• Tidak ada hasil yang ditemukan

INDUSTRIAL VENTILATION A Manual of Recommended Practice 23rd Edition

N/A
N/A
Rahmat Aziz Damar Sogi Zuhuri

Academic year: 2023

Membagikan "INDUSTRIAL VENTILATION A Manual of Recommended Practice 23rd Edition"

Copied!
514
0
0

Teks penuh

34;Cap" has not been an active member of the Committee for the past eleven years, his presence has been felt at almost every meeting. Occupational Health, Michigan Department of Health, for the contribution of their original field manual which forms the basis of the First Edition was , and to mr.

Previous Members

Density: The ratio of the mass of a sample of a substance to the volume of the sample. Gravity, specifically: The ratio of the mass of a unit volume of a substance to the mass of the same volume of a standard substance at a standard temperature.

GENERAL PRINCIPLES OF VENTILATION

  • ACCELERATION OF AIR AND HOOD ENTRY
  • AIR FLOW CHARACTERISTICS OF BLOWING
  • INTRODUCTION
  • SUPPLY SYSTEMS
  • EXHAUST SYSTEMS
  • BASIC DEFINITIONS
  • PRINCIPLES OF AIR FLOW

SP can be positive or negative relative to the local atmospheric pressure, but must be measured perpendicular to the air flow. Velocity pressure (VP) is defined as the pressure required to accelerate air from zero velocity to a certain velocity (V) and is proportional to the kinetic energy of the airflow.

FIGURE 1-1. SP,  VP,  and  TP at a point
FIGURE 1-1. SP, VP, and TP at a point

ATMOS'PHE'R1C

  • ACCELERATION OF AIR AND HOOD ENTRY LOSSES
  • DUCT LOSSES
  • MULTIPLE-HOOD EXHAUST SYSTEMS
  • AIR FLOW CHARACTERISTICS OF BLOWING AND EXHAUSTING

This equation gives the friction losses, expressed as "wg per 100 feet of pipe, for standard air with a density of 0.075 Ibm/ftl flowing through an average, clean, circular galvanized pipe with approximately 40 slip joints per 100 feet (k = 0.0005 ft ) The later work of Loeffler(l4) presented equations for use in the "velocity pressure" calculation method. Because the static pressure at the end of the duct must be atmospheric (SPs = 0), the energy principle results in

FIGURE  1~5,  Variation  of SP,  VP,  and TP through  a ventilation  system  [1.7]
FIGURE 1~5, Variation of SP, VP, and TP through a ventilation system [1.7]

GENERAL INDUSTRIAL VENTILATION

  • ADAPTIVE MECHANISM OF THE BODY
  • ACUTEHEATDISORDERS .1 Heat Stroke
  • ASSESSMENT OF HEAT STRESS AND I-IEAT STRAIN
  • VENTILATION SYSTEMS . 2.16 VELOCITY COOUNG
  • PROTECTIVE SUITS FOR SHORT EXPOSURES 2.19 RESPIRATORY HEAT EXCHANGERS
  • REFRIGERATED SUITS 2.21 ENCLOSURES
  • INSULATION REFERENCES
  • INTRODUCTION
  • DILUTION VENTILATION PRINCIPLES
  • DILUTION VENTILATION FOR HEALTH

Dilution ventilation systems typically process large volumes of air using low-pressure fans. The values ​​in the table must be multiplied by the evaporation rate (pts/min) to obtain the effective ventilation rate (Q') (see equation 2.5).

TABLE 2-1. Dilution Air Volumes for Vapors
TABLE 2-1. Dilution Air Volumes for Vapors

34;K)}Z;'A CTORS

SUGCESTED FOR INLET

AND EXHAUST LOCATIONS

  • MIXTURES-DILUTION VENTILATION FOR HEALTH In many cases, the evaporating liquid for which dilution
  • FIRE DILUTION VENTILATION FOR MIXTURES It is common practice to regard the entire mixture as
  • VENTILATION FOR HEAT CONTROL
  • HEAT BALANCE AND EXCHANGE
  • ACUTE HEAT DISORDERS
  • ASSESSMENT OF HEAT STRESS AND HEAT STRAIN
  • WORKER PROTECTION
  • VENTILATION CONTROL
  • VENTILATION SYSTEMS
  • VELOCITY COOLING
  • RADIANT HEAT CONTROL
  • PROTECTIVE SUITS FOR SHORT EXPOSURES For brief exposures to very high temperatures, insulated
  • RESPIRATORY HEAT EXCHANGERS
  • REFRIGERATED SUITS
  • ENCLOSURES
  • INSULATION

In the absence of information to the contrary, the effects of the various hazards should be considered additive. The rate and amount of heat exchange is governed by the basic laws of thermodynamics of heat exchange between objects.

