI SATU PHASA
DENGAN NILAI PHASA-NETRALNYA, DENGAN ASUMSI SISTEM 3 PHASA YANG DIANALISIS
Electric Power Systems L3 - Olof Samuelsson
3
Model Generator Serempak
Model Rangkaian Mesin Serempak
a a' b b' c c' d Stator Rotor Celah Udara mmf lilitan Kumparan medan pada rotor U U S S Stator Rotor Kumparan medan a a' a' a b b' b b' c c' c' cElectric Power Systems L3 - Olof Samuelsson
5
PADA ANALISIS SISTEM TENAGA I (SISTEM
DALAM KEADAAN STEADY STATE),
KARAKTERISTIK GENERATOR DENGAN
KUTUB MENONJOL MENDEKATI
KARAKTERISTIK GENERATOR DENGAN
KUTUB BULAT.
SEMUA GENERATOR DIASUMSIKAN
MEMPUNYAI ROTOR BULAT
ROTOR YANG DICATU OLEH SUMBER ARUS SEARAH MENGHASILKAN MEDAN MAGNET YANG BERASAL DARI ARUS YANG MENGALIR PADA BELITAN ROTOR.
ROTOR TERSEBUT DIPUTAR OLEH PRIME MOVER (TURBIN), SEHINGGA MEDAN MAGNET YANG DIHASILKAN ROTOR TERSEBUT MEMOTONG KUMPARAN-KUMPARAN PADA STATOR.
AKIBATNYA, TEGANGAN DIINDUKSIKAN (DIBANGKITKAN) PADA KUMPARAN STATOR TERSEBUT.
FREKWENSI DARI TEGANGAN YANG DIBANGKITKAN OLEH STATOR ADALAH :
Hz
n
p
f
60
2
Electric Power Systems L3 - Olof Samuelsson
7
TEGANGAN YANG DIBANGKITKAN PADA KUMPARAN STATOR DISEBUT TEGANGAN BEBAN NOL.
GENERATOR 3 FASA DENGAN BELITAN STATOR 3 FASA MEMBANGKITKAN TEGANGAN 3 FASA YANG SEIMBANG.
BILA SUATU BEBAN 3 FASA SEIMBANG DIHUBUNGKAN KE GENERATOR, MAKA AKAN MENGALIR ARUS 3 FASA SEIMBANG PADA BELITAN-BELITAN STATOR 3 FASA-NYA (BELITAN JANGKAR)
ARUS TERSEBUT MENIMBULKAN MMF YANG DISEBUT MMF DARI REAKSI JANGKAR.
SEHINGGA MEDAN MAGNET DIDALAM AIR GAP MERUPAKAN RESULTAN DARI MMF YANG DIHASILKAN OLEH ROTOR DAN REAKSI JANGKAR TERSEBUT.
DAN, MMF RESULTAN TERSEBUT YANG MEMBANGKITKAN TEGANGAN PADA TIAP-TIAP PHASA DARI KUMPARAN STATOR.
90o Ia Er Ef Ear r ar f
Diagram fasor yang menunjukkan hubungan antara fluks dan tegangan kumparan fase a.
