MM3

Intelligent

MCC

Controller

MM3

Intelligent

MCC

Controller

The Motor Manager 3 (MM3) combines control functions and comprehensive motor protection in one package. This compact device provides sophisticated control and protective relaying at significant cost savings over the discrete devices normally found in a low voltage motor control center (MCC).

One MM3 is required for every starter in the MCC. The contactors can be energized and de-energized using the MM3’s direct wired inputs, or via the serial port. A total of 6 fixed and 10 programmable switch inputs are available. A wide range of starter types may be controlled by the MM3 using two contactor outputs and two auxiliary outputs. One analog input can be programmed by the user as well as one analog out. A programmable undervoltage auto restart function is available.

Motor protection features for the most common causes of failure are provided to prevent costly shut downs and rewinds. These include overload, phase unbalance, locked rotor (stall), ground fault, undercur-rent and underpower. A thermistor input can also be provided to protect a hot winding. The relay checks the contactor status at start and stop commands to indicate contactor fail-ure. Alarms are provided to warn of additional abnormal conditions.

The MM3 has two mounting configu-rations: chassis mount no display, and panel mount local display. Both models have a 2 wire RS485 ModBus® RTU protocol communication port operating at up to 57,600 bps. The panel mount model has a stop key and 8 status LEDs, a 2 by 20 line display, 2 additional command mode LEDs, and a keypad, which allows full local access without a computer.

DESCRIPTION

9

Applications

■ Low voltage motor control centers

■ Integrated process & electrical control

Protection

■ Overload

■ Phase unbalance

Contactor failure ■ Locked/stalled rotor

■ Ground fault

■ Hot winding thermistor

Undercurrent/underpower

Control

Undervoltage auto restart

Outputs: 2 contactor, 2 programmable ■ Inputs: 6 fixed, 10 programmable

■ 1 analog input

1 analog output 4-20 mA

Monitoring and Metering

■ Display phase current, ground current, thermal capacity, analog input, power, energy, etc.

■ Trip record and pre-trip values

■ Maintenance information

Self-test

User Interfaces

RS485 ModBus®Port, 1200 - 57,600 bpsDisplay model for local interface ■ Up to 10 status LEDs

Features

Reduces MCC and field wiring ■ Replaces timers, relays, protective

devices, meters, panel indicators

Integrated primary CTs up to 250 FLCLocal faceplate

■ Standard removable rear terminals

(2)

9

PROTECTION AND CONTROL

The MM3 is available with different protection and control features depending on the model ordered as outlined in the Model Table (page 208).

Overload (49/51)

An overload trip is caused when the thermal capacity value equals 100%. Thermal capacity used is calculated from accumulated I2t value and chosen overload curves. True RMS current sensing ensures correct response to the heating effect of harmonics. One of 12 different I2t time-overcurrent over-load curves may be selected from 8 standard curves and 4 NEMA compati-ble curves.

Of the 12 overload curves available 4 are NEMA compatible time/current overload curves.

Phase Unbalance (46)

The MM3 monitors the percentage unbalance in the motor phase currents. If a phase current unbalance of greater than 15% exists for more than 5 seconds an alarm is generated. If a phase current unbalance of greater than 30% exists for more than 5 seconds a trip occurs.

Locked/Stalled Rotor (48)

Mechanical equipment such as pumps or fans can be quickly damaged if it gets jammed resulting in a locked rotor stall. The MM3 will trip when the running current exceeds the stalled rotor trip level after the programmed time delay. If stall protection is not required this feature may be set to ‘OFF’. This feature is disabled during the inrush of motor starting.

Ground fault (50G/51G)

The ground fault level is measured as a percentage of FLC. Ground overcurrent can be detected either from the resid-ual connection of the phase CTs or from the zero sequence CT. A delay time is set to prevent nuisance alarms from momentary surges. Both a ground fault alarm and trip are provid-ed. The alarm can be set below the trip level to get an early warning of insula-tion breakdown.

Overtemperature (49)

An input from motor winding thermis-tors is available. The MM3 can accept both positive temperature coefficient (PTC) and negative temperature coeffi-cient (NTC) sensors. A thermistor level can be selected for both alarm and trip.

Cooling Time

After an overload trip the thermal capacity value will decrease exponen-tially to model the cooling characteristic of the motor. An over-load trip can normally be reset when the thermal capacity value decreases to 15%. A stopped motor cooling time can be set to determine how long it takes for a stopped motor to reach steady state ambient temperature from its maximum allowable temperature.

