Modifications to Ref. 9-1

Dalam dokumen (Belajar Untuk Negri Maju) SNI - FEMA 302 (Halaman 126-135)

Chapter 3 QUALITY ASSURANCE

9.1.1 Modifications to Ref. 9-1

9.1.1.1: Replace Sec. 9.2.3 with Sec. 5.2.7 of these Provisions. Add the following:

9.3.1.2 For load combinations that include earthquake loads, the design strength shall be computed using the strength reduction factors, N, listed in Appendix C.”

9.1.1.2: Insert the following notations in Sec. 21.0:

" = the angle between the diagonal reinforcement and the longitudinal axis.

Ab = the area, in. (mm ) of the shank of the bolt or stud.2 2 Avd = total area of reinforcement in each group of diagonal bars.

= neutral axis depth at and .

Rp = height of the plastic hinge above critical section and which shall be established on the basis of substantiated test data or may be alternately taken at 0.5Rw.

= 1.2D + 0.5L + E.

h = Overall dimension of member in the direction of action considered.

Se Connection = moment, shear, or axial force at connection cross section other than the nonlinear action location corresponding to probable strength at the nonlinear action location, taking gravity load effects into consideration per 21.2.7.3.

Sn Connection= nominal strength of connection cross section in flexural, shear, or axial action per 21.2.7.3.

)E = elastic design displacement at the top of the wall using gross section properties and code-specified seismic forces.

(Mn)/ME))E

Mn) Pu)

)i = inelastic deflection at top of wall = )t - )y. )m = Cd)s.

)s = design level response displacement, which is the total drift or total story drift that occurs when the structure is subjected to the design seismic forces.

)t = total deflection at the top of the wall equal to Cd times the elastic design displacement using cracked section properties or may be taken as (I /I )Cg eff d)E. Ig is the gross moment of inertia of the wall and Ieff is the effective moment of inertia of the wall. Ieff may be taken as 0.5Ig.

)y = displacement at the top of the wall corresponding to yielding of the tension reinforcement at critical section or may be taken as where ME equals moment at critical section when top of wall is displaced )E. is nominal flexural strength of critical section at .

Ny = yield curvature which may be estimated as 0.003/Rw. Q = dynamic amplification factor from 21.2.7.3 and 21.2.7.4.

9.1.1.3: Insert the following definitions in Sec. 21.1:

"Connection -- An element that joins two precast members or a precast member and a cast- in-place member.

Dry Connection -- Connection used between precast members which does not qualify as a wet connection.

"Joint -- The geometric volume common to intersecting members.

"Nonlinear Action Location -- Center of the region of yielding in flexure, shear, or axial action.

Nonlinear Action Region -- The member length over which nonlinear action takes place.

It shall be taken as extending a distance of no less than h/2 on either side of the nonlinear action location.

Strong Connection -- A connection that remains elastic while the designated nonlinear action regions undergo inelastic response under the design basis ground motion.

Wet Connection -- A connection that uses any of the splicing methods, per 21.2.6.1 or 21.3.2.3, to connect precast members and uses cast-in-place concrete or grout to fill the splicing closure.”

9.1.1. 4: Replace Sec. 21.2.1.3 and 21.2.1.4 with the requirements of Sec. 9.4 through 9.7.

Concrete Structure Design Requirements

9.1.1.5: Insert the following new Sec. 21.2.1.6 and 21.2.1.7:

"21.2.1.6 A precast seismic-force-resisting system shall be permitted provided it satisfies either of the following criteria:

"1. It emulates the behavior of monolithic reinforced concrete construction and satisfies 21.2.2.5, or

"2. It relies on the unique properties of a structural system composed of interconnected precast elements and it is demonstrated by experimental evidence and analysis to safely sustain the seismic loading requirements of a comparable monolithic reinforced concrete structure satisfying Chapter 21. Substantiating experimental evidence of acceptable performance of those elements required to sustain inelastic deformations shall be based upon cyclic inelastic testing of specimens representing those elements.