Electric Power Systems L3 - Olof Samuelsson 9 ar a ar
jI
X
E
ar f rE
E
E
E
r
E
f
jI
aX
ar l a r tE
jI
X
V
s a f tE
jI
X
V
reactance leakage armature to due reaction armature to due load no at generated l a ar a f tE
jI
X
jI
X
V
a s
a f tE
I
R
jX
V
X
S= X
ar+ X
lE
f+
-E
r+
-+
-X
arX
lR
aI
aX
s tV
Electric Power Systems L3 - Olof Samuelsson
11
Rangkaian Pengganti 1 Fasa Generator Serempak
Electric Power Systems L3 - Olof Samuelsson
13
Parameter Saluran
• Distributed along line
– L
W/km self and mutual inductance
– R
W /km conduction losses
– C F/km capacitance between phases
– G S/km corona losses
• Return current at unbalance
– Through earth
– Average equivalent depth 850 m
1
2
3
4
Im
port
ance
Line models
<80km
Saluran Transmisi Pendek
80-240km
Saluran Transmisi Menengah
>240km
Saluran Transmisi Panjang
R
L
B
2
G
2
B
2
G
2
Electric Power Systems L3 - Olof Samuelsson
15
Voltage levels
• High voltage transmission
– Large equipment
– Lines have X/R≥10 =>
low losses
• Medium voltage for industries
• Low voltage indoor (households…)
– Compact equipment
+
-R
Z
+
-RV
SV
X =
L
I
SI
RRangkaian Pengganti
Electric Power Systems L3 - Olof Samuelsson 17
+
-R
X =
L
+
-RV
V
I
S SI
R c Y 2 c Y 2 Y = X 1 c = C cZ
Rangkaian Pengganti
Saluran Transmisi Menengah
DALAM ANALISIS SISTEM TENAGA LISTRIK HANYA DIGUNAKAN RANGKAIAN PENGGANTI SALURAN TRANSMISI PENDEK DAN MENENGAH
Electric Power Systems L3 - Olof Samuelsson
19
RADIATOR COOLING SYSTEM TOP OIL TEMP.
The power transformer
• Key component in AC power system
– High reliability and efficiency >95%
– Ratings up to 750MVA in Sweden
• Different types
– Two-winding most common
– Three-winding has two secondaries
– Phase-shifting
Electric Power Systems L3 - Olof Samuelsson
Electric Power Systems L3 - Olof Samuelsson
+ -r 1 V x I1 1 1 IE B G a r a x 2 2 -2 aV + 2 I2 a 2
Rangkaian pengganti transformator dengan
besaran
dinyatakan terhadap sisi 1
(diukur di sisi 1, sisi 2 dihubungkan singkat)
a
N
N
2 1Electric Power Systems L3 - Olof Samuelsson 25 + -R + -2 V ' 1 V X I1 eq eq 2 2 1 ) 12 (
r
a
r
R
eq
2 2 1 ) 12 (x
a
x
X
eq
2 1 2 ) 21 (a
r
r
R
eq
2 1 2 ) 21 (a
x
x
X
eq
Rangkaian ekivalen transformator dengan besaran dinyatakan terhadap sisi 1 dan sisi 2, arus magnet diabaikan.
+
-+
-2V '
1V
X
I
1 eq= I2
' 2 2 1 ) 12 (x
a
x
X
eq
(21) 2 12a
x
x
X
eq
Electric Power Systems L3 - Olof Samuelsson
Electric Power Systems L3 - Olof Samuelsson
Electric Power Systems L3 - Olof Samuelsson
Electric Power Systems L3 - Olof Samuelsson
33
Transformator 3 (tiga) belitan
(Three winding transformers)
Model Beban
Beban terdiri dari motor-motor induksi, pemanas dan penerangan serta motor-motor serempak. Untuk tujuan analisis, ada tiga cara
merepresentasikan beban :
1. Representasi beban dengan daya tetap.
Daya aktif (MW) dan daya reaktif (MVAR)
mempunyai harga yang tetap.
2. Representasi beban dengan arus tetap
I
V
jQ
P
I
*
V
V
P
Q
1tan
Electric Power Systems L3 - Olof Samuelsson
35
3. Representasi beban dengan impedansi tetap
jQ
P
V
I
V
Z
2 2V
jQ
P
V
I
Y
Impedansi :
Admitansi :
Diagram Segaris
DENGAN MENGANGGAP BAHWA SISTEM 3 FASA DALAM KEADAAN SEIMBANG, PENYELESAIAN/ANALISIS DAPAT DIKERJAKAN DENGAN MENGGUNAKAN RANGKAIAN 1 FASA DENGAN SALURAN NETRAL SEBAGAI SALURAN KEMBALI.
