Innovating Level Controls Since 1984

Instruction and Maintenance Manual Techtrol Ultrasonic Level System

for Liquid, 'TUS'- Utratrol

Pre Installation Check :

1. Unpack the box carefully and visually check & ensure that transmitter is not damaged in transit.

2. Ensure that the supplied transmitter is as per ordered.

Installation Guidelines :

Ensure the following during location and mounting of transmitter.

1. Installation must be carried out by trained personnel

2. Ensure that the ambient temperature and process temperature must be within specified limits.

1. In outdoor location, transmitter electronics should be protected from severe weather conditions and direct sunlight, by use of canopy.

2. The location should not have any strong wind/ breeze or turbulence in vessel which may disturb ultrasonic signal.

3. Distance between tank wall and transmitters center line should be at least 110mm per meter of its measuring range. (fig 3)

4. Obstructions like( ladder, agitator, jutting tank wall) should not come in the way of ultrasonic beam (fig 4)

5. In closed tank with concave cover, transmitter should be mounted 'off-centre' and 'vertical' to minimize creation of unwanted echoes.

(fig 5)

1. In case of excessive turbulence in liquid, use of still well is suggested.

2. Not suitable for application where heavy condensation could form on the transducer face.

3. Not suitable for foaming liquids.

General

Location of transmitter

Liquid surface conditions

þ þ

Instruction manual should be read & understood before installation of gauge.

Installation should be carried out by qualified & experienced personnel.

Caution

Fig. 1

Dimensional Drawing

Ø96 123

Ø90

85237

4"NB, 150#

PP FLANGE

TUS-Ultratrol- Range : 0.4 - m Output: 4-20 mA Supply: 24VDC

Max Temp 70°C: Enclosure

Cable gland

Transducer face

257

Ø62

157100 3"NB, 150#

PP FLANGE Ø96

123

TUS-Ultratrol- Range : 0.4 - m Output: 4-20 mA Supply: 24VDC Max Temp 70°C:

Transducer face Enclosure

Cable gland

Ultratrol 3 Ultratrol 1 & 2

FRP

Nozzle Canopy Sunlight

Ultratrol

TANK

max 3°

Ultratrol

110mm/m

Fig. 2 Fig. 3

Agitator Ultratrol

TANK Staircase

Jutting wall

Fig. 4

Fig. 5

(2)

Mounting Considerations

1. Mount away from any source of electrical noise such as a variable speed drive or other high powered electrical devices.

2. Transmitter process flange should be of PP MOC (non –metallic) and equivalent counter flange on tank. (Fig. 6) 3. When mounted on a nozzle, ensure that the transducer face protrudes at least 5mm into the tank. (Fig. 6) If this is not

possible, ensure nozzle dimensions are as indicated in (Fig. 7)

4. The mounting nozzle should be welded in- plumb to the tank and be free from internal weld beads or other projections.

5. Ensure maximum liquid level does not come with in blanking distance (dead zone) of x'mitter..

6. Fixing of bracket to the tank should be at right angle, to ensure mounting of transmitter is vertical. (Fig. 8 & 9) 7. Mount transmitter perpendicular to liquid surface to ensure good echo from liquid surface.

Innovating Level Controls Since 1984

Fig. 7

Ultratrol

Nozzle

Flange PP (non -metallic) Transducer

face

3" or 4"NB max

0.35mtr

Sch-10 Nozzle

Fig. 6

Nozzle

SS Angle 400

500

425

Mtg. plate

Fig. 8 Bracket

BD : Blanking Distance, E : Total Range from X'mitter Face,

F : Measuring Span,

D : Distance, L : Level ( E - D )

Mounting of Ultratrol with flange

Mounting of Ultratrol on bracket

Bracket Ultratrol 20mA

(100%)

4mA (0%)

E F L

BD 0.11m/m

D Ultratrol

Fig. 9

Termination and Wiring :

1. During wiring of transmitter, supply should be kept off.

2. Open the enclosure cover and wire transmitter to power supply (16 to 30VDC) with correct polarity by using 2 core screen cable and its output 4-20 mA can be used further to interface with PLC or SCADA. (fig 10)

3. Wire transmitter along with Techtrol Indicators and Controller (TUIC/TLIC) as shown in fig 11.

4. Wire transmitter along with Techtrol Loop Powered Indicator as shown in fig 12.

5. Max. cable run from Ultratrol to control room should be less than 100mtrs.

Dist 0.40 m Heig 1.00 m

OK SET

_ +

mA + _ 24 VDC

Ultratrol LOAD

Fig. 10

Dist 0.40 m Heig 1.00 m

OK SET

_ +

mA

Ultratrol

TUIC/TLIC

+ -

N

L E

90- 270VAC

RL1 RL2 RL3 RL4

Potential Free Realy Contacts

To x'mitter

Fig. 11

4-20mA DC

+ -

24VDC

x'mitterTo 24 VDC Loop Powered

TLPI

Dist 0.40 m Heig 1.00 m

SET OK

Ultratrol LOAD

Fig. 12 Cable routing Fig. 13

Precautions :

