4. REKOMENDASI HASIL PEMELIHARAAN
4.4 Shutdown Function Check
5. Uji fungsi
annunciatordan alarm
Audible Alarm tidak bunyi
Lampu tidak nyala
Pemeriksaan kondisi Alat Periksa pengawatan Alat Pemeriksaan kondisi lampu Pemeriksaan pengawatan annunciator dan auxiliary relay
Diganti
Lampiran 1 TABEL PERIODE PEMELIHARAAN PROTEKSI DAN KONTROL PENGHANTAR
KODE SUBSISTEM ITEM PEKERJAAN
HARIAN MINGGUAN BULANAN 3 BULAN 1 TAHUN 2 TAHUN 6 TAHUN KONDISIONAL
KETERANGAN
15 Proteksi dan Kontrol Penghantar 15.1 Inspeksi
15.1.1 Inspeksi level -1 ( In service inspection) Peralatan Proteksi Utama
15.1.1.1 Distance Relay + DEF Pengecekan kesiapan Distance Relay + DEF
●
15.1.1.2 Current Differential Relay Pengecekan kesiapan Current Differential Relay
●
15.1.1.2 Pilot Differential Cable Relay Pengecekan kesiapan Pilot Differential Cable Relay
●
Peralatan Proteksi Cadangan
15.1.1.3 OCR/GFR Pengecekan kesiapan OCR/GFR
●
15.1.1. Relay breaker failure Pengecekan kesiapan Breaker Failure Relay
●
Relay skeme khusus
15.1.1.4 Under/Overvoltage Relay Pengecekan kesiapan Under/Overvoltage Relay
●
15.1.1.5 Overload Shedding Pengecekan kesiapan Overload Shedding
●
15.1.1. Trip Circuit Supervision Pengecekan kesiapan Rangkaian Tripping
●
KODE SUBSISTEM ITEM PEKERJAAN
HARIAN MINGGUAN BULANAN 3 BULAN 1 TAHUN 2 TAHUN 6 TAHUN KONDISIONAL
KETERANGAN
Kondisi umum panel proteksi
15.1.1 Suhu, Kelembaban ruangan dan panel Pengukuran suhu dan kelembaban ruangan dan panel
dengan thermometer dan higrometer
●
15.1.1. Suara Normal/Tidak Normal
●
15.1.1 Bau Normal/Bangkai/Hangus
●
15.1.1. Kondisi panel Normal/Kotor/Lembab
●
15.1.1 Lampu penerangan panel Normal/Redup/Tidak berfungsi/Tidak ada
●
15.1.1. Heater Normal/Rusak/ Tidak ada
●
15.1.1 Pintu panel Normal/Korosi/Tidak bisa dikunci/Rusak
●
15.1.1. Door sealant Normal/Tidak Elastis/Putus/Tidak ada
●
15.1.1 Lubang kabel kontrol Normal/Tidak rapat/Glen kabel tidak ada
●
15.1.1. Grounding panel Normal/Korosi/Rantas/Kendor/Tidak ada
●
Kondisi panas diukur dengan menggunakan thermal image
15.1.1 Kabel control Normal/cacat
●
KODE SUBSISTEM ITEM PEKERJAAN
HARIAN MINGGUAN BULANAN 3 BULAN 1 TAHUN 2 TAHUN 6 TAHUN KONDISIONAL
KETERANGAN
15.1.1. Terminal wiring Kencang/kendor
●
15.1.1 Body relay Normal/panas
●
15.1.1. ACT (ACT jenuh untuk meter) Normal/panas
●
15.1.1 Inspeksi level -1 ( In service inspection) Kondisi meter pada panel kontrol
15.1.1 Kondisi Amperemeter (R,S,T) Normal/Tidak Normal
●
15.1.1. Kondisi KV Meter (R,S,T) Normal/Tidak Normal
●
15.1.1 Kondisi MW Meter Normal/Tidak Normal
●
15.1.1. Kondisi Mvar Meter Normal/Tidak Normal
●
15.1.1 KWH Meter IN Normal/Tidak Normal
●
15.1.1. KWH Meter OUT Normal/Tidak Normal
●
15.1.1 KondisiSynchrocheck Relay Normal/Tidak Normal
●
15.1.1. Annunciator Pengecekan kondisi Annunciator (lamp test & horn)