FIGURE 2-2. Contaminant concentration  buildup  IfC I  =  0,  then the equation becomes
FIGURE 2-2. Contaminant concentration buildup IfC I = 0, then the equation becomes

LOCAL EXHAUST HOODS

  • INTRODUCTION
  • CONTAMINANT CHARACTERISTICS
  • HOOD TYPES
  • HOOD DESIGN FACTORS

The hood's primary function is to create an air flow field which effectively captures the pollution and transports it into the hood. However, if the pollution contains large particles which are emitted at a significant speed, the hood should be placed in the path of the emission.

CON EENCF

AME:F{ICAN CONF'ERENCE;

LJDe 10

The design of the slot and plenum is such that the pressure loss through the slot is high compared to the pressure loss through the plenum. Thus, all portions of the slot are subjected to essentially equal suction and the slot velocity will be essentially uniform.

FIGURE 3-6.  Velocity  contours  - plain  circular opening - %  of opening  velocity
FIGURE 3-6. Velocity contours - plain circular opening - % of opening velocity

FREELY SUSPENDED HOOD

SUSPENDED HOODS

INDUSTHIAL BYG IENISTS DATE

F'LOW/C'AP /

AMERICAN CONFERENCE OF GOVERNMENTAL

INDUSTRIAL HYGIENISTS DATE

HOOD TYPES

4- 96 FIGURE 3-11

DISTRIBUTION BY SLOT RE:S[S'TANC

HOOD LOSSES

The hood entry loss (he) can therefore be expressed in terms of hood loss coefficients (Ff) which, multiplied by the slot or duct velocity pressure (VP), will give the entry loss (he) in inches of water. The hood entry loss represents the energy needed to overcome the losses due to air moving through and into the duct.

FIGURE 3-15. Air flow at the vena contracta
FIGURE 3-15. Air flow at the vena contracta

INDUSTHIAL HYG NISTS

NOO]) LOS

  • MINIMUM DUCT VELOCITY
  • SPECIAL HOOD REQUIREMENTS
  • PUSH-PULL VENTILATION
  • HOT PROCESSES

The opening height of the hood should be the same as the width of the extended beam, if possible. VI = the velocity of the hot air column at the hood, fpm As = area of ​​the heat source, ft2.

FIGURE 3-17.  Simple  hood
FIGURE 3-17. Simple hood

AIR CLEANING DEVICES

INTRODUCTION

The degree of removal required, the amount and characteristics of the contaminant to be removed, and the conditions of the air or gas flow will all influence the device selected for a particular application. Air filters are designed to remove low dust concentrations of the magnitude found in atmospheric air.

SELECTION OF DUST COLLECTION EQUIPMENT Dust collection equipment is available in numerous designs

One of the main economies of unit collectors is recycling, for which such equipment may not be suitable. It should be remembered that the visibility of an effluent will be a function of the light-reflecting surface of the effluent material.

DUST COLLECTOR TYPES

An electrostatic precipitator, for example, may be a better choice for a significant initial cost penalty because of the energy savings through its substantially lower pressure drop. Packing and overflow of dry materials in dust pits, floating or sludge-forming characteristics in wet collectors are examples of problems that may be encountered.

DRY TYPE DUST COLLECTORS DUST DISPOSAL

SLIDE GATE

DUST GATE

DRY TYPE DUST COLLECTORS DISCHARGE VALVES

The curtain is held closed by differential pressure until the collected material has built up sufficient height to overcome the pressure.

DOUBU~ DUMP VALVE

DRY TYPE DUST COLLE'CTORS DISCHARGE VAL VES

ELECTROSTATIC PRECIPITATOR HIGH VOLTAGE DESIGN

AMEHICAN CONFEHENCE OF GOVEHNMENTAL

INDUSTHIAL HYG IENISTS DATE

ELECTROSTATIC PRECIPITATOR ,LOW VOLTAGE DESlGN

The efficiency of the cloth as a filter only has significance when the new cloth is put into use for the first time. The combination of dust and collected dust becomes increasingly efficient as the dust cake accumulates on the surface of the fabric.

AMEHICAN CONFEHENCE OF GOVEENMENTAL

INDUSTHIAL HYGIENISTS DATE

PERFORMANCE VS TIME BETWEEN RECONDITIONINGS

FABRIC COLLECTORS 1-88 FIGURE 4-6

Periodically (usually at 3- to 6-hour intervals) the air flow must be stopped to re-condition the fabric. All models collect dust on the outside and have air flow from the outside to the inside of the fabric.

