At higher corner frequency values, Figure 7.25 shows that PID groups 2, 3, and 4 provide additional phase bias in the 3-8 rad/s modal frequency range. The example of detailed tuning of AVRs in the power plant with three remote generators is described in section 7.11.
Proportional plus Integral Compensation
Simple PI Compensation
The frequency response of a simple PI compensator modified with a series shift block is shown in Figure 7.27. The PI with series lag compensator shown above can be converted to PID form.
Rate feedback compensation
- Method of analysis
 - Tuning of the Excitation System (ES)
 - Rate feedback compensation using Frequency Response Methods
 - Rate feedback compensation using the Root Locus Method
 
Note that the top corner frequency is independent of the velocity feedback parameters, KF and TF. The desired shape of the open/closed loop system is shown in Figure 7-38.
Tuning of AVRs with Type 2B PID compensation in a three- generator system
The three-generator, 132 kV power system
The characteristics of this generator brushless generator and power system are: (i) the lines are long with a surge impedance load (SIL) of 45 MW; (ii) at the rated output of the station, the lines are heavily loaded (about 1.7xSIL); (iii) with the interruption of a line the loading on the second. To ensure that the tuning of the PID covers a range of operating conditions, the 75 generation/operating conditions shown in Table 7.9 are examined.
The frequency response characteristics of the brushless exciter and genera- tor
These two responses are shown in Figure 7.43 along with the phase response of the open-loop transfer function. Based on PID parameter Set 4 in Table 7.6, let's determine the terminal voltage response of the closed-loop system to a +1% step change in the generator reference voltage.
Summary, Chapter 7
An emphasis in the studies was to determine a basis for evaluating a suitable set of PID 2B parameters to meet the dynamic performance specifications over a wide range of operating conditions. The purpose of new technique called the 'phase matching', explained in Appendix 7–I.5, is to improve the robustness of the generator controls to variations in the gain of the voltage control loop.
The analysis is based on an operating condition chosen to be the 'best' representation of those frequency response characteristics over the range of operating conditions. The studies using this technique have shown the importance of obtaining good models and parameters for both exciter and generator, preferably validated through tests.
Appendix 7–I
Depending on the position of the gain crossover in the range 0.7 - 2.5 rad/s, the phase margin is the difference between the open-loop phase response ( ) and. 2 produces excessive phase conduction and therefore the phase margin of the OLTF is greater than the desired value PMdes.
Types of Power System Stabilizers
Introduction
This chapter discusses the design of velocity signal synthesizing prefilters and highlights some issues that may be detrimental to the performance of the resulting prefilter and velocity PSS. When designing the PSS, attention should be paid to reducing the effects of the torsional modes of the turbogenerator unit on its dynamic performance [5].
Dynamic characteristics of washout filters
- Time-domain responses
 - Frequency-domain responses
 
The responses of two identical washout filters in series to a step input of 1 unit are shown in Figure 8.2 for values of the washout time constant of 4 and 8 s. Consequently, the responses of two such filters to a ramp of 1 unit/s are shown in Figure 8.3 for a range of values of the washout time constant from 1 to 10 s.
Performance of a PSS with electric power as the stabilizing sig- nal
- Transfer function and parameters of the electric power pre-filter
 - Dynamic performance of a speed-PSS with an electric power pre-filter
 
Note the minus sign of the PSS output signal on the summing connection to the AVR. Care must be taken to apply negative feedback from the PSS output signal to the AVR summing connection.
Performance of a PSS with bus-frequency as the stabilizing sig- nal
- Dynamic performance of a speed-PSS with a bus-frequency pre-filter The bus-frequency pre-filter delivers a synthesized speed signal to a PSS whose design is
 - Degradation in damping with the bus-frequency pre-filter
 
The real parts of the mode shifts for the bus-frequency PSS are significantly degraded (by a factor of 1/c) with respect to the speed-PSS. The ratio of the true rotor speed to the bus frequency at the modal frequency is 1.57; this ratio agrees well with the value c= 1.59 in the table.
Performance of the “Integral-of-accelerating-power” PSS
- Introduction
 - Torsional modes introduced by the speed stabilizing signal
 - The Ramp Tacking Filter (RTF) The RTF is a low-pass filter of the form,
 