21.2.1.7 In structures having precast gravity load carrying systems, the seismic-force- resisting system shall be one of the systems listed in Table 5.2.2 of the 1997 NEHRP Recommended Provisions and shall be well distributed using one of the following methods:

“1. The seismic-force-resisting system shall be spaced such that the span of the diaphragm or diaphragm segment between seismic-force-resisting systems shall be no more than three times the width of the diaphragm or diaphragm segment. Where the seismic- force-resisting system consists of moment resisting frames, at least (Nb/4) + 1 of the bays (rounded up to the nearest integer) along any frame line at any story shall be part of the seismic-force-resisting system where Nb is the total number of bays along that line at that story. This requirement applies to only the lower two thirds of the stories of buildings three stories or taller.

“2. All beam-to-column connections that are not part of the seismic-force-resisting system shall be designed in accordance with the following:

Connection Design Force. The connection shall be designed to develop strength M. M is the moment developed at the connection when the frame is displaced by )s assuming fixity at the connection and a beam flexural stiffness of no less than one half of the gross section stiffness. M shall be sustained through a deformation of )m.

Connection Characteristics. The connection shall be permitted to resist moment in one direction only, positive or negative. The connection at the opposite end of the member shall resist moment with the same positive or negative sign. The connection shall be permitted to have zero flexural stiffness up to a frame displacement of )m.

In addition, complete calculations for the deformation compatibility of the gravity load carrying system shall be made in accordance with 5.2.2.4.3 of the 1997 NEHRP Recommended Provisions using cracked section stiffness in the seismic- force-resisting system and the diaphragm.

Where gravity columns are not provided with lateral support on all sides, a positive connection shall be provided along each unsupported direction parallel to

a principal plan axis of the structure. The connection shall be designed for a horizontal force equal to 4 percent of the axial load strength, Po, of the column.

The bearing length shall be calculated to include end rotation, sliding, and other movements of precast ends at supports due to earthquake motions in addition to other movements and shall be at least 2 inches more than that required for bearing strength.”

9.1.1.6: Insert the following new Sec. 21.2.2.5, 21.2.2.6 and 21.2.2.7:

"21.2.2.5 Precast structural systems using frames and emulating the behavior of monolithic reinforced concrete construction shall satisfy either 21.2.2.6 or 21.2.2.7.

"21.2.2.6 Precast structural systems utilizing wet connections shall comply with all the applicable requirements of monolithic concrete construction for resisting seismic forces.

"21.2.2.7 Precast structural systems not meeting 21.2.2.6 shall utilize strong connections resulting in nonlinear response away from connections. Design shall satisfy the requirements of 21.2.7 in addition to all the applicable requirements of monolithic concrete construction for resisting seismic forces, except that provisions of 21.3.1.2 shall apply to the segments between nonlinear action locations.

9.1.1.7: Change Sec. 21.2.5.1 as follows and insert the following new Sec. 21.2.5.2 and 21.2.5.3.

21.2.5.1 Except as permitted in 21.2.5.2 and 21.2.5.3, reinforcement resisting earthquake- induced flexural and axial forces in frame members and in wall boundary elements shall comply with ASTM A 706. ASTM A 615 Grades 40 and 60 reinforcement shall be permitted in these members if (a) the actual yield strength based on mill tests does not exceed the specified yield strength by more than 18,000 psi (retests shall not exceed this value by more than an additional 3000 psi), and (b) the ratio of the actual ultimate tensile strength to the actual tensile yield strength is not less than 1.25.

"21.2.5.2 Prestressing tendons shall be permitted in flexural members of frames provided the average prestress, fpc, calculated for an area equal to the member's shortest cross- sectional dimension multiplied by the perpendicular dimension shall not exceed the lesser of 700 psi or fc/6 at locations of nonlinear action where prestressing tendons are used in members of frames.