UNTUK MEREPRESENTASIKAN SUATU SISTEM TENAGA LISTRIK 3 FASA CUKUP DIGUNAKAN DIAGRAM 1 FASA YANG DIGAMBARKAN DENGAN MEMAKAI
SIMBOL-SIMBOL DAN SALURAN NETRAL DIABAIKAN.
DIAGRAM TERSEBUT DISEBUT DIAGRAM SEGARIS (ONE LINE DIAGRAM). DIAGRAM SEGARIS BIASANYA DILENGKAPI DENGAN DATA DARI MASING-MASING
Electric Power Systems L3 - Olof Samuelsson
GEN.1 : 20.000 KVA, 6.6 KV, X = 0.655 OHM GEN.2 : 10.000 KVA, 6.6 KV, X = 1.31 OHM GEN.3 : 30.000 KVA, 3.81 KV, X = 0.1452 OHM
T1 DAN T2 : MASING-MASING TERDIRI DARI 3 TRAFO 1 FASA : 10.000 KVA, 3.81-38.1 KV, X = 14.52 OHM
DINYATAKAN TERHADAP SISI TEGANGAN TINGGI. TRANSMISI : X = 17.4 OHM
BEBAN A : 15.000 KW, 6.6 KV, POWER FACTOR : 0.9 LAG
Electric Power Systems L3 - Olof Samuelsson
39
DIAGRAM IMPEDANSI
DENGAN MENGGUNAKAN RANGKAIAN PENGGANTI MASING2 KOMPONEN DAN DARI DATA YANG DIKETAHUI DIPEROLEH:
BILA TERJADI HUBUNG SINGKAT 3 FASA ( SISTEM TETAP SEIMBANG) PADA BUS DIMANA BEBAN B TERHUBUNG, AKAN DIHITUNG ARUS HUBUNG SINGKAT TERSEBUT.
BEBAN A & B DAPAT DIABAIKAN
PERHITUNGAN DILAKUKAN DENGAN MENYATAKAN SEMUA BESARAN (TEGANGAN, ARUS & IMPEDANSI) TERHADAP SALAH SATU SISI TEGANGAN
Electric Power Systems L3 - Olof Samuelsson
41
UNTUK MENGHITUNG ARUS H.S. TERSEBUT, DIAGRAM IMPEDANSI DAPAT DISEDERHANAKAN (DENGAN SEMUA BESARAN DINYATAKAN TERHADAP SISI TEGANGAN TINGGI)
DIGUNAKAN SUPERPOSISI
KERJAKAN LAGI SOAL DIATAS BILA HUBUNG SINGKAT TERJADI PADA PERTENGAHAN SALURAN TRANSMISI
Per Unit Normalization
• Normalize to nominal value
• Example: 11 kV at 10 kV base
V
p.u.=V
actual/V
base=11kV/10kV=1.1p.u.
• p.u. indicates if situation is normal
• Voltage levels comparable
Electric Power Systems L3 - Olof Samuelsson
43
4 (EMPAT) BESARAN DALAM SISTEM TENAGA LISTRIK :
I (ARUS - AMPERE)
V (TEGANGAN - VOLT)
S (DAYA - VOLTAMPERE)
Z (IMPEDANSI - OHM)
DENGAN MENENTUKAN BESARAN DASAR (BASE), BESARAN PERSATUAN (PER-UNIT) DAPAT DIHITUNG.