Undercurrent/Underpower (37)

Both undercurrent and underpower alarms and trips are provided with time delays. Protection against failed

shearpin, loss of pump flow, etc., which may result in only a small change in current is provided by the under power alarm.

Contactor Failure

The MM3 monitors the contactor while performing start and stop commands. If the contactor does not change status (open to closed or closed to open) an ‘open control circuit’ or ‘welded contactor’ alarm is triggered.

Additional Alarms

The MM3 has programmable alarms to warn of a number of abnormal condi-tions. These include: acceleration time exceeded, abnormal inverter starter, incomplete start, motor greasing, contactor inspection, motor stop time, analog input, and process interlock switch open.

Starters

The MM3 can control a variety of starter types using the contactor outputs. Contactor A is used for full voltage non-reversing starters. Contactor A and B are used for revers-ing, two speed, autotransformer, inverter, wye-delta open transition, slip ring, and part winding starters. Contactors A, B, and one auxiliary output are used for the reduced volt-age wye-delta closed transition starter.

100000

10000

1000

100

10

1

0.1 0.5 1 2 3 4 5 6 7 89 10 20 50 100

807903D4.cdr

TIME IN SECONDS

MULTIPLE OF PICKUP CURRENT (PER UNIT)

CURVE #

CLASS 30 CLASS 20 CLASS 15 CLASS 10

FUNCTIONAL BLOCK DIAGRAM

52

480 VOLT BUS

FUSE

CONTACTOR

PHASE PT

PHASE CT

GROUND CT

THERMISTOR

MOTOR

LOAD WINDING

THERMISTOR 49

51G 51 49 37 46 59 27

4-20mA INPUT CONTROL

INPUTS AUX 2 RELAY

RS485 REMOTE COMMUNICATION 1200-57K6 BAUD

PROCESS PLC OR TRANSDUCER

809751A2.dwg

AUX 1 RELAY CONTACTOR B (REVERSE/DELTA)

CONTACTOR A (FORWARD/WYE)

MOTOR MANAGER 3

49/51 Overload

46 Phase unbalance

(single phase)

— Welded/open contactor

50G/51G Ground fault

48 Locked rotor/stalled rotor

37 Undercurrent/underpower

27 Undervoltage

59 Overvoltage

49 Hot winding (thermistor) – option 3

(3)

9

at which a number of routine mainte-nance tasks should be performed. When these times are exceeded an alarm is generated. These include:

■Motor greasing interval: number of hours after which motor bearings must be lubricated

■Contactor inspection: number of starts after which contactor contacts must be inspected for wear

■Maximum motor stopped time: The maximum number of hours that the motor can be left not running

Networking

Gateway solutions exist to connect the MM3 to installed protocols in a given system. The X-Link is a gateway prod-uct from SST (www.sstech.on.ca). This product makes it possible to transfer data between two communications networks. Networks such as ModBus, ModBus Plus, ProfiBus, DeviceNet, Data Highway Plus, GE Fanuc, ControlNet and DNP are supported.

Undervoltage Auto Restart

It is possible to automatically restart the motor after a momentary power loss if this feature is enabled. When the control voltage drops below the dropout voltage the contactors are de-energized. The MM3 can initiate timers to restart selected drives upon the return of supply voltage. If control volt-age is restored within the programmed restart time it will be restarted immedi-ately. If the control voltage takes longer to be restored the MM3 can be programmed to attempt to restart the motor after a programmed time delay.

Outputs

The MM3 has one or two contactors (A and B). There are also two auxiliary programmable output relays available on the MM3. These two outputs can be assigned to any one of 31 functions.

Switched Inputs

The MM3 has up to 6 fixed control inputs. These are used for start A and B, stop, local isolator, and contactor A and B status. The MM3 also has up to 10 programmable switch inputs. Each input can have one of 33 interlock func-tions assigned to it. Once a function is assigned to one interlock input that function cannot be assigned to any other interlock input.

Analog Input

The analog input can be scaled to user defined values. High and low alarm and trip setpoints are recorded with time delays.

Metering

The MM3 meters and displays:

■RMS current of each phase

■Ground fault leakage current

■Motor load as a % of full load current

■Thermal capacity used (%) according to I2t history and chosen overload

curve; hot/cold ratio is used to model heating when running below full motor current

■% unbalance

■Power (kW)

■Energy (kWh)

■Voltage

■Analog input

Trip Record

When the MM3 issues a trip command a trip record is generated. This includes the cause of the trip and pre-trip actual values.