"21.2.5.3 For members in which prestressing tendons are used together with reinforcement to resist earthquake-induced forces, prestressing tendons shall not provide more than one quarter of the strength for both positive moments and negative moments at the joint face and shall extend through exterior joints and be anchored at the exterior face of the joint or beyond. Anchorages for tendons must be demonstrated to perform satisfactorily for seismic loadings. Anchorage assemblies shall withstand, without failure, a minimum of 50 cycles of loading ranging between 40 and 85 percent of the minimum specified tensile strength of the tendon. Tendons shall extend through exterior joints and be anchored at the exterior face or beyond."

NSn Connection > RSe Connection

Concrete Structure Design Requirements

(21-A)

9.1.1.8: Change Sec. 21.2.6.1 as follows:

21.2.6.1 Reinforcement resisting earthquake-induced flexural or axial forces in frame members or in wall boundary members is permitted to be spliced using welded splices or mechanical connectors conforming to 12.14.3.3 or 12.14.3.4 provided that: (a) not more than alternate bars in each layer of longitudinal reinforcement are spliced at a section and (b) the center-to-center distance between splices of adjacent bars is 24 inches or more measured along the longitudinal axis of the member.

Exception: Items (a) and (b) need not apply where splices are used outside the following locations (i) joints or (ii) where analysis indicates flexural yielding caused by inelastic lateral displacement of the frame.”

9.1.1.9: Insert the following new Sec. 21.2.7:

21.2.7 Emulation of monolithic construction using strong connections. Members resisting earthquake-induced forces in precast frames using strong connections shall satisfy the following:

21.2.7.1 Location. Nonlinear action location shall be selected so that there is a strong column/weak beam deformation mechanism under seismic effects. The nonlinear action location shall be no closer to the near face of strong connection than h/2. For column-to- footing connections where nonlinear action may occur at the column base to complete the mechanism, the nonlinear action location shall be no closer to the near face of the

connection than h/2.

21.2.7.2 Anchorage and splices. Reinforcement in nonlinear action region shall be fully developed outside both the strong connection region and the nonlinear action region.

Noncontinuous anchorage reinforcement of strong connection shall be fully developed between the connection and the beginning of nonlinear action region. Lap splices are prohibited within connections adjacent to a joint.

“21.2.7.3 Design forces. Design strength of strong connections shall be based on:

Dynamic amplification factor, R, shall be taken as 1.0.

21.2.7.4 Column-to-column connection. The strength of such connections shall comply with 21.2.7.3 with Q taken as 1.4. Where column-to-column connections occur, the columns shall be provided with transverse reinforcement as specified in 21.4.4.1 through 21.4.4.3 over their full height if the factored axial compressive force in these members, including seismic effects, exceeds A fg c/10.

Exception: Where column-to-column connection is located within the middle third of the column clear height, the following shall apply: (a) the design moment strength, NMn, of the connection shall not be less than 0.4 times the maximum Mpr for the column within the story height and (b) the design shear strength NVn of the connection shall not be less than that determined per 21.4.5.1.

21.2.7.5 Column-face connection. Any strong connection located outside the middle half of a beam span shall be a wet connection unless a dry connection can be substantiated by approved cyclic test results. Any mechanical connector located within such a column- face strong connection shall develop in tension or compression, as required, at least 40 percent of the specified yield strength, fy, of the bar.”

9.1.1.10: Add the following new Sec. 21.4.5.3:

"21.4.5.3: At any section where the design strength, NPn, of the column is less than the sum of the shear Ve computed in accordance with 21.4.5.1 for all the beams framing into the column above the level under consideration, special transverse reinforcement shall be provided. For beams framing into opposite sides of the column, the moment components may be assumed to be of opposite sign. For determination of the nominal strength, Pn, of the column, these moments may be assumed to result from the deformation of the frame in any one principal axis."

9.1.1.11: Change the reference to Sec. 9.2 in Sec. 21.6.3 to the load combination specified in Sec.

5.2.7 of this document for earthquake forces.

