TOPIK PRESENTASI:
Liquid, Steam & Gas Measuring Instrumentation And Its
Application
PT. Petrokimia Nusantara
Interindo
DIBAWAKAN OLEH
:
ISI PRESENTASI
1. PENGERTIAN FLOWMETER ?
2. CARA MEMILIH FLOWMETER
3. JENIS/TIPE FLOWMETER
4. TEKNOLOGI FLOWMETER
5. PRODUCT LINE
1.
Mass
flow dan
Volumetric
flow ?
Bila anda ingin mengukur flow/arus, anda membutuhkan flowmeter. Dan flow/arus dapat disimpulkan dengan jumlah media melewati suatu lokasi dalam jangka waktu.
Melihat kesimpulan tersebut, sepertinya sangat mudah dan flowmeter apa saja dapat memadai. Akan tetapi, lihatlah rumus dibawah yang menjelaskan total arus
didalam pipa.
Q
= A x vQ
is flow rateA = cross-sectional area pipa
v = rata-rata kecepatan media di dalam pipa.
Cobalah mengaplikasikan rumus diatas, arus yang meluncur dengan rata2 kecepatan (V) 1m/s melewati pipa dengan cross-section(A) 1 m2.
Jawaban : 1 m/s X 1 m2 = 1 m3/s (
Q
)Q
adalah volumetric flow.Lihatlah rumus dibawah ini:
W
=rho
xQ
W
= Mass flow rate.rho
= the fluid density with temperature and pressure change.Q
= Volumetric flowPertanyaan : Diketahui bahwa media meluncur dengan kecepatan 1 m3/s(
Q
) dandensity (berat jenis) 1 kg/m3.
Jawaban : 1 m3/s X 1 kg/m3 = 1 kg/s (
W
)Perlu diketahui bahwa W adalah mass per unit waktu, jadi
W
disimpulkan sebagai “mass” flow rate.Sekarang flow apa yang ingin diukur? Volume atau mass?
Dalam aplikasi tertentu mengukur volume adalah jawaban yang tepat. Aplikasi dimana media yang diukur mempunyai density, pressure dan temperature yang konstan dan tentunya homogenis (contohnya : air).
Dalam proses lain, mass flow sangat penting. Mass flow digunakan untuk
mengukur media dimana density (berat jenis) dan temperature berubah setiap saat. (contohnya : Gas, udara, uap, dan chemical).
Sebelum memilih flowmeter yang tepat dalam suatu applikasi, beberapa hal penting yang perlu dilihat. Jenis media yang ingin diukur, range flow,
2. CARA MEMILIH FLOWMETER
Melihat instrument yang baik atau tidak itu dilihat dari 5 sisi terpenting,:
1. Accuracy dari Flowrate (VOLUMETRIC FLOWNYA, ATAU MASSFLOWNYA) 2. Repeatability
3. Turndown Rationya/rangeability 4. Response Time(seberapa cepat).
5. Dan yang terakhir lebih ke applikasi seperti piping requirements, Space Installation, ambient temperature di lapangan dll.
1. Percent accuracy
Pertama kita harus lihat dulu apakah flowmeter tersebut mengukur volumetric-flow atau mass-flow atau dua2nya. Tingkat accuracy dari volumetric flow dan massflow dari
sebuah flowmeter biasanya berbeda, dan kebanyakan % accuracy volumetric flownya lebih akurat, tetapi tidak menutup kemungkinan bisa sebaliknya.
2. % Repeatability
Seberapa sama alat tersebut membaca flow-rate ber-ulang2 kali, dengan amount yang sama. Dan ini sangat penting, kalo kita ngerti konsep “Turbelence Flow”. Faktor ini
sangat penting sekali, karena banyak flowmeter yang % Repeatability minim.
3. Turndown Ratio/ % Rangeability
The ability of instruments to read the different variation of flow/speed of the media. Jadi seberapa bisa flowmeter itu untuk mengukur flowrate dari maximum flow hingga
minimum flownya. Rumusnya dibawah !
TR = q
max/ q
minDimana,
TR = Turndown Ratio
q
max= maximum flow
q
min= minimum flow
Volumetric flow measurement technology : • Ultrasonic (Sierra Instruments)
• Magnetic
• vortex (Sierra Instruments)
• turbine meters
• Positive displacement Sensor
Indirect Mass flow measurement technology : • Differential Pressure (orifice,venturi,pitot tube,dll)
• Multivariable vortex flowmeter (Sierra Instruments)
Direct Mass flow measurement technology :
• Thermal Mass flowmeter (Sierra Instruments)
• Coriolis Mass flowmeter
3. Jenis dan tipe flowmeter
Velocity
Sensor
Temperature
Sensor
Q Industrial Thermal Vortex Meter4. PRODUCT LINE FLOWMETER
Sierra Instruments (Innova Mass 240)
Phase : Gas Only Type : Thermal
Mass-flow reading Accuracy : +/- 0.5 % Full Scale Turndown Ratio/Rangeability : 100 :1 Reapeatability : 0.2 % Gas Response Time : 200 miliSecond
Product Benefits:
Capillary Thermal
•Smart Valve” Mass Flow Controller
• Any clean gas or mixture including toxics and corrosives.