Statistics and Maintenance

The MM3 records statistical data about relay and motor operation. The MM3 also allows the user to set the interval

MONITORING AND METERING

MCC WIRING

CONVERTIONAL MCC MCC WITH MOTOR MANAGER 3 SUPERVISORY CONTROL SYSTEM FOR ONE STARTER SUPERVISORY CONTROL SYSTEM FOR ONE STARTER

TWO WIRE REMOTE CONTROL

CONTROL CABLE

LOCAL MCC

RS485 TWISTED PAIR

MM III 240/120 V AC

FIELD STOPCONTRACTOR

809755A2.AI PANEL DEVICES RUNNING INDICATOR STOPPED INDICATIOR TRIPPED INDICATIOR HOURS RUN COUNTER NUMBERS OF STARTS START PUSHBUTTON STOP PUSHBUTTON STOP C3 CONTACTORC2

CONTACTOR TRIP FIELD

STOP

GROUND

FAULT STALLRELAY THERMISTOR RELAYU/C ACCELTIME RELAYTRIP L

10 WIRE CONTROL CABLE

240/120V AC L

N

Cost Effective MCC Wiring with MM3.

RS232 CABLES FROM COM PORT OF THE SERIAL CARD AND X-LINK TO F485

NULL MODEM CABLE SUPPLIED WITH X-LINK

FOR X-LINK CONFIGURATIONCONNECTED FROM X-LINKCONFIG PORT TOPC COM PORT

TWISTED PAIR SHIELDED

TWISTED PAIR

SLAVE 1 SLAVE 1 SLAVE 1

SLAVE 2 SLAVE 2 SLAVE 2

SLAVE 3

SHIELDED TWISTED PAIR

DAISY-CHAIN 1 DAISY-CHAIN 2

DAISY-CHAIN 3

RS232 COMPUTER

FIBER OPTICRS485 POWERPOWER 9VAC/ 9VDC Tx Rx+ - COM GND + -COM PORT9VAC/9VDC F485 OR SCI BOX

RS232 COMPUTER

FIBER OPTICRS485POWERPOWER 9VAC/ 9VDC Tx Rx+ - COM GND + -COM PORT9VAC/9VDC F485 OR SCI BOX

RS232 COMPUTER

FIBER OPTICRS485POWERPOWER 9VAC/ 9VDC Tx Rx+ - COM GND + -COM PORT9VAC/9VDC F485 OR SCI BOX

STOP SETPOINT ACTUAL RESET STORE START A START B MANUAL AUTO CONTACTOR A

CONTACTOR B AUX 1 PC EQUIPPED WITH:

SST 5136-PFB PROFIBUS CARD MICROSOFT EXCEL

SST X-LINK CONFIGURATION SOFTWARE SST DP MASTER DDE SERVER SOFTWARE SST PROFIBUS CONFIGURATION SOFTWARE

SST X-LINK EQUIPPED WITH: SST 5136-PBMS PROFIBUS CARD OPTIONAL RS232 SERIAL CARD KERNEL DRIVER MODBUS DRIVER (DRIVER 1) PROFIBUS-PBMSLV DRIVER (DRIVER 2)

PROFIBUS-DP NETWORK

MODBUS NETWORK

STATUSCOMMUNICATE RELAYS

POWER QUALITY METER PQM

SIMULATION ALARM SELF TEST PROGRAM SR469 IN SERVICESTOPPED R1 TRIP SETPOINT ACCESSSTARTING R2 AUXILIARY COMPUTER RS232RUNNING R3 AUXILIARY R4 ALARM R5 BLOCK START R6 SERVICE MESSAGE