Figure 4-8 shows air flow versus time for a multiple-section  collector.  Each individual section or compartment has an air  flow  versus  time  characteristic  like  that  of the  intermittent  collector,  but  the  total  variation  is  reduced  because
Figure 4-8 shows air flow versus time for a multiple-section collector. Each individual section or compartment has an air flow versus time characteristic like that of the intermittent collector, but the total variation is reduced because

INDUSTRIAL HYG IENISTS DATE

FABRIC COLLECTORS 1-88 FIGURE 4-7

AIR FLOW THROUGH FABRIC COLLECTORS

FABRIC COLLECTORS PULSE JET TYPE

1-88 FIGURE 4-9

EPA-sponsored research(43) has shown that superior performance results from downflow of the contaminated air stream. The flow of water can be driven by the velocity of the air stream or maintained by pumps and channels.

WET TYPE' COLLECTOR

F'OR GASEOUS CONTAMINANT)

WET CENTHIFUGAL

VENTURI SCRUBBER

WET TYPE DUST COLLECTORS (FOR PARTICULATE

CONTAMINANTS)

1-88 FIGURE 4-11

COLLECTING ELEMENTS

TYPICAL WET ORIFICE TYPE COLLECTOR

WET TYPE DUST COLLECTOR (FOR PARTICULATE

1-88 FIGURE 4-12

ADDITIONAL AIDS IN DUST COLLECTOR SELECTION The collection efficiencies of the five basic groups of air

Example: A suitable collector will be selected for a lime kiln to illustrate the use of the scheme. A vertical line from the intersection of the 2.25 grains per cubic feet horizontally and the deviation line to the bottom of the chart will indicate an average wastewater particle size of 6.0 microns.

CONTROL OF MIST, GAS, AND VAPOR CONTAMINANTS

Referring to Figure 4- I 4, the concentration and average particle size of the material leaving the furnace can vary between 3 and 10 grains per cubic foot, with a 5-10 micron range for the mass average particle size. Using the previous deviation line and its horizontal intersection of 0.045 grains per cubic foot gives a vertical line that intersects the average particle size plot at 1.6 microns, the average particle size of the collector wet stream.

LOW PHESSUHE CYCLONE

HIGH EFFICIENCY CENTHIFUGALS

DRY TYPE

CENTRIFUGAL COLLECTORS

RANGE OF PARTICLE SIZE AMERICAN CONFERENCE

OF GOVERNMENTAL

1-88 FIGURE 4-14

  • GASEOUS CONTAMINANT COLLECTORS
  • UNIT COLLECTORS
  • DUST COLLECTING EQUIPMENT COST
  • Notew Collector Collector Collector static static Remark No
    • SELECTION OF AIR FILTRATION EQUIPMENT Air filtration equipment is available in a wide variety of

In most applications, cleaned air is recirculated, although exhaust ducts can be used if the additional resistance is within the capability of the air eliminator. Recirculation water pumps and/or settling tanks may be required, but not included in the equipment price.

Table 4-3.  Dust Collector Selection  Guide
Table 4-3. Dust Collector Selection Guide

UNIT COLLECTOR (FABRIC-SHAKER TYPE)

COST ESTIMATES OF

DUST COLLECTING EQUIPMENT

  • RADIOACTIVE AND HIGH TOXICITY OPERATIONS There are three major requirements for air cleaning equipment
  • EXPLOSION VENTING

The contact does not depend on inertia and the particle is retained on the fiber due to the inherent adhesive forces that exist between the particle and the fiber. High efficiency is essential due to the extremely low tolerances for the amount and concentration of the waste water from the stack and the high cost of the materials handled.

Table  4-5  shows  performance  versus  filter  fiber  size  for  several filters. Note that efficiency increases as fiber diameter  decreases because more small fibers are used per unit volume
Table 4-5 shows performance versus filter fiber size for several filters. Note that efficiency increases as fiber diameter decreases because more small fibers are used per unit volume

This effectively limits the maximum pressure rise to less than the burst pressure of the vessel. In order to select the most reliable, economical and effective means of explosion control, an assessment of the specifics of the exhaust system and the degree of protection required is necessary.