9.1.1.12: Replace Sec. 21.6.4.1 with the following:

21.6.4 Diaphragms used to resist prescribed lateral forces shall comply with the following:

“1. Thickness shall not be less than 2 inches. Topping slabs placed over precast floor or roof elements shall not be less than 2-1/2 inches thick.

“2. Where mechanical connectors are used to transfer forces between the diaphragm and the lateral system, the anchorage shall be adequate to develop 1.4A fs y where As is the connectors cross sectional area.

“3. Collector and boundary elements of topping slabs placed over precast floor and roof elements shall not be less than 3 inches or 6db thick where db is the diameter of the largest reinforcing bar in the topping slab.

“4. Prestressing tendons shall not be used as primary reinforcement in boundaries and collector elements of structural diaphragms. Precompression from unbonded tendons may be used to resist diaphragm forces.”

9.1.1.13 Replace Sec. 21.6.6 with the following:

21.6.6 Design of structural walls for flexural and axial loads:

“21.6.6.1 Structural walls and portions of structural walls subject to combined flexural and axial loads shall be designed in accordance with 10.2 and 10.3 except that 10.3.6 and the nonlinear strain requirements of 10.2.2 do not apply. The strength-reduction factor N shall be in accordance with 9.3

21.6.6.2 Unless a more detailed analysis is made, the design of flanges for I-, L-, C-, or T- shaped sections shall conform to the following:

Concrete Structure Design Requirements

“1. In compression, the effective flange width shall not be assumed to extend further from the face of the web than one-half the distance to an adjacent structural wall web or 15 percent of the total height of the wall above the level considered.

“2. In tension, the amount of reinforcement used shall be not less than that within the web plus a distance on either side, extending from the face of the web, equal to the smallest of 30 percent of the total height of the wall above the level considered, one-half the distance to an adjacent structural wall web, or the actual projection of the flange.

21.6.6.3 Walls and portions of walls with Pu > 0.35Po shall not be considered to contribute to the calculated strength of the structure for resisting earthquake-induced forces. Such walls shall conform to the requirements of 5.2.2.4.3 of the 1997 NEHRP Recommended Provisions.

21.6.6.4 Structural walls and portions of structural walls shall have boundary zones satisfying the requirements of 21.6.6.5, 21.6.6.6, or 21.6.6.7.

21.6.6.5 No boundary zones shall be required if the following conditions exist:

“1. Pu # 0.10A fg c for geometrically symmetrical wall sections Pu # 0.05A fg c for geometrically unsymmetrical wall sections

and either

“2. Mu/Vu wR # 1.0

or

“3. Vu # 3Acv%fc and Mu/Vu wR # 3.0

21.6.6.6 Structural walls and portions of structural walls not satisfying 21.5.6.6.5 shall be provided with boundary zones at each end dimensioned and reinforced in accordance with 21.6.6.9. The horizontal lengths of those boundary zones shall be determined using 21.6.6.7 or 21.6.6.8.

21.6.6.7 Unless a more detailed analysis is made in accordance with 21.6.6.8, boundary zone horizontal lengths shall be assumed to vary linearly from 0.25Rw to 0.15Rw for Pu varying from 0.35Po to 0.15Po. The boundary zone horizontal length shall not be taken as less than 0.15Rw.

21.6.6.8 Requirements for boundary zone horizontal lengths shall be determined based on compressive strain levels at extreme edges when the wall or portion of wall is subjected to displacement levels calculated from Eq. 5.3.7.1 of the 1997 NEHRP Recommended Provisions using cracked shear area and moment of inertia properties and considering the response modifications effects of possible nonlinear behavior of the building.

Boundary zone detail requirements as defined in 21.6.6.9 shall be provided over those portions of the wall, horizontally and vertically, where compressive strains exceed 0.003. In no instance shall designs permit compressive strains greater than 0.015.

