Maintenance factor 0.80 (fixed) Reflection factors Ceiling: 70.0 %,

Walls: 50.0 %, Floor: 20.0 % Ground area 502.29 m²

Wall zone 0.081 m

Height Working plane 0.750 m Mounting height 4.000 m Clearance height 5.500 m

(2)

Summary

Results

Symbol Calculated Target Check Index

Working plane Ēperpendicular 588 lx ≥ 500 lx WP2

Uo (g1) 0.44 ≥ 0.60 WP2

Lighting power density 4.95 W/m² – 0.84 W/m²/100 lx –

Glare valuation(1) RUG, max 18 ≤ 19

Energy estimation(2) Consumption 6059 kWh/a max. 17600 kWh/a

Room Lighting power density 4.87 W/m² –

0.83 W/m²/100 lx –

(1) Based on a rectangular space of 28.170 m x 18.110 m and SHR of 0.25.

(2) Calculated using DIN:18599-4.

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

18 34.0 W 5000 lm 147.0 lm/W

72 Philips RC530B PSD W8L150 1 xLED50S/940 OC

(3)
(4)

Luminaire layout plan

Manufacturer Philips

Article name RC530B PSD W8L150 1 xLED50S/940 OC

Fitting 1x LED50S/940

P 34.0 W

ΦLuminaire 5000 lm

72 x Philips RC530B PSD W8L150 1 xLED50S/940 OC

Type Field Arrangement

1st luminaire (X/Y/Z) 1.431 m / 1.497 m / 4.000 m

X-direction 12 pcs., Centre - centre, Distances not equal

Y-direction 6 pcs., Centre - centre, Distances not equal

Arrangement A1

X Y Mounting

height

Luminaire

1.430 m 16.591 m 4.000 m 1

3.920 m 16.591 m 4.000 m 2

6.410 m 16.591 m 4.000 m 3

8.900 m 16.592 m 4.000 m 4

11.390 m 16.592 m 4.000 m 5

13.880 m 16.592 m 4.000 m 6

16.352 m 16.592 m 4.000 m 7

18.824 m 16.593 m 4.000 m 8

21.180 m 16.593 m 4.000 m 9

23.624 m 16.593 m 4.000 m 10

25.680 m 16.593 m 4.000 m 11

27.330 m 16.594 m 4.000 m 12

1.430 m 13.572 m 4.000 m 13

(5)

X Y Mounting height

Luminaire

3.920 m 13.572 m 4.000 m 14

6.410 m 13.572 m 4.000 m 15

8.900 m 13.573 m 4.000 m 16

11.390 m 13.573 m 4.000 m 17

13.880 m 13.573 m 4.000 m 18

16.352 m 13.573 m 4.000 m 19

18.825 m 13.574 m 4.000 m 20

21.180 m 13.574 m 4.000 m 21

23.625 m 13.574 m 4.000 m 22

25.680 m 13.575 m 4.000 m 23

27.330 m 13.575 m 4.000 m 24

1.430 m 10.553 m 4.000 m 25

3.920 m 10.553 m 4.000 m 26

6.410 m 10.554 m 4.000 m 27

8.900 m 10.554 m 4.000 m 28

11.390 m 10.554 m 4.000 m 29

13.880 m 10.554 m 4.000 m 30

16.353 m 10.555 m 4.000 m 31

18.825 m 10.555 m 4.000 m 32

21.180 m 10.555 m 4.000 m 33

23.625 m 10.555 m 4.000 m 34

25.680 m 10.556 m 4.000 m 35

27.330 m 10.556 m 4.000 m 36

1.431 m 7.534 m 4.000 m 37

(6)

