• Tidak ada hasil yang ditemukan

Introduction of CHINT ATS

N/A
N/A
madeagust

Academic year: 2024

Membagikan "Introduction of CHINT ATS "

Copied!
30
0
0

Teks penuh

(1)

Global marketing Kevin

Sep 2021

Introduction of CHINT ATS

(2)

CONTENTS

目录

Contents

A. What is ATS

B. CHINT ATS Introduction

C. Application of ATS

(3)

What is ATS

(4)

What is ATS

What does ATS mean?

What are functions of ATS ?

What are characteristics of ATS ?

Where is the main application of ATS?

(5)

ATS— Automatic Transfer Switching

Necessity : In order to ensure the continuity and reliability of power supply for important loads 。

Hospital Commercial Industry Factory Fire Protection

What is ATS

Function: when the normal power supply fails, it will automatically transfer to the

standby power supply

(6)

What is ATS

VS

PC Class CB Class

The actuator is the circuit breaker The actuator is a disconnector

Faster conversion time, ≤ 250ms Longer conversion time, 1000~2500ms Without over current protection With over current protection

CB class is mainly concerned with load safety

PC class mainly concerned with continuous power supply

(7)

Differences between PC and CB class

PC Class

(Disconnector type) CB Class

(Circuit breaker tpye)

Overload and shortcircuit

protection NO YES

Actuator Disconnector Circuit breaker

Driving mechanism Electromagnetic coil Motor

Action time 100~250ms 1000~2500ms

Reliability High Low

Volume 1 / 2 of the same level of CB Big

Price Expensive (Same level) Cheap

Feature Ensure continuityof power supply Ensure safetyof power supply Application occasion Important occasions

motor load, fire pump, fire elevator, fire

exhaust fan General occasions

(8)

ATS electrical symbols

PC Class CB Class

(9)

Self-throwing

& Self-reset

添加标题

What is ATS

ATS has 3 conversion methods

Self-throwing

& Not Self-reset Self-throwing

& Self-reset

Grid to Grid

Self-throwing means when the normal power fails, the power supply will automatically switch to the standby power supply Self reset means that when the normal power returns to normal, the power supply will automatically switch from the

standby to the normal power

Grid to Grid Grid to Generator

(10)

CHINT ATS Introduction

(11)

ATS

PC Class CB Class

Un:AC 400V

In:10~630A NZ7

NXZM

Un:AC 380V

In:16~3150A NH40SZ

NXZ

NXZB

Un:AC 400V

In:63~800A

Un:AC 400V

In:20~63A

Un:AC 400V

In:80~630A Old Generation

NEXT Series

CHINT ATS

(12)

Chint NXZ

Automatic Transfer Switch Equipment

The Next Reliable Choice

(13)

NXZ Series ATS

NXZ

Electric Equipment Grade :PCclass

Frame size:125A/250A/630A

Rated voltage: 400/415V

With large screen display, communication functions

CE and KEMAcertification

NXZM

Electric Equipment Grade :CB class(NXZM)

Frame size :63A 125A/160A/250A /320A/400A 630A/800A

Rated voltage: 400/415V

CEand KEMAcertification

NXZB-63

Electric Equipment Grade :CBclass(NXZB)

Frame size: 63A

Rated voltage: 400/415V

CE and KEMA certification

(14)

NXZ Series ATS

Rated limit short-circuit current Iq (kA): 100 kA Rated impulse withstand voltage Uimp (kV): 8kV

Transfer/ Return delay time: 0~300s adjustable Installation mode: Integrated, Split

Protection: Phase failure, Under/Over voltage,

Generator control, Fire control linkage Communication function (Optional), LED/LCD display

Highlights of NXZ series

(15)

Generator Control

 Only for grid-generator mode

 When the normal power fails, ATS will send a closing signal to the generator

Generator Grid

 When the ATS receives the fire signal, the ATS will break the normal power and the backup power at the same time, Then output a feedback signal

fire signal

LOAD LOAD

NXZ Series ATS

Fire Control linkage

(16)

NXZ Competitor

The volume of 125A 250A frame

product reduces by 40% The length of the whole series has been shortened by 80~205mm VS

-15%

-40%

NXZM NZ7 VS

NXZ Series ATS

(17)

NXZ Series ATS

Has the function of isolating padlock

(18)

NXZ Series ATS

Large screen display and can also be installed separately

(19)

NXZ Series ATS

Manual/automatic transfer to prevent manual handle from misoperation

Add handle placement position to facilitate handle storage

(20)

Controller multi-function integration, users can flexibly choose the desired function

NXZ Series ATS

RS485 communication Features

3

conversion modes can be set

4

delay time values can be set

4

conversion voltage thresholds can be set

RS485communication

(21)

NZ7

 Electric Equipment Grade:CB class

 Un:AC 400V

 In:63~630A

 Ui: 800V Uimp: 8kV

 Protection:overload、short circuit、under voltage、phase loss、over voltage

 Transfer mode: R / S / F

 Transfer delay: 1~180s adjustable

Old generation ATS

NH40SZ

 Electric Equipment Grade:PC class

 Un:AC 380V

 In:16~3150A

 Protection:under voltage、phase loss、

over voltage

 Transfer mode: R / S / F

 Transfer delay: 1~999s adjustable

(22)

ACB ATS Controller

2 power controller 3 power controller Bus connect controller This controller can be matched with NA1 or NXA for ATS system

NZQ7A NZQ7B NZQ7C

(23)

Application of ATS

(24)

ATS application scenarios

It is widely used in

Real estate Fire protection Data center & Base station

Industrial plant Hospital & Airport

And other important places where power failure is not allowed to realize

continuous power supply

(25)

NXZ PC ATSE NXM NXM

NXB

NXB-63 NU6

Fire Blowers

Fire alarm

Fire pump Fire shutter door

Emergency lighting

Grounding Surge protection

NXM Standby power

ATS Application in Fire Protection

RQ V/F 3M

NXM NXC NXR NJR2 NVF300 NXM NXC NXR

RQ V/F 3M

NXM NXC NXR NJR2 NVF300

Fire pump Power Grid

Generator

The fire load power supply generally

adopts PC class ASTE for switching

(26)

G

NH40SZ PCclass ATS Generator

ATS application in power supply

NXA

NZ7 CBclass ATS

Power grid

NXM

NXB

NXB-63 NXU NXM

NXM

NZQ7A

NM8N

NM8N

Different types of ATS work together to ensure

the continuity of power supply

(27)

ATS typical application

Split installation NXZ

(28)

ATS typical application

NH40SZ in Fire protection NZ7 in Factory power distribution NZ7 in Mining industry

(29)

Other application of ATS

(30)

THANKS

Referensi