Global marketing Kevin
Sep 2021Introduction of CHINT ATS
CONTENTS
目录
Contents
A. What is ATS
B. CHINT ATS Introduction
C. Application of ATS
What is ATS
?
What is ATS
What does ATS mean?
What are functions of ATS ?
What are characteristics of ATS ?
Where is the main application of ATS?
ATS— Automatic Transfer Switching
Necessity : In order to ensure the continuity and reliability of power supply for important loads 。
Hospital Commercial Industry Factory Fire Protection
What is ATS
Function: when the normal power supply fails, it will automatically transfer to the
standby power supply
What is ATS
VS
PC Class CB Class
The actuator is the circuit breaker The actuator is a disconnector
Faster conversion time, ≤ 250ms Longer conversion time, 1000~2500ms Without over current protection With over current protection
CB class is mainly concerned with load safety
PC class mainly concerned with continuous power supply
Differences between PC and CB class
PC Class
(Disconnector type) CB Class
(Circuit breaker tpye)
Overload and shortcircuit
protection NO YES
Actuator Disconnector Circuit breaker
Driving mechanism Electromagnetic coil Motor
Action time 100~250ms 1000~2500ms
Reliability High Low
Volume 1 / 2 of the same level of CB Big
Price Expensive (Same level) Cheap
Feature Ensure continuityof power supply Ensure safetyof power supply Application occasion Important occasions
motor load, fire pump, fire elevator, fire
exhaust fan General occasions
ATS electrical symbols
PC Class CB Class
Self-throwing
& Self-reset
添加标题What is ATS
ATS has 3 conversion methods
Self-throwing
& Not Self-reset Self-throwing
& Self-reset
Grid to Grid
Self-throwing means when the normal power fails, the power supply will automatically switch to the standby power supply Self reset means that when the normal power returns to normal, the power supply will automatically switch from the
standby to the normal power
Grid to Grid Grid to Generator
CHINT ATS Introduction
ATS
PC Class CB Class
Un:AC 400V
In:10~630A NZ7
NXZM
Un:AC 380V
In:16~3150A NH40SZ
NXZ
NXZB
Un:AC 400V
In:63~800A
Un:AC 400V
In:20~63A
Un:AC 400V
In:80~630A Old Generation
NEXT Series
CHINT ATS
Chint NXZ
Automatic Transfer Switch Equipment
The Next Reliable Choice
NXZ Series ATS
NXZ
Electric Equipment Grade :PCclass
Frame size:125A/250A/630A
Rated voltage: 400/415V
With large screen display, communication functions
CE and KEMAcertification
NXZM
Electric Equipment Grade :CB class(NXZM)
Frame size :63A 125A/160A/250A /320A/400A 630A/800A
Rated voltage: 400/415V
CEand KEMAcertification
NXZB-63
Electric Equipment Grade :CBclass(NXZB)
Frame size: 63A
Rated voltage: 400/415V
CE and KEMA certification
NXZ Series ATS
Rated limit short-circuit current Iq (kA): 100 kA Rated impulse withstand voltage Uimp (kV): 8kV
Transfer/ Return delay time: 0~300s adjustable Installation mode: Integrated, Split
Protection: Phase failure, Under/Over voltage,
Generator control, Fire control linkage Communication function (Optional), LED/LCD display
Highlights of NXZ series
Generator Control
Only for grid-generator mode
When the normal power fails, ATS will send a closing signal to the generator
Generator Grid
When the ATS receives the fire signal, the ATS will break the normal power and the backup power at the same time, Then output a feedback signal
fire signal
LOAD LOAD
NXZ Series ATS
Fire Control linkage
NXZ Competitor
The volume of 125A 250A frame
product reduces by 40% The length of the whole series has been shortened by 80~205mm VS
-15%
-40%
NXZM NZ7 VS
NXZ Series ATS
NXZ Series ATS
Has the function of isolating padlock
NXZ Series ATS
Large screen display and can also be installed separately
NXZ Series ATS
Manual/automatic transfer to prevent manual handle from misoperation
Add handle placement position to facilitate handle storage
Controller multi-function integration, users can flexibly choose the desired function
NXZ Series ATS
RS485 communication Features
3
conversion modes can be set4
delay time values can be set4
conversion voltage thresholds can be setRS485communication
NZ7
Electric Equipment Grade:CB class
Un:AC 400V
In:63~630A
Ui: 800V Uimp: 8kV
Protection:overload、short circuit、under voltage、phase loss、over voltage
Transfer mode: R / S / F
Transfer delay: 1~180s adjustable
Old generation ATS
NH40SZ
Electric Equipment Grade:PC class
Un:AC 380V
In:16~3150A
Protection:under voltage、phase loss、
over voltage
Transfer mode: R / S / F
Transfer delay: 1~999s adjustable
ACB ATS Controller
2 power controller 3 power controller Bus connect controller This controller can be matched with NA1 or NXA for ATS system
NZQ7A NZQ7B NZQ7C
Application of ATS
ATS application scenarios
It is widely used in
Real estate Fire protection Data center & Base station
Industrial plant Hospital & Airport
And other important places where power failure is not allowed to realize
continuous power supply
NXZ PC ATSE NXM NXM
NXB
NXB-63 NU6
Fire Blowers
Fire alarm
Fire pump Fire shutter door
Emergency lighting
Grounding Surge protection
NXM Standby power
ATS Application in Fire Protection
RQ V/F 3M~
NXM NXC NXR NJR2 NVF300 NXM NXC NXR
RQ V/F 3M~
NXM NXC NXR NJR2 NVF300
Fire pump Power Grid
Generator
The fire load power supply generally
adopts PC class ASTE for switching
G
NH40SZ PCclass ATS Generator
ATS application in power supply
NXA
NZ7 CBclass ATS
Power grid
NXM
NXB
NXB-63 NXU NXM
NXM
NZQ7A
NM8N
NM8N
Different types of ATS work together to ensure
the continuity of power supply
ATS typical application
Split installation NXZ
ATS typical application
NH40SZ in Fire protection NZ7 in Factory power distribution NZ7 in Mining industry
Other application of ATS
THANKS