Luminaire layout plan

X Y Mounting

height

Luminaire

3.921 m 7.534 m 4.000 m 38

6.411 m 7.535 m 4.000 m 39

8.901 m 7.535 m 4.000 m 40

11.391 m 7.535 m 4.000 m 41

13.881 m 7.536 m 4.000 m 42

16.353 m 7.536 m 4.000 m 43

18.825 m 7.536 m 4.000 m 44

21.181 m 7.536 m 4.000 m 45

23.625 m 7.537 m 4.000 m 46

25.681 m 7.537 m 4.000 m 47

27.331 m 7.537 m 4.000 m 48

1.431 m 4.515 m 4.000 m 49

3.921 m 4.516 m 4.000 m 50

6.411 m 4.516 m 4.000 m 51

8.901 m 4.516 m 4.000 m 52

11.391 m 4.516 m 4.000 m 53

13.881 m 4.517 m 4.000 m 54

16.353 m 4.517 m 4.000 m 55

18.826 m 4.517 m 4.000 m 56

21.181 m 4.517 m 4.000 m 57

23.626 m 4.518 m 4.000 m 58

25.681 m 4.518 m 4.000 m 59

27.331 m 4.518 m 4.000 m 60

1.431 m 1.497 m 4.000 m 61

(7)

X Y Mounting height

Luminaire

3.921 m 1.497 m 4.000 m 62

6.411 m 1.497 m 4.000 m 63

8.901 m 1.497 m 4.000 m 64

11.391 m 1.498 m 4.000 m 65

13.881 m 1.498 m 4.000 m 66

16.354 m 1.498 m 4.000 m 67

18.826 m 1.498 m 4.000 m 68

21.181 m 1.499 m 4.000 m 69

23.626 m 1.499 m 4.000 m 70

25.681 m 1.499 m 4.000 m 71

27.331 m 1.499 m 4.000 m 72

(8)

Luminaire list

Φtotal

360000 lm

Ptotal

2448.0 W

Luminous efficacy 147.1 lm/W

Luminous efficacy Φ

P pcs. Manufacturer Article No. Article name

34.0 W 5000 lm 147.0 lm/W

72 Philips RC530B PSD W8L150 1 xLED50S/940 OC

(9)
(10)

Calculation objects

Working planes

Properties Ē

(Target)

Emin Emax Uo (g1) (Target)

g2 Index

Working plane (Data Hall )

Perpendicular illuminance (adaptive) Height: 0.750 m, Wall zone: 0.081 m

588 lx (≥ 500 lx)

258 lx 855 lx 0.44

(≥ 0.60)

0.30 WP2

Surface result objects

Properties ∅ min max Uo (g1) g2 Index

Surface result object 1 (Floor/ceiling) Perpendicular illuminance (adaptive) Height: 0.000 m

569 lx 189 lx 822 lx 0.33 0.23 RS1

Surface result object 1 (Floor/ceiling) Luminance

Height: 0.000 m

36.2 cd/m² 12.0 cd/m² 52.3 cd/m² 0.33 0.23 RS1

Calculation surfaces

Properties Ē Emin Emax Uo (g1) g2 Index

Calculation surface 3 Perpendicular illuminance Height: 0.000 m

390 lx 321 lx 456 lx 0.82 0.70 CG1

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

(11)

Properties Ē (Target)

Emin Emax Uo (g1) (Target)

g2 Index

Working plane (Data Hall )

Perpendicular illuminance (adaptive) Height: 0.750 m, Wall zone: 0.081 m

588 lx (≥ 500 lx)

258 lx 855 lx 0.44

(≥ 0.60)

0.30 WP2

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

(12)

Surface result object 1 (Floor/ceiling)

Properties Ē Emin Emax Uo (g1) g2 Index

Surface result object 1 (Floor/ceiling) Perpendicular illuminance (adaptive) Height: 0.000 m

569 lx 189 lx 822 lx 0.33 0.23 RS1

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

(13)

Properties ∅ min max Uo (g1) g2 Index Surface result object 1 (Floor/ceiling)

Luminance Height: 0.000 m

36.2 cd/m² 12.0 cd/m² 52.3 cd/m² 0.33 0.23 RS1

Utilisation profile: DIALux presetting (5.26.2 Standard (office))

(14)

Calculation surface 3

Properties Ē Emin Emax Uo (g1) g2 Index

Calculation surface 3 Perpendicular illuminance Height: 0.000 m

390 lx 321 lx 456 lx 0.82 0.70 CG1

Utilisation profile: DIALux presetting (5.26.2 Standard (office))