HOT RTD LOSS OF LOAD

MOTOR MANAGEMENTRELAY PROGRAM PORTSETPOINT 789

456 COMPUTER RS485 AUXILIARY RS485 LOCKOUT SR469 STATUSMOTOR STATUSOUTPUT RELAYS

OVERLOAD PICKUP UNBALANCE PICKUP GROUND PICKUP

STOP RUNNING RELAY A STOPPED RELAY B TRIPPED AUX RELAY 1 ALARM AUX RELAY 2

VALUE MESSAGE

AUTOMANUAL STORE

RUNNING RELAY A STOPPED RELAY B TRIPPED AUX RELAY 1 ALARM AUX RELAY 2

VALUE MESSAGE

AUTOMANUAL STORE RESET ACTUAL SETPOINT

STARTASTARTB

STOP RUNNING RELAY A STOPPED RELAY B TRIPPED AUX RELAY 1 ALARM AUX RELAY 2

VALUE MESSAGE

AUTOMANUAL STORE

RUNNING RELAY A STOPPED RELAY B TRIPPED AUX RELAY 1 ALARM AUX RELAY 2

VALUE MESSAGE

AUTOMANUAL STORE RESET ACTUAL SETPOINT

STARTASTARTB

809822a1.ai

(4)

9

Communication

The MM3 uses a ModBus® RTU RS485 connection for communication. Up to 32 MM3s can be daisy chained togeth-er on a single communication channel. The MM3 supports operation at 1200 to 57600 bps. A RS232/485 converter module may be used to connect a personal computer to the MM3.

Software

The MM3 is provided with a free communications program called MM3PC. It runs on a personal comput-er undcomput-er Windows®. It allows access to all the features of the MM3 with easy to use pull down menus. Using this program it is possible to:

■Program or modify setpoints

■Load or save setpoints from or to a disk

■Read actual values from the MM3

■Monitor status

■Read pre-trip data and trip record

■Display dynamic trending of actual values

■Get help on any topic

■Print the instruction manual from disk

■Simulate and test features

Windows®based software is supplied with the MM3.

Mounting Configurations

The MM3 can be ordered in two mounting configurations; the chassis mount and the panel mount with local display.

The chassis mount model is the “black box” version of the MM3. It is mounted inside the motor control center (MCC).

The chassis mount version has the added flexibility of using the display port as a second communications port. The advantage is that slower metering functions can be assigned to one communications port while the other port could be used for high speed command operations such as Start/Stop or quick status updates such as tripped, running, etc. Using the second port provides a means for redundant communication channels guaranteeing control and status infor-mation even if one channel is interrupted.

Alternatively up to 32 MM3’s could be daisy chained and connected to a Touch-screen Graphical Interface (TGI) module for remote status/command operations.

The panel mount with display model is the “Top of the Line” MM3.

The panel mount with local display model is mounted on the front panel of the MCC with its 2 by 20 alphanumeric display, full keypad, and 10 status LEDs exposed to the operator for complete local viewing and setpoint program-ming. The setpoints can also be loaded into the relay through the RS485 communications port.

MODELS

USER INTERFACES

Model Table: The MM3 is available in chassis mount or panel mount models.

Protection 3 phase overload protection (49/51) 3 phase overload protection (49/51)

Phase unbalance (46) Phase unbalance (46)

Welded/open contactor Welded/open contactor

Ground fault trips (50G/51G) Ground fault trips (50G/51G) Stalled rotor protection (48) Stalled rotor protection (48)

Display kw and kWh Display kw and kWh

Undercurrent/underpower (37) Undercurrent/underpower (37)

Overvoltage (59) Overvoltage (59)

Undervoltage (27) Undervoltage (27)

Inputs 4 control 6 control

2 programmable 10 programmable

Thermistor input Analog in input Analog output

Relays Contactor A Contactor A

Contactor B

Aux 1 Aux 1

Aux 2 or ESD relay Aux 2 or ESD relay

(5)

9

FEATURES

Front View

STATUS INDICATORS:

RUNNING: Contactor is energized and motor is running.

STOPPED: Contactor is not ener-gized and motor is not running.

TRIPPED: Contactor is not ener-gized. Motor is not running. The MM3 has tripped the motor due to a fault. Normally a cause of trip message will be displayed.

ALARM: One or more alarm condi-tions are present. Normally a cause of alarm message will be displayed.

GROUND CT INPUT

50:0.025 ground fault input.

Rear View

DISPLAY:

2 line, 40 character illuminated display communicates all messages in simple English for easy interpretation by users unfamiliar with unit.

SUPPLY VOLTAGE

required to power the MM3

VOLTAGE INPUT

Phase A voltage input for voltage and power monitoring.

SWITCH INPUTS

Opto-isolated 120/240 VAC live inputs for various interlock functions. The interlock inputs are fully programmable and can be assigned to such functions as setpoint access, plant interlock, test, and various others.