CATATAN : BESARAN – BESARAN TSB ADALAH BESARAN
B base actual pu
V
V
Volts
V
Volts
V
V
)
(
)
(
B base actual puI
I
Amps
I
Amps
I
I
)
(
)
(
B base actual puS
S
VA
S
VA
S
S
)
(
)
(
actual puZ
Z
ohm
Z
ohm
Z
Z
)
(
)
(
PER – UNIT
VALUES
Electric Power Systems L3 - Olof Samuelsson
45
Base values
• Theoretically
– Any two of S, V, I and Z
• Practically
– System MVA base +
One voltage base
– S
base/V
base=> I
base– V
base2/S
base
=> Z
basebaseLN
base
B
KV
KVA
I
1
1
2
1
2
1000
base
baseLN
base
baseLN
B
MVA
KV
KVA
KV
Z
Electric Power Systems L3 - Olof Samuelsson
47
Dengan menggunakan
data 3 fase
:
baseLL
base
B
KV
KVA
I
3
3
3
2
3
2
1000
base
baseLL
base
baseLL
B
MVA
KV
KVA
KV
Z
GEN.1 : 20.000 KVA, 6.6 KV, X = 0.655 OHM GEN.2 : 10.000 KVA, 6.6 KV, X = 1.31 OHM GEN.3 : 30.000 KVA, 3.81 KV, X = 0.1452 OHM
T1 DAN T2 : MASING-MASING TERDIRI DARI 3 TRAFO 1 FASA : 10.000 KVA, 3.81-38.1 KV, X = 14.52 OHM
DINYATAKAN TERHADAP SISI TEGANGAN TINGGI. TRANSMISI : X = 17.4 OHM
BEBAN A : 15.000 KW, 6.6 KV, POWER FACTOR : 0.9 LAG
Electric Power Systems L3 - Olof Samuelsson
49
I
II
III
KVAB= 30.000 KVA KVAB= 30.000 KVA KVAB= 30.000 KVA KVB= 6.6 KV KVB= 66 KV KVB= 3.81 KV A IB 2.624,32 6 , 6 3 000 , 30 I A B 262,43 66 3 000 , 30 IB 4.546,07 A 81 , 3 3 000 , 30 Ohm ZB 1,452 30 6 , 6 2 ZB 145,2Ohm 30 662 ZB 0,484Ohm 30 81 , 3 2
Data 3 phasa
BILA TERJADI HUBUNG SINGKAT 3 FASA ( SISTEM TETAP SEIMBANG) PADA BUS DIMANA BEBAN B TERHUBUNG, AKAN DIHITUNG ARUS HUBUNG SINGKAT TERSEBUT.
PERHITUNGAN DILAKUKAN SETELAH SEMUA BESARAN (TEGANGAN ARUS & IMPEDANSI) DIUBAH SATUANNYA DALAM PU.
Electric Power Systems L3 - Olof Samuelsson
51
DENGAN CARA YANG SAMA ARUS HUBUNG SINGKAT 3 FASA DARI BUS DIMANA BEBAN B TERHUBUNG DAPAT DIHITUNG
Kerjakan contoh diatas dng : MVAbase=50
MVA, KVbase=10 KV (Gen 1 & 2), hub.
Per unit transformer model
• p.u. value of Z
12
and Z
21
the same!
• Simple p.u. model only a Z
eq
TRANFORMATOR 1 PHASA DENGAN RATING 110/440 V, 2.5 KVA. REAKTANSI BOCOR DIUKUR DARI SISI TEGANAGAN RENDAH 0.06 OHM.
Electric Power Systems L3 - Olof Samuelsson 53 V1 V2 I1 N1 : N2 I2 110 Volt 440 Volt 2,5 kVA 440 110 a
X
12
0
,
06
W
W
4
,
84
5
,
2
1000
x
110
,
0
2 1 BZ
IMPEDANSI BASE SISI TEGANGAN RENDAH :
REAKTANSI BOCOR (THD SISI TEGANGAN RENDAH):
pu
X
0
,
012
84
,
4
06
,
0
12
REAKTANSI BOCOR (THD SISI TEGANGAN TINGGI) :
IMPEDANSI BASE SISI TEGANGAN TINGGI :
REAKTANSI BOCOR (THD SISI TEGANGAN TINGGI):
W 77,5 5 , 2 1000 x 440 , 0 2 2 B Z
W
0
,
96
110
440
06
,
0
2 2 12 21a
X
X
pu
X
0
,
012
5
,
77
96
,
0
21
X
12
= X
21
(pu)
Electric Power Systems L3 - Olof Samuelsson
55
Impedansi (pu) trafo 3 belitan
DARI TEST HUBUNG SINGKAT DAPAT DIPEROLEH 3 (TIGA) IMPEDANSI SEBAGAI BERIKUT :
Z12 : IMPEDANSI BOCOR DIUKUR PADA PRIMER DENGAN SEKUNDER SHORT DAN TERSIER OPEN.