EXHAUST SYSTEM DESIGN PROCEDURE

  • DIFFERENT DUCT MATERIAL FRICTION
  • FRICTION LOSS FOR NON-CIRCULAR DUCTS .5-13 5.13 CORRECTIONS FOR NONSTANDARD DENSITY 5-15
  • CONSTRUCTION GUIDELINES FOR LOCAL
  • INTRODUCTION
  • PRELIMINARY STEPS
  • DESIGN PROCEDURE
  • DUCT SEGMENT CALCULATIONS
  • DISTRIBUTION OF AIR FLOW

Determine the channel area by dividing the design flow rate by the minimum channel velocity. Multiply the designed duct length by the loss coefficient from the tabulated data of Tables 5-5 or 5-6 (lines 23 through 25.) Use of galvanized sheet duct was assumed throughout this chapter.

FIGURE 5-1.  System  duct calculation  parameter location
FIGURE 5-1. System duct calculation parameter location

HOOD NO

VELOCITY PRESSURE METHOD CALCULATION SHEET

TAPERED DUCT SYSTEM

EXTENDED PLENUM SYSTEM

CONVENTIONAL SYSTEM

Sell cleaning rn,Wl

Hopper duel - with pncurnaLic cleaning

  • AIDS TO CALCULATIONS
  • PLENUM EXHAUST SYSTEMS
  • FAN PRESSURE CALCULATIONS
  • CORRECTIONS FOR VELOCITY CHANGES
  • SAMPLE SYSTEM DESIGN
  • DIFFERENT DUCT MATERIAL FRICTION LOSSES The friction loss table, Table 5-5, provides average values
  • FRICTION LOSS FOR NON-CIRCULAR DUCTS Round ducts are preferred for industrial exhaust systems
  • CORRECTIONS FOR NONSTANDARD DENSITY Fan tables and exhaust flow rate requirements assume a

An increase or decrease in static pressure would correspond exactly to a decrease or increase in air velocity pressure. This is equal to -4.2 SP because the static pressure on the suction side of the fan is always negative.

FIGURE 5-6.  Branch  entry velocity correction
FIGURE 5-6. Branch entry velocity correction

PROBLEM 2

1-88 FIGURE 5-8

AIR CLEANING EQUIPMENT

Each exhaust system handling such materials should be provided with a suitable air cleaner as described in Chapter 4. As a general rule, the exhaust fan should be located on the clean air side of such equipment.

EVASE DISCHARGE

Most important is the air pattern as it passes through the building. According to Wilson (5.6), the boundary of the zone of high turbulence (Z2) follows the slope I: I 0 down from the top of the recirculation cavity.

AIR BLEED-INS

CONSTRUCTION GUIDELINES FOR LOCAL EXHAUST SYSTEMS

Unless flanges are used for connections, the duct must be supported near each connection, usually within 2 inches. A straight duct section of at least six equivalent duct diameters should be used when connecting to a fan (see Figure 5-27).

TABLE 5-4. Typical Physical and Chemical Properties of Fabricated  Plastics and  Other Materials
TABLE 5-4. Typical Physical and Chemical Properties of Fabricated Plastics and Other Materials

HOOD ENTRY

A composite hood, such as the slot/plenum shown at right, will have 2 losses, one through the slot and the other through the transition to the duct.

LOSS COEEFICIENTS

1-95 IFIGURE 5-13

INDUSTRJAL YGIEN 'TS DATE

UI1ANC,1 EINTR.Y LOSS

OF' GO VEHNMENTAL,

In :::oieolo SF) for expansion or ethroction use ol:jeiJraic W) (+), (mel lIsliolly SP is In discharge channel of fon, and SP is.

Table  5-5  Tabulated  Friction  Loss Factors
Table 5-5 Tabulated Friction Loss Factors

AMEHICA CONFERENCE

The typical sheet metal fabricator has patterns for channels in 0.5 inch increments up to 5.5 inches in diameter; 1 inch increments from 6 inches through 20 inches and 2 inch increments from 22 inches and larger diameters.

TABLE 5-7A.  Velocity Pressure to  Velocity Conversion - Standard Air
TABLE 5-7A. Velocity Pressure to Velocity Conversion - Standard Air

PSYCHROMETRIC CHART

AVOID ASPECT HATIO (n)