It should be noted that the RTF tracking function is turned off if it deviates noticeably. The value of the time constant T9 more or less determines the angular frequency of the RTF.
Conceptual explanation of the action of the pre-filter in the IAP PSS
- Action of the pre-filter, no washout filters
 - Effect of the washout filters and integrators on the performance of the pre- filter
 - Dynamic performance of the complete pre-filter
 - Potential causes of degradation in performance of the pre-filter of the IAP PSS
 
RTF, but also how closely the RTF's output tracks the input to the RTF. Degradation of prefilter performance can be attributed to a number of causes.
The Multi-Band Power System Stabilizer
It is interesting to investigate the nature of the frequency response for MB-PSS omitting washout filters, velocity transducers and torsion (notch) filters. The frequency responses for three bands and the output of the MB-PSS are shown in Figure 8.24; they closely match Figures 5 and 6 in [16].
Concluding remarks
The use of the latter signal as the stabilization signal for a 'true' speed PSS has been found to reduce the effective damping gain of the PSS (by as much as 40% in the cases studied). However, the attenuation gain of the PSS can be increased to compensate for the gain reduction.
Pons, "Extensive PSS use in large systems: the Argentinian case," in Power Engineering Society Summer Meeting, 1999. Beaulieu, "Practical experience with the use of power system stabilizers," in Power Engineering Society Summer Meeting, 1999.
Appendix 8–I
8–I.2 Steady states at the input and output of the RTF and associated tracking errors for mechanical input power RTF and associated tracking errors for mechanical input power. Since the Laplace transform of is , the Laplace transform of each of the input functions is simple.
Basic Concepts in the Tuning of
PSSs in Multi-Machine Applications
Introduction
- Eigenvalues and Modes of the system
 
The -element column vector, , is the right eigenvector of the matrix corresponding to the eigenvalue. In the case of the oscillating modes, assuming the mode is unique, the right and left eigenvectors of the complex conjugate eigenvalues are also complex conjugates.
Mode Shape Analysis
- Example 1: Two-mass spring system
 - Example 2: Four-mass spring system
 
The form of the answers is again consistent with the results in Figure 9.2 and/or Table 9.2. The second mode shows the behavior of masses relative to a frame of reference.
Participation Factors
- Example 4.3
 
Similarly, the kth column represents the participation factors of the modes in the kth state. It can be confirmed that the sum of the participation factors covering the eight eigenvalues is
Determination of the PSS parameters based on the P-Vr approach with speed perturbations as the stabilizing signal
- The P-Vr transfer function in the multi-machine environment
 - Transfer function of the PSS of generator i in a multi-machine system The basic concepts for the determination of the parameters of a PSS in a single machine sys-
 
For example, for PSS tuning of a generator in a multi-machine power system, phase information on the P-Vr transfer function is determined from field tests [10] or based on SMIB models with machine inertia. constant set to a very large value in the generator of interest [11], [12]. The damping gain (at the machine's MVA rating) of the PSS determines the extent of the shift to the left.
Synchronising and damping torque coefficients induced by PSS i on generator i
In other words, the damping gain ki per unit of the PSS is the realized one. This observation is illustrated in the SMIB cases by a comparison of the inherent coupling coefficients in Figures 5.5(a) and 5.18.
Zywno, “Using Power System Stabilizers to Improve Overall System Stability,” Power Systems, IEEE Transactions on, vol. Gibbard, “Robust design of power system stabilizers with fixed parameters over a wide range of operating conditions”, Power Systems, IEEE Transactions on, vol.
Application of the PSS Tuning Concepts to a Multi-Machine Power System
Introduction
The PSSs in a new power station must be set to meet the damping and other performance criteria of the system operators over the range of system operating conditions and contingencies. Normally, the main emphasis is placed on the dynamic performance of the multi-machine power system after large-signal disturbances.
A fourteen-generator model of a longitudinal power system
- Power flow analysis
 - Dynamic performance criterion The dynamic performance criterion requires
 