Z13 : IMPEDANSI BOCOR DIUKUR PADA PRIMER DENGAN TERSIER SHORT DAN SEKUNDER OPEN.
Z23 : IMPEDANSI BOCOR DIUKUR PADA SEKUNDER DENGAN TERSIER SHORT DAN PRIMER OPEN.
RANGKAIAN PENGGANTI TRAFO 3 BELITAN :
3
2
23
3
1
13
2
1
12
Z
Z
Z
Z
Z
Z
Z
Z
Z
13 23 12
3 13 23 12 2 23 13 12 12
1
2
1
2
1
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Semua impedansi
dalam pu.
Electric Power Systems L3 - Olof Samuelsson
57
MENGUBAH (BASE) DARI BESARAN PERSATUAN
Bo Bn Bn Bo o nKVA
KVA
KV
KV
pu
Z
pu
Z
2)
(
)
(
Z
n= IMPEDANSI (p.u) DENGAN BASE BARU
Z
o= IMPEDANSI (p.u) DENGAN BASE LAMA
KV
Bn= TEGANGAN BASE (KV) BARU
KV
Bo= TEGANGAN BASE (KV) LAMA
KVA
Bn= DAYA BASE (KVA) BARU
k l m n p r G M1 M2 T1 T2 Generator G: 300 MVA, 20 kV, x” = 20% = 0.2 pu
Motor M1: 200 MVA (input), 13,2 kV, x” = 20% = 0.2 pu Motor M2: 100 MVA (input), 13,2 kV, x”=20% = 0.2 pu Transmisi: 64 km, 0,5 Ohm/km
Trafo T1: 350 MVA, 230 Y - 20 kV, x =10%
Trafo T2 terdiri dari 3 trafo single-phase : 100 MVA, 127-13,2 kV, x =10%
Electric Power Systems L3 - Olof Samuelsson
59
The three-phase rating of transformer T2 is :
3 x 100 = 300 MVA
and its line-to-line voltage ratio is :
kV
2
.
13
/
220
2
.
13
/
127
3
A base of 300 MVA, 20 kV in the generator circuit
requires a 300 MVA base in all parts of the
system and the following voltage bases
In the transmission line: 230 kV (since T1 is
rated 230/20 kV)
In the motor circuit:
13
.
8
kV
220
2
.
13
230
k l m n p r G M1 M2 T1 T2
I
II
III
MVAB= 300 MVA MVAB= 300 MVA MVAB= 300 MVA KVB = 20 KV KVB = 230 KV KVB = 13.8 KV
IB = 8660,254 A IB = 753,066 A IB = 12551,093 A
Electric Power Systems L3 - Olof Samuelsson
61
The reactances of the transformers converted to the
proper base are :
unit per 0915 . 0 13.8 13.2 0.1 X : T r Transforme unit per 0857 . 0 350 300 0.1 X : T r Transforme 2 2 1
The base impedance of the transmission line is :
W
3
.
176
300
230
2and the reactance of the line is :
unit
per
1815
.
0
176.3
64
x
5
.
0
Reactance of motor M1 =
0
.
2745
per
unit
200
300
8
.
13
2
.
13
2
.
0
2
Reactance of motor M2 =
0
.
5490
per
unit
100
300
8
.
13
2
.
13
2
.
0
2
j0.085 j0.18 j0.09 j0.27 j0.55 j0.2 + _ + Em1 + Em2 k l m n p rElectric Power Systems L3 - Olof Samuelsson
63
If the motors M1 and M2 have inputs of 120 and 60
MW respectively at 13.2 kV, and both operate at
unity power factor (
0.8 lag
), find the voltage at
terminals of the generator.
Together the motors take 180 MW, or
unit
per
6
.