Nt ' )i hw & Rp

2 Rp

% Ny

Ash ' 0.09shcfc) fyh

cu) cu)

cu) cu)

(21-B)

(21-C)

For structural walls in which flexural yielding at the base of the wall is the governing state, compressive strains at the extreme edges of walls may be determined as follows:

“1. The total curvature demand, Nt, shall be determined from Eq. (21-B)

“2. If Nt is less than or equal to 0.003/ , boundary zone detailed as defined in 21.6.6.9 are not required. If Nt exceeds 0.003/ , the compressive strains may be assumed to vary linearly over the depth and have maximum value equal to the product of and Nt.

21.6.6.9 Structural wall boundary zone detail requirements. Boundary zone details shall meet the following:

“1. Dimensional requirements:

“1.1 All portions of the boundary zones shall have a thickness of Ru/16 or greater.

“1.2 Boundary zones shall extend vertically a distance equal to the development length of the largest vertical bar within the boundary zone above the elevation where the requirements of 21.6.6.7 or 21.6.6.8 are met.

Extensions below the base of the boundary zone shall conform to 21.4.4.6.

Exception: The boundary zone reinforcement need not extend above the boundary zone a distance greater than the larger of Rw or Mu/4Vu.

“1.3 Boundary zones as determined by the requirements of 21.6.6.8 shall have a minimum length of 18 inches at each end of the wall or portion of wall.

“1.4 In I-, L-, C-, or T-shaped sections, the boundary zone at each end shall include the effective flange width in compression and shall extend at least 12 inches into the web.

“2. Confinement reinforcement:

“2.1 All vertical reinforcement within the boundary zone shall be confined by hoops or cross ties producing an area of steel not less than:

“2.2 Hoops and cross ties shall have a vertical spacing not greater than the smaller of 6 inches or 6 diameters of the smallest vertical bar within the boundary zone.

“2.3 The ratio of the length to the width of the hoops shall not exceed 3. All adjacent

NVn ' 2Nfysin"Avd # 10N fc)bwd

0.83N fc)bwd

Concrete Structure Design Requirements

(21-D)

“2.4 Cross ties or legs of overlapping hoops shall not be spaced further apart than 12 inches along the wall.

“2.5 Alternate vertical bars shall be confined by the corner of a hoop or cross tie.

“3. Horizontal reinforcement:

“3.1 All horizontal reinforcement terminating within a boundary zone shall be anchored in accordance with 21.6.2

“3.2 Horizontal reinforcement shall not be lap spliced within the boundary zone.

“4. Vertical reinforcement:

“4.1 Vertical reinforcement shall be provided to satisfy all tension and compression requirements.

“4.2 Area of reinforcement shall not be less than 0.005 times the area of boundary zone or less than two No. 5 (#16) bars at each edge of boundary zone.

“4.3 Lap splices of vertical reinforcement within the boundary zone shall be confined by hoops or cross ties. Spacing of hoops and cross ties confining lap-spliced reinforcement shall not exceed 4 inches.

9.1.1.14: Add a new Sec. 21.6.7 as follows and renumber existing Sec. 21.6.7 through 21.6.9 to 21.6.8 through 21.6.10:

"21.6.7 Coupling Beams:

"21.6.7.1: For coupling beams with ln/d $ 4, the design shall conform to the requirements of 21.2 and 21.3. It shall be permitted to waive the requirements of 21.3.1.3 and 21.3.1.4 if it can be shown by rational analysis that lateral stability is adequate or if alternative means of maintaining lateral stability is provided.

"21.6.7.2: Coupling beams with ln/d < 4 shall be permitted to be reinforced with two intersecting groups of symmetrical diagonal bars. Coupling beams with ln/d < 4 and with factored shear force Vu exceeding 4%f ’ b d metric equivalent is 0.332 %f ’ b d where fc w c w cN is in MPa and bw and d are in mm)shall be reinforced with two intersecting groups of

symmetrical diagonal bars. Each group shall consist of a minimum of four bars assembled in a core each side of which is a minimum of bw/2. The design shear strength, NVn, of these coupling beams shall be determined by:

where N = 0.85.

The metric equivalent of the expression 10N%f b d, Eq. 21-D, is as follows:c w

where bw and d are in mm and fcN is in MPa.