COMMUNICATIONS

RS485 2 wire serial communication port operates at 1200 - 57,600 bps for remote commands, monitoring and setpoint store. ModBus®RTU protocol.

Ground safety and surge

THERMISTOR

NTC or PTC thermistor input for hot winding detection.

ANALOG INPUT/OUTPUT

4 - 20mA input for process control monitoring / alarming / tripping.

4 RELAYS

■Contactor A: direct on line / forward / wye

■Contactor B: reverse / delta

■User programmable relay (AUX 1)

■User programmable relay (AUX 2)

PROGRAM KEYS:

ACTUAL VALUES: Press to enter actual values mode to display actu-al motor vactu-alues such as current, ground leakage, thermal capacity.

SETPOINTS: Press to enter setpoint mode to alter or examine setpoints.

STORE: Save a newly entered setpoint.

RESET: Reset the MM3 after a trip.

MESSAGE: Move to the desired setpoint or actual value message.

VALUE: Increment or decrement currently displayed setpoint value.

CONTROL KEYS:

AUTO: Selects

operation of start via communi-cation port.

MANUAL: Selects manual opera-tion of motor using start key.

START A: Energize contactor A.

START B: Energize contactor B.

STOP: De-energize contactors.

RELAY INDICATORS:

RELAY A: Contactor A energized.

RELAY B: Contactor B energized.

AUX 1: User programmable relay 1 energized.

AUX 2: User programmable relay 2 energized.

CONTROL POWER

120/240 VAC supply voltage selector switch and fuse access door

Ground safety

RESIDUAL GROUND INPUT PHASE CT INPUTS

(6)

9

TYPICAL WIRING

809772A4.dwg GE Power Management

PHONE JACK

TO REMOTE DISPLAY

48 21 22 24 23 30 29 28 18 17 16 15 14 13 12 11 1 2 3 4 5 6 7 8 9

10 20 25

26 27 31 32 33

43 42 41 40 39 38 37 36 35 34

44 45 46 47

EARTH SAFETY EARTH SAFETY EARTH SURGE

LIVE NEUTRAL

CON

TROL PO

WER

ANALOG IN SHIELD ANALOG -ANALOG + THERMISTOR -THERMISTOR +

ANAL

OG IN

CONTACTOR B STATUS NO CONTACTOR A

STATUS NO ISOLATOR STATUS NO START B START A FIXED SWITCH INPUTS

STOP INTERLOCK

INPUT 1 INTERLOCK

INPUT 2 INTERLOCK

INPUT 3 INTERLOCK

INPUT 4 INTERLOCK

INPUT 5 INTERLOCK

INPUT 6 INTERLOCK

INPUT 7 INTERLOCK

INPUT 8 INTERLOCK

INPUT 9 INTERLOCK

INPUT 10

PROGRAMMABLE INPUTS

INTERNAL CONNECTOR

MOTOR MANAGER 3 OPTION 2

SERIAL 485 A+ SERIAL 485

B-485 SHIELD ANALOG + ANALOG -ANALOG OUT

SHIELD

ANAL

OG OUT

RS485

PROGRAMMABLE

RELA

Y 1

PROGRAMMABLE

RELA

Y 2

PROG. RELA

Y 2

EXT

. COIL

+24 VDC +24 COM

COM

COM N/C N/C

N/O N/O

MOTOR

CT PHASE C CT PHASE B

CT GROUND CT MODULE

CT PHASE A CONTACTOR

L1

L2

L3 A

A

A F3

F4

F5

F2 F1 A

B

C 480 VOLTS

C

A B

480 VOLTS

110/230 VAC

A

STATOR THERMISTOR

4-20mA ANALOG IN

MCC GROUND BUS

NOTES:

1. RELAY CONTACT STATE SHOWN WITH CONTROL POWER NOT APPLIED.

2. TERMINALS MARKED WITH "*" MUST BE CONNECTED BEFORE MOTOR CAN BE STARTED. 3. DO NOT GROUND TERMINAL 19 WHEN USING A EXTERNAL GROUND CT.