0
300
180
Therefore with V and I at the motors in
per-unit :
|V| . |I|
cosφ
= 0.6 per-unit
P =
and since,
unit
per
0
/
6273
.
0
0.9565
0.6
I
unit
per
0
/
9565
.
0
8
.
13
2
.
13
0 0
V
At the generator,
V = 0.9565 + 0.6273(j0.0915 + j0.1815 + j0.0857)
= 0.9565 + j0.2250 = 0.9826/13.20
0per-unit
The generator terminal voltage is :
I=0.6/0.9565x0.8
=0.78/-36.86
0pu
Drop Tegangan
Tegangan Motor
Electric Power Systems L3 - Olof Samuelsson
65
CONTOH 2 :
The three phase rating of a three-winding transformer
are:
Primary
Y-connected, 66 kV, 15 MVA
Secondary Y-connected,13.2 kV, 10.0 MVA
Tertiary
-connected, 2.3 kV, 5 MVA
Neglecting resistance, the leakage impedance are
Zps = 7% on 15-MVA 66-kV base
Zpt = 9% on 15-MVA 66-kV base
Zst = 8% on 10.0-MVA 13.2-kV base
Find the per-unit impedances of the star-connected
circuit model for a base of 15 MVA, 66 kV in the
With a base of 15 MVA, 66 kV in the primary circuit,
the proper bases for the per-unit impedances of the
equivalent circuit are 15 MVA, 66 kV for
primary-circuit quantities, 15 MVA, 13.2 kV for secondary
circuit quantities, and 15 MVA, 2.3 kV for tertiary
circuit quantities.
Zps and Zpt were measured in the primary circuit
and are therefore already expressed on the proper
base for the equivalent circuit. No change of voltage
base is required for Zst. The required change in
Electric Power Systems L3 - Olof Samuelsson
67
Zst = 8% x 15/10 = 12%
In per-unit on specified base :
0
.
09
0
.
12
0
.
07
0
.
07
per
unit
2
1
unit
per
05
.
0
09
.
0
12
.
0
07
.
0
2
1
unit
per
02
.
0
12
.
0
09
.
0
07
.
0
2
1
j
j
j
j
Z
j
j
j
j
Z
j
j
j
j
Z
t s p
A constant-voltage source (infinite bus) supplies
a purely resistive 5-MW 2.3-kV load a 7.5-MVA
13.2-kV synchronous motor having a
subtransient reactance of X” = 20%. The source
is connected to the primary of the three winding
transformer. The motor and resistive load are
connected to the secondary and tertiary of the
transformer.
Draw the impedance diagram of the system and
mark the per-unit impedance for a base of 66 kV,
15 MVA in the primary.
Electric Power Systems L3 - Olof Samuelsson 69
j0.05
j0.07
j0.40
j0.02
3.0
+
_
E
out+
_
The constant-voltage source can be represented
by a generator having no internal impedance.
The resistance of the load is 1.0 per-unit on a base
of 5 MVA, 2.3 kV in the tertiary
Expressed on a 15 MVA 23.kV base the load
resistance is
unit
per
0
.
3
5
15
x
0
.
1
R
Changing the reactance of the motor to a base of
15 MVA, 13.2 kV yields
unit
per
40
.
0
15
x
20
.
0
''
X
Electric Power Systems L3 - Olof Samuelsson
71
Gunakan base 100 MVA dan 22 kV pada sisi
Generator G1. Data peralatan adalah sbb.:
G1
: 35 MVA, 22 kV, x = 18%
G2
: 25 MVA, 11 kV, x = 15%
G3
: 30 MVA, 11 kV, x = 15%
T1
: 50 MVA, 22Δ-220Y kV, x=10%
T2
: 40 MVA, 11Δ-220Y kV, x=6%
T3
: 40 MVA, 11Y-220Y kV, x=8%
Beban 3 fasa pada bus L menyerap daya 58 MW,
faktor daya 0.6 lagging, pada tegangan 215 kV.
Electric Power Systems L3 - Olof Samuelsson
73