• Can calibrate with low cost and safe reference gases =
inexpensive
• Great Range and Sensitivity:
• Maximum 1000 slpm full scale
• Minimum 10 sccm (0.01 slpm) full scale!
• Direct Gas Mass measurement—No T or P compensation
• Compact size makes installation simple
4. PRODUCT LINE FLOWMETER
Sierra Instruments (Innova Mass 240)
Phase : Gas, Steam, Liquid Type : Multivariable Vortex Volumetric-Flow reading accuracy :
+/- 0.7 % for liquid. +/- 1 % steam and gas Mass-flow reading Accuracy :
+/- 1 % for liquid
+/- 1.5 % for Gas and steam Turndown Ratio/Rangeability :
30:1
Temperature Reading Accuracy : 1 Celcius liquid, steam and gas
Pressure accuracy : 0.4 % liquid, steam and gas Density Reading accuracy : 0.5 % liquid, steam and gas
Response Time : 200 miliSecond
4. PRODUCT LINE FLOWMETER
Sierra Instruments (Innova Sonic)
Phase : Liquid Type : Ultrasonic
Volumetric-Flow reading accuracy : +/- 1 % for liquid
Indirect Mass Flowmeter ?
DP-Flowmeter Multivariable Mass Flowmeter
INNOVA MASS 240
Mass flow rate
Volumetric flow rate
Temperature
Pressure
Why Direct Mass Flowmeter ?
1. Direct mass flow meters memiliki tingkat akurasi, turndown ratio and rangeabilility yang tinggi.
2. Direct mass flow meters tidak membutuhkan pressure atau temperature compensation equipment or flow computers.
3. Hemat biaya, cara pemasangan yang mudah dan tidak ada “moving parts”.
4. Gas memiliki density yang bervariasi. Tidak seperti mass flow meters, volumetric gas flow meters sangat sensitive terhadap perubahan pressure dan temperature.
Thermal
5. APPLIKASI FLOWMETER
• Leak detects in gas pipeline
• Natural gas fuel flow measurement
• Air entering the boiler’s furnace
• Boiler feed water measurement
• Superheated steam measurement
• Control of water volumes in main cooling water system
NATURAL GAS FUEL FLOW MONITORING
• Diskripsi : Menentukan efesiensi gas turbin secara akurat dalam kondisi maksimal.
• Media : Gas
• Flow measurement method : Mass flow
• Flowmeter recommended : Thermal Mass Flowmeter
Outstanding rangeability (100:1)
Built in flow-conditioning for upstream piping requirements No moving parts
One-second response to change in flow-rate. Excellent sensitivity to low speed flow
High accuracy and repeatability
Mengukur konsumsi gas alam yang masuk kedalam heater dan furnace di boiler.
AIR ENTERING THE BOILER’S FURNACE
• Description : Mengukur udara yang masuk kedalam furnace secara continuous untuk mengontrol fuel/air ratio.
• Media : Air
• Flow measurement method : Mass flow
BOILER FEEDWATER WATER MONITORING
• Description : Supply air yang di produksi dari condenser hasil condensasi uap yang berasal dari boiler.
• Media : Water
• Flow measurement method : volumetric flow
• Flowmeter recommended : Vortex Meter • Flowmeter type : Innova flo 240/241
CONTROL OF RAW WATER SUPPLY
• Description : Water being recovered from lake, sea, and other source.
• Media : water
• Flow measurement method : volumetric flow
• Flowmeter recommended : Ultrasonic flowmeter
High Accuracy
Simple to install, save cost and no process interruption Internally configured batch controller
Can be installed for sizes 1 up to 200 inch pipe. Range temperature (-40 to 150 C)
WATER CONTROL IN MAIN COOLING WATER SYSTEM
• Description : Supply air ke cooling system.
• Media : water
• Flow measurement method : volumetric flow
• Flowmeter recommended : Vortex flowmeter
SUPERHEATED STEAM MEASUREMENT
Description : steam at temperature above saturation temperature.
Relasi Pressure vs Temperature
Pada atmospheric pressure, temperatur saturasi terjadi di temperatur 100°C. Tetapi apabila pressure dinaikan pada uap, temperature akan naik tanpa merubah phase. Apabila uap mampu mengalir kedalam boiler pada rate sama uap itu produksi,
Relasi Pressure vs Volume
Volume berkurang pada saat pressure bertambah. Dan biasanya terjadi didalam boiler pada saat pressure di kisaran 7 bar . Apabila pressure bertambah, density dari uap juga akan bertambah.
Diagram dibawah menunjukan perubahan yang drastis pada volume di pressure yang rendah.
• Media : Superheated steam
• Flow measurement method : Indirect Mass-flow measurement
• Flowmeter recommended : Multivariable Mass-flow meter.
• Why multivariable mass-flow ? Mengukur lima jenis parameter dari satu perangkat, meliputi tekanan, temperatur, mass flow, volumetric flow, and density. Vortex meters memiliki rangeability yang tinggi. Ini membolehkan pengukuran uap di kecepatan yang bervariasi.