CONTACTOR A 4-20 mA ANALOG OUT

RS485

19

= OPTION 2

* *

N/O

N/O

CON

TA

CT

OR

B

CON

TA

CT

OR

(7)

PROTECTION OVERLOAD CURVES

Trip Time: ±200 ms up to 10 sec

Accuracy: ± 2% of trip time over 10 sec

Detection Level: ± 1% of primary CT amps

GROUND FAULT TRIP TIME

Accuracy: - 0 ms, + 50 ms, 0.0 = less than 50 ms

SINGLE PHASE (PHASE UNBALANCE)

Range: Greater than 30% U/B

Accuracy: ± 2 percentage points

Trip Delay: 5 sec, ± 1 sec

Calculation Method: If IAV≥IFLC: UB = |IM-IAV| x 100

IAV

If IAV<IFLC: UB = |IM-IAV| x 100

IFLC

Where: IAV= average phase currents

IM= current in a phase with maximum

deviation from IAV

IFLC= motor full load current setting

UNDERCURRENT

Range: 10-100% of motor FLC, or OFF

Delay Range: 1 to 60 sec

Accuracy: ± 1 sec

UNDERVOLTAGE – SUPPLY VOLTAGE

Undervoltage: 65 % of nominal (120 VAC or 240 VAC) immediate restart for maximum dip time of 0.1-0.5 sec or OFF delayed restart for maximum dip time of 0.1-10.0 sec/unlimited time

Delay Restart Range: 0.2-300 sec

Delay Restart Accuracy: ± 0.2 sec 9

Motor protection and control shall be provided by an intelligent control device capable of manual or automatic control.

Protection features available shall include trip and alarms for:

■Overload with 12 overload curves

■Phase unbalance

■Welded/open contactor

■Ground fault

■Locked/stalled rotor

■Thermistor for hot winding

■Undercurrent and underpower

■Additional alarms for abnormal conditions

Control features available shall include:

■6 fixed control inputs for start A & B, stop, local isolator, contactor A & B status

■10 programmable inputs, each of which can be assigned to any one of 33 functions

■2 contactors (A & B)

■2 auxiliary relays, each of which can be assigned to any one of 31 functions

■One analog input with high and low alarm and trip setpoints

■Undervoltage auto restart

Motor current sensing shall be from internal primary CTs up to 250 FLC. Ground sensing shall be from an exter-nal core balance CT or residually. Metering values shall include:

■RMS current of each phase

■RMS ground fault leakage current

■Thermal capacity

■Analog input

■Motor load

■Thermal capacity used

■Unbalance

■Power (kW)

■Energy (kWh)

■RMS voltage

GUIDEFORM฀SPECIFICATIONS

APPROVALS

: IEC 947-1, IEC 1010-1

Quality Assurance System (registered by QMI):

UL ฀฀฀฀Listed฀for฀USA฀and฀Canada ISO: 9001 - 1994

PACKAGING

Max. Weight: 6 lbs 12 oz (3.1 kg)

Shipping Dimensions:12" x 9" x 7.5" (350 mm x 229 mm x 190 mm)

INSTALLATION

WARNING: HAZARD may result if the product is not used for its intended purpose.

FUSE฀TYPE/RATING

0.5 A 250 V

Fast blow, high breaking capacity

TYPE฀TESTS

Transients: ANSI/IEEE C37.90.1 Oscillatory/ Fast Risetime Transients IEC 801-4 Electrical Fast Transient/ Burst Requirements

Impulse: IEC 255-5 5 kV Impulse Voltage Test

RFI: 150 MHz, 450 MHz 5 W Handheld Transmitter @ 25 cm

Static: IEC 801-2 Electrostatic Discharge

Hipot: 1500 V, 1 min all input > 30 V

ENVIRONMENTAL

Pollution Degree: 2

Overvoltage Category: 2

Insulation Voltage 300 V

Continuous Operating Temperature:

Peak Operating Temperature: 0°C to 60°C, 16Hrs (IEC60068-2-2) 85 °C

IP Class: IEC 529 IPX0

POWER฀SUPPLY

SUPPLY VOLTAGE

AC Nominal: 120 VAC, range 80-135 VAC 240 VAC, range 150-250 VAC

Frequency: 50/60 Hz

Power Consumption: 25 VA (Maximum) 7 VA (Nominal)

COMMUNICATIONS

Type: RS485 2 wire, half duplex

Baud Rate: 1,200-57,600 bps

Protocol: ModBus®RTU

Functions: Read/write setpoints, read actual values, execute commands, read coil status, read device status, loopback test

INPUTS

THERMISTOR INPUTS

Sensor Types: positive temperature coefficient PTC RHOT=100-30,000Ω

negative temperature coefficient NTC RHOT=100-30,000Ω

Delay: 1 sec

Accuracy: ± 5% or 100 Ω(whichever is greater)

ANALOG INPUT

Range: 4-20 mA

Accuracy: ± 1% of full scale

Alarm: Programmable 4-20 mA

Trip: Programmable 4-20 mA

Accuracy: ± 2% of full scale reading

Isolation: 15 V isolated, active source

OUTPUTS

RELAY CONTACTS

MM3 CONTACTOR A & B OUTPUT RELAYS VOLTAGE MAKE/CARRY MAX. OPERATING MAX. SWITCH.