Data for the power flow analysis of the six normal operating conditions given in Table 10.1 are provided in Appendix 10–I.2. Included in Appendix 10–I.2 are relevant results of the analysis, such as reactive outputs of generators and SVCs, together with tap positions on generator and network transformers.
Eigen-analysis, mode shapes and participation factors of the 14- generator system, no PSSs in service
- Eigenvalues of the system with no PSSs in service
 - Application of Participation Factor and Mode Shape Analyses to Case 1 Consider in Figure 10.2 the unstable, oscillatory mode (designated ‘Mode L’)
 
Let's look at graphs of not only the magnitudes of its participation factors (PF), but also its mode shape (MS); the plots are shown in figure 10.3. In the participation factor plot 'W' and 'DEL' are the rotor speed and angle perturbations respectively.).
The P-Vr characteristics of the generators and the associated synthesized characteristics
As detailed in Section 5.10.6.1, the 'best fit' characteristic for these studies is considered to be that which lies in the middle of the magnitude and phase bands formed by the P-Vr characteristics1. The more or less invariant nature of the phase responses of the P-Vr characteristics is also explained in Section 9.4.1.
The synthesized P-Vr and PSS transfer functions
Blocks that can accommodate complex poles and zeros are desirable in the PSS structure, as will be seen from the form of PSS transfer functions in (10.4) and (10.6) below. For illustrative purposes, the very short time constants (6.7 ms) of the low-pass filter are used here to minimize its influence in the range of modal frequencies.
Synchronising and damping torque coefficients induced by PSS i on generator i
For PSS-induced synchronizing and damping torque coefficients, the rotor angle path is open and the PSS path is closed (see Figure 10.23). The responses are shown in Figure 10.25 for two generators for the operating condition Case 1; coefficients are in units of generator rating.
Dynamic performance of the system with PSSs in service
- Assessment of dynamic performance based on eigen-analysis
 - Assessment of dynamic performance based on participation and mode- shape analysis
 
In Chapter 13, it will be shown that the smaller increments in the inter-area mode shift mode with PSS amplification are due to (i) smaller values of the participation factor of the generators participating in the mode, and (ii) the influence of the interaction between their PSSs [4]. A plot of the rotor modes for Case 1 with increasing gain is shown in Fig. 10.26(a).
Intra-station modes of rotor oscillation [6], [7]
Note that the PSS design procedure based on the P-Vr characteristic does not explicitly attempt to shift the intra-station modes directly to the left in the complex s-plane. The design of an auxiliary controller specifically for damping the intra-station modes is proposed in [8].
Correlation between small-signal dynamic performance and that following a major disturbance
- A transient stability study based on the fourteen-generator system
 - The analysis of modal interactions [10], [11], [12]
 
The peak amplitudes of the velocity perturbations in Figure 10.32(a) are 1.5 to 2%, which is not small. The second-order terms complement the information provided by the first-order linear approximation of the power system equations.
Summary: Tuning of PSSs based on the P-Vr approach
This is caused by the production of a positive or negative damping torque induced on generator i by the action of the PSS fitted to machine j [4]. Furthermore, we observe in Figure 10.26 that the mode shifts associated with the inter-area modes are smaller than those of the local modes.
The following Tables 10.15 and 10.16, together with Table 10.11, show the values of the modes of rotor oscillation for Cases 1 to 6 with the PSSs off and in service. The transformer tap ratios listed in Table 10.21 are based on the convention shown in Figure 10.35.
Tuning of FACTS Device Stabilizers
- Introduction
 - A ‘simplistic’ tuning procedure for a SVC
 - Theoretical basis for the tuning of FACTS Device Stabilizers
 - Tuning SVC stabilizers using bus frequency as a stabilizing sig- nal
 - Use of bus frequency as a stabilizing signal for the SVC, BSVC_4
 
The residuals of the transfer function for the inter-area modes K, L and M are then calculated for the operating conditions 1 to 6. The residuals are from the SVC transfer function for the range of operating conditions, Cases 1 to 6.