Netquality report

Analysis EN 50160

Signatur

Company: UPI

Location: BANDUNG

Measuring point: POWER QUQLLITY Device name: 00000C3A UMG 510

Database: C:\Documents and Settings\Ase Subandi\.pas\pasdb Analysis Timeframe: March 14, 2010 12:00 AM - March 15, 2010 11:59 PM Analysis date: March 26, 2010

Creator: E ASE SUBANDI

Analysis application: PAS 1.5.0(2008-07-29) build: 5607

Comment: POWER QUALITY 3

Overview

1. Flicker Failed Page2

2. Supply frequency OK Page4

3. Harmonics OK Page6

4. THD OK Page10

5. Symmetry Page12

6. Supply voltage OK Page13

7. Voltage drop Page15

8. Transients Page17

Main input

Nominal voltage 220V

Nominal current 0A

Frequency 50Hz

Event limits Sag: 90%; Swell: 110%; Interruption: 5%; Absolut voltage change:

Off

Transient limits Trns: 28%; Peak: 141%

Auxillary input

Nominal voltage 0V

Nominal current 0A

Event limits Sag: Off; Swell: Off; Interruption: Off; Absolut voltage change: Off

Transient limits Trns: Off; Peak: Off

(2)

Flicker

In 82.6% of the time the flicker was above 1.0.

Flicker

Name Average Minimum Maximum

Long term flicker L1 1.25 0.87 3.27

Errors

No errors occurred

Warnings

No Warnings reported

(3)

Diagram: Long term flicker L1

0.80

0.90

1.00

1.10

1.20

1.30

1.40

1.50

1.60

1.70

1.80

1.90

2.00

2.10

2.20

2.30

2.40

2.50

2.60

2.70

2.80

2.90

3.00

3.10

3.20

[] 3.30

3.40 1:00:00 AM 3/14/104:00:00 AM

7:00:00 AM 3/14/1010:00:00 AM 1:00:00 PM 3/14/104:00:00 PM 7:00:00 PM 3/14/1010:00:00 PM 1:00:00 AM 3/15/104:00:00 AM 7:00:00 AM 3/15/1010:00:00 AM 1:00:00 PM 3/15/104:00:00 PM 7:00:00 PM 3/15/1010:00:00 PM

Diagram: Long term flicker L1 Long term flicker L1[00000C3A UMG 510]

(4)

Supply frequency

In 99.4% of the time the frequency was between 49.5hz and 50.5hz.

Supply frequency

Name Average Minimum Maximum

Frequency 50.30Hz 49.19Hz 50.54Hz

Errors

No errors occurred

Warnings

Missing time sequence from 3/14/10 12:00:00 AM to 3/14/10 6:00:00 AM Missing time sequence from 3/15/10 6:00:00 AM to 3/15/10 11:59:59 PM

(5)

Histogram: Frequency

050

100

150

200

250

300

350

400

450

500

550

600

650

700

750 49.15 Hz 49.20 Hz

49.25 Hz 49.30 Hz 49.35 Hz 49.40 Hz 49.45 Hz 49.50 Hz 49.55 Hz 49.60 Hz 49.65 Hz 49.70 Hz 49.75 Hz 49.80 Hz 49.85 Hz 49.90 Hz 49.95 Hz 50.00 Hz 50.05 Hz 50.10 Hz 50.15 Hz 50.20 Hz 50.25 Hz 50.30 Hz 50.35 Hz 50.40 Hz 50.45 Hz 50.50 Hz

50.55 Hz

Histogram: Frequency Frequency(3/14/10 6:00:00 AM - 3/15/10 6:00:00 AM)[00000C3A UMG 510]

(6)