CONTINUOUS CURRENT CAPACITY RESISTIVE 30 VDC 8 A 8 A 2500 VA

CONFIGURATION SPST-NO – Contactor A & B – Form A

CONTACT MATERIAL Silver Alloy (AgCdO)

MAX OPERATING VOLTAGE 380 VAC, 125 VDC

MIN PERMISSIBLE LOAD 5 VDC, 100 mA

METERING

PHASE CURRENT INPUTS

Conversion: True RMS, sample time 1.67 ms

Range: 0.1 to 8 x phase CT primary amps setpoint when external CTs are used .2 to 250 A, FLC < 32 A

Accuracy: ± (2% + 1)*

GROUND FAULT CURRENT INPUT

Conversion: True RMS, sample time 1.67 ms

Range: 0.1 to 1.0 x FLC amps setpoint (residual connection) 0.5 to 15.0 A (50:0.025 CT)

Full Scale: 1.5 x FLC amps setpoint (residual connection) 15 A (50:0.025 CT)

Accuracy: ± (2% + 2)* (residual connection) FLC < 32 A ± (2% + 6)* (residual connection) FLC < 32 A 50:0.025 CT: ± 0.3 A

*Accuracy is given as ± ([% of reading] + [number of least significant digits])

MONITORING

VOLTAGE INPUT/POWER READING

Conversion: True RMS, sample time 1.67 ms

Voltage Full Scale: 1.5 x VT Primary

Voltage Accuracy: ± 2% of VT Primary or

± 2% of reading, whichever is greater

Power Accuracy: ± 5% of nominal or

± 5% of reading, whichever is greater

Input Voltage: Nominal: 120 VAC or 240 VAC Max: 250 VAC

VT Burden: 0.01 VA ACCELERATION TIME

Range: 0.5 to 125 sec, or OFF

Accuracy: ± 0.5 sec THERMAL COOLING TIMES

Range: 5-1080 min when motor stopped 50% of motor stopped value when motor running

Accuracy: ± 1 min STALLED ROTOR

Range: 1.15 to 4.50 x FLC, or OFF

Delay Range: 0.5 to 5 sec

Accuracy: ± 0.5 sec

*Specifications subject to change without notice.

NOTE:It is recommended that all MM3 relays are powered up at least once per year to avoid deterioration of electrolytic capaci-tors in the power supply.

OUTPUTS

MM3 CONTACTOR AUX 1 & AUX 2 OUTPUT RELAYS VOLTAGE MAKE/CARRY MAX. OPERATING MAX. SWITCH.

CONTINUOUS CURRENT CAPACITY RESISTIVE 30 VDC 8 A 8 A 2400 VA

CONFIGURATION SPST-NO + SPST-NC – AUX 1 & 2 – Form A

CONTACT MATERIAL Silver Alloy (AgCdO)

MAX OPERATING VOLTAGE 380 VAC, 125 VDC

MIN PERMISSIBLE LOAD 5 VDC, 10 mA

ANALOG OUTPUTS

Output: 4-20 mA

Max Load: 600Ω

Max Output: 21 mA

Accuracy: ±2% of full scale reading

Isolation: 36 V isolated, active source

(8)

9

Accessories

MM3PC software package supplied free

RS232 TO RS485 CONVERTER box designed for harsh industrial environ-ments

5A PHASE CT: 300, 350, 400, 500, 600, 750, 1000

50:0.025 Ground CT for sensitive ground detection on high resistance grounded systems

Control key cover hides auto, manual and start buttons

CUTOUT

6.49 (164.8)

6.25 (158.8) 0.10

(2.54)

0.078 T Typ (2) 8 PLACES 1.15

(29.2) 0.17 (4.3) 2.31 (58.7) 3.47 (88.1)

4.063

(117.6) (117.6)4.073 3.285 (83.4) 3.75

(95.3)