1. Before switching on supply, ensure correct polarity of wiring.

2. Ensure transmitter enclosure is closed properly with its cover & gasket.

3. After wiring, ensure cable is routed downward before cable gland to prevent seepage of water in the enclosure. (fig 13) 4. Ensure cable should be full tight in gland ensuring zero gap between 'cable gland ID' and 'cable OD'.

Programming :

Transmitter is programmed through keys, in conjunction with display. Correct programming is essential for obtaining accuracy, reliable performance and measurement.

Dist 0.40 m Heig 1.00 m

SET OK

_ +

Keys Display

Level Distance

Fig. 14

Terminals (Max. Adj.)

(Min. Adj.)

(3)

Function of Keys : (Fig 14)

1. Key to exit from programming 2. Key to increment of digit

3. Key for shifting to right digit or select next menu or choose options

4. Key to enter in programming menu or enter parameter and move next programming menu Using and key, you can edit the parameters while programming.

1. In 'Run mode' data can be viewed on display are measured value of LEVEL and DISTANCE, as shown in adjacent column.

Press OK to enter in programming (Menu 1)

2. Basic Settings - (Menu 1)

Press OK to enter in Basic Setting such as max and min range.

Press OK to enter in next menu.

3. Min Adjustment - Setting for 4 mA (Menu 1.1)

Press OK to edit distance in mtr, using Increment and Next/Shift key.

Press OK to confirm and go to next (Menu 1.2)

4. Max. Adjustment - Setting for 20 mA (Menu 1.2)

Press OK to edit distance in mtr, using Increment and Next key.

Press OK to confirm and go to next (Menu 1.3)

5. Fast Level Change - (Menu 1.3) Select Yes or No using Next key.

Press OK to enter selection and go to next (Menu 1.4)

6. Damping (Menu 1.4) Do not edit this menu and

Press Next key to enter in next (Menu 1.5)

7. Range Setting for total range including blanking dist. (Menu 1.5) Edit value in meter and

Press OK key to confirm and go to next (Menu1.6)

8. Near Blanking Setting for blanking distance (Menu 1.6) Edit value in meter of blanking distance

and press OK key to confirm and display shows 'Run Mode Display' Increment Next/Shift

SL Programming Menus and Steps Display

Innovating Level Controls Since 1984

SET

OK

Dist 0.40 m Heig 1.00 m

Basic Settings Display

1

Fast level change Yes

1.3

Damping 6S

1.4

Range 1.400 m(d)

1.5

Near blanking 0.400 m(d)

1.6 Min adjustment 0.00%

1.400 m(d) 0.817 m(d)

1.1

Max adjustment 100.00%

0.400 m(d) 0.365 m(d)

1.2

(4)

Innovating Level Controls Since 1984

MAN/ULTRATROL/REV-00/11-14 inspiregr[email protected]om | 9763672223 We reserve the right to modify design and specifications without prior notice.

Custom built specs./options available on demand.

Periodic Maintenance :

1. During maintenance switch off the power supply.

2. Check and tighten all loose electric connections.

3. The equipment should be cleaned with a damp cloth, without use of solvents.

4. After maintenance, ensure transmitter enclosure is closed with its gasket and cover to ensure weather proofness.

Trouble shooting :

SL Problem Cause Solution

1. No display 1. Wiring with incorrect polarity.

2. Loose connections 2. Tighten loose connections 2. Incorrrect output 1. Incorrect supply

2. Transmitter not perpendicular to liquid surface

3. Incorrect calibration 3. Re-calibrate the transmitter 4. Incorrect programming 4. Check and re-program correct

parameter values 3. No change in output 1. Wrong installation

2. Obstructions by tank internal correct installation

2. Remove / Shift obstructions

1. Wire with correct polarity (Fig 5, 6,7)

1. Ensure supply is between 16 to 30VDC.

2. Ensure perpendicularity as per installation guidelines

1. Refer Installation guidelines for

Pune Techtrol Pvt Ltd

[CIN : U31909PN1991PTC063403]

NSIC-CRISILSE1A

R A T E D

S-18, MIDC, Bhosari, Pune - 411026. India +91-20-66342900

Works :J-52/7, MIDC, Bhosari, Pune - 411026. India +91-20-67313600

[email protected] www.punetechtrol.com