Harmonics

2. Voltageharmonics

Name Average Minimum Maximum

Voltageharmonics L1(rel) 0.24% 0.05% 0.29%

3. Voltageharmonics

Name Average Minimum Maximum

Voltageharmonics L1(rel) 3.51% 1.77% 3.61%

4. Voltageharmonics

Name Average Minimum Maximum

Voltageharmonics L1(rel) 0.09% 0.03% 0.11%

5. Voltageharmonics

Name Average Minimum Maximum

Voltageharmonics L1(rel) 3.00% 2.08% 3.05%

6. Voltageharmonics

Name Average Minimum Maximum

Voltageharmonics L1(rel) 0.07% 0.03% 0.07%

7. Voltageharmonics

Name Average Minimum Maximum

Voltageharmonics L1(rel) 1.03% 0.56% 1.11%

8. Voltageharmonics

Name Average Minimum Maximum

Voltageharmonics L1(rel) 0.05% 0.03% 0.06%

9. Voltageharmonics

Name Average Minimum Maximum

Voltageharmonics L1(rel) 1.01% 0.38% 1.08%

10. Voltageharmonics

Name Average Minimum Maximum

Voltageharmonics L1(rel) 0.04% 0.02% 0.05%

(7)

11. Voltageharmonics

Name Average Minimum Maximum

Voltageharmonics L1(rel) 0.29% 0.05% 0.31%

12. Voltageharmonics

Name Average Minimum Maximum

Voltageharmonics L1(rel) 0.03% 0.02% 0.04%

13. Voltageharmonics

Name Average Minimum Maximum

Voltageharmonics L1(rel) 0.52% 0.10% 0.56%

14. Voltageharmonics

Name Average Minimum Maximum

Voltageharmonics L1(rel) 0.03% 0.02% 0.04%

15. Voltageharmonics

Name Average Minimum Maximum

Voltageharmonics L1(rel) 0.47% 0.13% 0.51%

16. Voltageharmonics

Name Average Minimum Maximum

Voltageharmonics L1(rel) 0.03% 0.02% 0.03%

17. Voltageharmonics

Name Average Minimum Maximum

Voltageharmonics L1(rel) 0.26% 0.17% 0.28%

18. Voltageharmonics

Name Average Minimum Maximum

Voltageharmonics L1(rel) 0.03% 0.02% 0.03%

19. Voltageharmonics

Name Average Minimum Maximum

Voltageharmonics L1(rel) 0.26% 0.12% 0.28%

20. Voltageharmonics

Name Average Minimum Maximum

Voltageharmonics L1(rel) 0.03% 0.02% 0.03%

(8)

21. Voltageharmonics

Name Average Minimum Maximum

Voltageharmonics L1(rel) 0.34% 0.13% 0.35%

22. Voltageharmonics

Name Average Minimum Maximum

Voltageharmonics L1(rel) 0.02% 0.02% 0.03%

23. Voltageharmonics

Name Average Minimum Maximum

Voltageharmonics L1(rel) 0.30% 0.15% 0.31%

24. Voltageharmonics

Name Average Minimum Maximum

Voltageharmonics L1(rel) 0.02% 0.01% 0.03%

25. Voltageharmonics

Name Average Minimum Maximum

Voltageharmonics L1(rel) 0.24% 0.09% 0.25%

Errors

No errors occurred

Warnings

No Warnings reported

(9)

Harmonics

0.00

0.50

1.00

1.50

2.00

2.50

3.00

3.50

4.00

4.50

5.00

5.50

6.00[%] 6.50

7.00 0 1

2 3

4 5

6 7

8 9

10 11

12 13

14 15

16 17

18 19

20 21

22 23

24 25

26

Harmonics Voltageharmonics L1(rel)[00000C3A UMG 510]

(10)

THD

In 100.0% of the time the THD was between 0.0% and 8.0%.