INDUS']" TAL HYGIENISTS

PRINCIPLE'S OF' DUCT' DE'SIGN E'LBOWS

AN CONFERENCE OVE MENTAL

SUDE

PUL OUT CAP

DUCT ENLARGEMENTS

DUCT CONTRACTIONS

SYMMETRICAL WYES

PREFERRED

AVOID

AMERICAN CONFERENCE

PRINCIPLES OF DUCT DESIGN OF GOVERNMENTAL

INDUSTRIAL HYGIENISTS DATE 1-95 FIGURE 5-25

P F'EHHED ACCEPTABLE BHANCF[ EN'I'HY

AMERIC AN CONFERENCE OF GOVERNMEN'TAL

AIRFLOW AROUND BUILDINGS

EFFECTIVE STACK HEIGHT AND WAKE DOWNWASH

4-94 FIGURE 5-29

OFFSET STACK

STACKHEAD

WEATHER CAP

INOT RECOMMENOEOI

STACKHEAD DESIGNS 1-95 FIGURE 5-30

FANS

INTRODUCTION

However, most systems require some powered drive device, such as a fan or an ejector. Selecting an air handling device can be a complex task and the specifier is encouraged to take advantage of all information available from applicable trade associations as well as individual manufacturers.

BASIC DEFINITIONS

Moving air in a ventilation or exhaust system requires energy to overcome system losses. This chapter describes the various air-moving devices used in industrial applications, provides guidelines for selecting the air-moving device for a particular situation, and discusses the proper installation of the air-moving device into the system to achieve the desired performance.

INDUST'RIAL BYG IENISTS DATE

EJE'CT01?S

TERMINOLOGY FOR AXIAL AND TUBULAR CENTRIFUGAL

Reprinted~ from AMCA Publication 201-90, FANS AND SYSTEMS, by permission of the Air Movement and Control Association, Inc.(6.1). Reprinted from AM~A Publication 201-90, FANS AND SYSTEMS, by permission of the Air Movement and Control Association, Inc.(6.1).

TERMINOLOGY FOR CENTRIFUGAL FAN

COMPONENTS

5-92 FIGURE 6-3

FAN SELECTION

Guide rods correct the circular motion imparted to the air by the wheel and improve the pressure characteristics and efficiency of the fan. On larger units, the motor is mounted separately and connected directly to the fan or indirectly through a belt drive.

FIGURE 6-4 (continued). Types of fans:  impeller and  housing design
FIGURE 6-4 (continued). Types of fans: impeller and housing design

DRIVE ARRANGEMENTS FOR CENTRIFUGAL

8 SWSI For belt drive or direct connection Arrangement 1 plus extended base for drive motor. 3 SWSI For belt drive or direct connection One bearing on each side and supported by a fan housing.

DATE  5-92  FIGURE  6-5b
DATE 5-92 FIGURE 6-5b

AMERICAN CONFERENCE OF GOVEHNMENTAL

DRIVE ARRANCEMEWT~C;F'OR

Drive loss is based on the conventional V-belt, which has been the "workhorse" of the drive industry for several decades. Reprinted from AMCA Publication 203-90, FIELD PERFORMANCE MEASUREMENT OF FAN SYSTEMS, by permission of Air Movement and Control Association, Inc.(P.1).

AMERICAN CONFERENCE ESTIMATED BELT OF GOVERNMENTAL DRIVE LOSS

HJGHER BELT SPEEDS TEND TO HAVE HIGHER LOSSES THAN LOWER BELT SPEEDS FOR THE SAME HORSEPOWER.

INDUSTRIAL HYGIENISTS DATE 5-92 FIGURE 6-6

RPM 1 P1

Since these expressions involve relationships between the variables, any appropriate units may be used as long as they are consistent. Size can be represented by any linear dimension, since all must be proportional in homologous series.

ACT[JAL

Care must be taken to apply laws between the same relative points of assessment. So enter the table with the actual volumetric flow at the fan inlet, 1000 acfm and FSP 4 "wg.

Figure  6-10  contains  a  typical  representation  of two  ho- ho-mologous fan  performance curves, PQI and PQ2
Figure 6-10 contains a typical representation of two ho- ho-mologous fan performance curves, PQI and PQ2

PWR =PWR (~)=4.39(0.0375)

FAN INSTALLATION AND MAINTENANCE

LLEL

AMEHICAN CONFERENCE

OF' GO VEENMENTAL

This can result in damage or failure of the fan impeller, housing, bearings or pedestal. The power supply must be shut off and locked in a disconnect near the fan.

FIGURE 6-14.  System  effect factor
FIGURE 6-14. System effect factor

Gambar

FIGURE  1-2. Measurement of SP,  VP,  and TP in  a pressurized  duct
FIGURE 1-4. Volumetric flow rates  in  various situations.  a.  Flow through  a  hood;  b
FIGURE  1~5,  Variation  of SP,  VP,  and TP through  a ventilation  system  [1.7]
TABLE 1-1. Absolute Surface Roughness
+7

Referensi

Dokumen terkait