(4) - 0.156ø (4)

0.950 (24.1)

0.704 (17.9)

1.030 (26.1) 0.704 (17.9) 1.040 (26.4)

2.270 (57.7)

1.25 (31.8) 1.25

(31.8) 1.25

(31.8)

3.963 (100.7) 3.963

(100.7)

2.950 (74.9) 2.950

(74.9)

1.475 (37.5) 1.475 (37.5)

NOTE CT & MAIN MODULES CAN BE SPLIT MOUNTED

& INTERFACED WITH CABLE 2.090

(53.1) 2.622 (66.6)

(4) - 0.156Ø (4) 9.833

(249.8) 8.850 (224.8)

REAR VIEW

3.600 (91.5)

4.712 (119.7)

SIDE VIEW FRONT VIEW MOUNTING DETAIL

CT MODULE

MAIN MODULE

SIDE VIEW FRONT VIEW

DISPLAY MODULE

4.00 (101.6) 6.750

(171.5) 1.57

(40) 0.85 (21.6)

COMM PORT TO MAIN MODULE

DISPLAY PORT

252627282930313233343536373839 1 2 3 4 5 6 7 8 9 101112131415

REMOTE CT PORT 161718192021222324

404142 434445464748

WARNING Check voltage switch before installation RUNNING

STOPPED TRIPPED ALARM

RELAY A RELAY B AUX. RELAY 1 AUX. RELAY 2

MESSAGE

VALUE

STOP

CUTOUT

CUTOUT CUTOUT CUTOUT

C

L CL CL

C L MOUNTING DETAIL

SPLIT LINE

809800A1.ai

DIMENSIONS

The motor manager shall generate a trip report each time a trip command is issued. It shall include the cause of the trip and the pre-trip metering values.

Statistical data and routine maintenance alarms shall be included features of the motor manager.

A RS485 ModBus® RTU connection shall be used for communication. It shall support operation at 1200 to 57,600 bps. A RS232/485 converter module can be used to connect a personal computer to the motor manager. Software shall be provided to allow easy access to all features.

A remote panel mount model shall be available with a 2 by 20 character display, control keys, and 10 LEDs to p r o v i d e l o c a l a c c e s s w i t h o u t a computer.

GUIDEFORM SPECIFICATIONS

continued

MM3 * * * *

MM3 Product family

1 Option 1basic unit

2 Option 2 full unit

E ESD relay

A Aux 2 relay

N No display (chassis unit)

W With local display

120 120 VAC control voltage

240 240 VAC control voltage

ORDERING

To order select the basic model and the desired features from the Selection Guide below.

www.GEindustrial.com/pm

Order online –

Referensi

Dokumen terkait

Peran tenaga kerja wanita dilihat dari curahan waktu kerja wanita dalam usahatani kacang tanah yang tertinggi yaitu pada kegiatan penyiangan, kedua panen, ketiga pasca

 Kami Memberikan Garansi 1 Tahun Ganti Baru Kamera Dan Alat Rekam atau DVR.  Lembaran ini Menjadi Bukti Bahwa Telah Terjadinya Transaksi Dengan Pihak

Berdasarkan hasil penelitian yang dilaksanakan pada tanggal 8-14 Mei 2015 di Dusun Tambakrejo Kecamatan Mojoanyar Kabupaten Mojokerto menunjukkan bahwa responden yang

Kalau kita kaji lebih dalam hal tersebut bukan merupakan kesalahan siswa semata tetapi dapat juga disebabkan oleh faktor guru itu sendiri sebagai pendidik .Kekurangan guru

Penelitian ini bertujuan mengevaluasi pengaruh lama penyimpanan formula tepung dalam mempertahankan viabilitas bakteri endofit dan karakterisasi fisiologi isolat endofit Bacillus

terjadi perubahan data fisik atau data yuridis. Setelah Akta Jual Beli telah selesai dibuat maka selanjutnya dilakukan pendaftaran peralihan Hak Milik atas tanah

Hal ini sesuai dengan kategorisasi bahwa Saninten termasuk vegatasi sub montana (1000 – 1500 m dpl) sehingga pada elevasi diatas titik tengah kisaran tersebut

Dari hasil perhitungan diperoleh bahwa ukuran perusahaan tidak mampu memberikan kontribusi yang signifikan terhadap kenaikan leverage pada Perusahaan Food and