THD

Name Average Minimum Maximum

Total harmonic distortion voltage L1 4.64% 3.35% 4.65%

Errors

No errors occurred

Warnings

Missing time sequence from 3/14/10 12:00:00 AM to 3/14/10 6:00:00 AM Missing time sequence from 3/15/10 6:00:00 AM to 3/15/10 11:59:59 PM

(11)

Histograms of THDs

0

0

1

2

2

2

3

4

4

4

5

6

6

6

7

8

8

8

910

10 0.00 % 0.20 %

0.40 % 0.60 % 0.80 % 1.00 % 1.20 % 1.40 % 1.60 % 1.80 % 2.00 % 2.20 % 2.40 % 2.60 % 2.80 % 3.00 % 3.20 % 3.40 % 3.60 % 3.80 % 4.00 % 4.20 % 4.40 % 4.60 % 4.80 % 5.00 % 5.20 % 5.40 % 5.60 % 5.80 % 6.00 % 6.20 % 6.40 % 6.60 % 6.80 % 7.00 % 7.20 % 7.40 % 7.60 % 7.80 % 8.00 % 8.20 % 8.40 % 8.60 %

8.80 %

Histograms of THDs Total harmonic distortion voltage L1(3/14/10 6:00:00 AM - 3/15/10 6:00:00 AM)[00000C3A UMG 510]

(12)

Symmetry

Errors

Missing Value: Spannungsunsymmetrie with 600sec average for 1 week as Histogram.

Warnings

Missing time sequence from 3/14/10 12:00:00 AM to 3/15/10 11:59:59 PM

(13)

Supply voltage

In 100.0% of the time the voltage was between 198.0V and 242.0V.

Supply voltage

Name Average Minimum Maximum

Voltage L1 228.78V 211.98V 229.70V

Errors

No errors occurred

Warnings

Missing time sequence from 3/14/10 12:00:00 AM to 3/14/10 6:00:00 AM Missing time sequence from 3/15/10 6:00:00 AM to 3/15/10 11:59:59 PM

(14)

Histograms of voltages

200.00 V

202.00 V 204.00 V 206.00 V 208.00 V 210.00 V 212.00 V 214.00 V 216.00 V 218.00 V 220.00 V 222.00 V 224.00 V 226.00 V 228.00 V 230.00 V 232.00 V 234.00 V 236.00 V 238.00 V 240.00 V 242.00 V 244.00 V

246.00 V

Histograms of voltages

(15)

Voltage drop

5 events have been found.

Undervoltage

Time Input Average Minimum Duration

3/14/10 10:12:37 AM '401 L1 157.53V 120.81V 20 ms

3/14/10 10:12:37 AM '422 L1 1.66V 0.05V 80 ms

3/14/10 10:12:37 AM '502 L1 102.67V 46.23V 20 ms

3/15/10 7:40:19 PM '010 L1 198.65V 196.46V 221 ms

3/15/10 7:46:18 PM '451 L1 199.13V 197.63V 200 ms

Errors

No errors occurred

Warnings

No Warnings reported

(16)

Diagram: Voltage drop

12:00:00 PM

2:00:00 PM 3/14/104:00:00 PM 6:00:00 PM 3/14/108:00:00 PM 10:00:00 PM 3/14/1012:00:00 AM 2:00:00 AM 3/15/104:00:00 AM 6:00:00 AM 3/15/108:00:00 AM 10:00:00 AM 3/15/1012:00:00 PM 2:00:00 PM 3/15/104:00:00 PM 6:00:00 PM 3/15/108:00:00 PM

Diagram: Voltage drop

(17)

Transients

2 transients have been found.

Time Type

3/14/10 10:12:37 AM '509 Transient (trns L1) 3/14/10 10:12:37 AM '509 3/15/10 4:06:52 PM '837 Transient (trns L1) 3/15/10 4:06:52 PM '837

Errors

No errors occurred

Warnings

No Warnings reported

(18)

Transients

2:00:00 PM 3/14/104:00:00 PM 6:00:00 PM 3/14/108:00:00 PM 10:00:00 PM 3/14/1012:00:00 AM 2:00:00 AM 3/15/104:00:00 AM 6:00:00 AM 3/15/108:00:00 AM 10:00:00 AM 3/15/1012:00:00 PM 2:00:00 PM 3/15/104:00:00 PM

Transients

Referensi

Dokumen terkait