●
KODE SUBSISTEM ITEM PEKERJAAN
HARIAN MINGGUAN BULANAN 3 BULAN 1 TAHUN 2 TAHUN 6 TAHUN KONDISIONAL
KETERANGAN
15.1.2
Inspeksi level -2 ( In service measurement, dilakukan sebelum dan sesudah shutdown Pemeliharaan 2 tahun)
15.1.2. Arus Pemeriksaan besaran arus fasa R, S dan T dengan tang
ampere
●
15.1.2. Tegangan Pemeriksaan besaran tegangan fasa R, S dan T pada relay
dan meter
●
15.1.2. Sumber DC Pengukuran besaran sumber DC di panel proteksi
penghantar
●
15.1.2. Riple catu daya Pengukuran ripple catu daya di panel proteksi penghantar
●
15.1.3 Inspeksi level -3 ( Shutdown measurment ) Peralatan proteksi utama
15.1.3.1 Distance relay + DEF Pengujian individu
●
*)15.1.3.1 Pengujian fungsi trip, SPAR, TPAR
●
15.1.3.1 Pengujian fungsi teleproteksi
●
*)15.1.3.1 Pengujian fungsi recorder internal (DFR, Event)
●
*)15.1.3.1 Fault locator
●
*)15.1.3.2 Current Differential Relay Pengujian individu
●
*)KODE SUBSISTEM ITEM PEKERJAAN
HARIAN MINGGUAN BULANAN 3 BULAN 1 TAHUN 2 TAHUN 6 TAHUN KONDISIONAL
KETERANGAN
15.1.3.2 Pengujian fungsi trip, SPAR, TPAR
●
15.1.3.2 Pengujian fungsi recorder internal (DFR, Event)
●
*)15.1.3.2 Pilot Differential Cable Relay Pengujian individu
●
*)15.1.3.2 Pengujian fungsi trip, SPAR, TPAR
●
15.1.3.2 Pengujian fungsi recorder internal (DFR, Event)
●
*)Keterangan *) : Inspeksi level -3 ( Shutdown measurment ) Pengujian individu relay jenis digital dan numeric dilakukan 6 tahun.
15.1.3 Inspeksi level -3 ( Shutdown measurment ) Peralatan proteksi cadangan
15.1.3.3 OCR/GFR Pengujian individu
●
*)15.1.3.3 Pengujian fungsi trip
●
15.1.3.3 Pengujian fungsi recorder internal (DFR, Event)
●
*)15.1.3 Relay Breaker Failure Pengujian individu
●
15.1.3 Pengujian fungsi trip
●
15.1.3 Pengujian fungsi recorder internal (DFR, Event)
●
KODE SUBSISTEM ITEM PEKERJAAN
HARIAN MINGGUAN BULANAN 3 BULAN 1 TAHUN 2 TAHUN 6 TAHUN KONDISIONAL
KETERANGAN
15.1.3 Relay skeme khusus
15.1.3.4 Under/Overvoltage relay Pengujian individu
●
*)15.1.3.4 Pengujian fungsi trip
●
15.1.3.4 Pengujian fungsi recorder internal (DFR, Event)
●
*)15.1.3.5 Overload shedding Pengujian individu
●
*)15.1.3.5 Pengujian fungsi trip
●
15.1.3.5 Pengujian fungsi recorder internal (DFR, Event)
●
*)15.1.3.3 Directional OCR/GFR Pengujian individu
●
*)15.1.3.3 Pengujian fungsi trip
●
15.1.3.3 Pengujian fungsi recorder internal (DFR, Event)
●
*)15.1.3.4 Pengujian Relai tegangan lebih/kurang
(OVR/UVR) Pengujian individu
●
*)15.1.3.4 Pengujian fungsi trip
●
15.1.3.4 Pengujian fungsi recorder internal (DFR, Event)
●
*)KODE SUBSISTEM ITEM PEKERJAAN
HARIAN MINGGUAN BULANAN 3 BULAN 1 TAHUN 2 TAHUN 6 TAHUN KONDISIONAL
KETERANGAN
15.1.3.5 Pengujian Relai beban lebih (OLS) Pengujian individu
●
*)15.1.3.5 Pengujian fungsi trip
●
15.1.3.5 Pengujian fungsi DTT
●
15.1.3.5 Pengujian fungsi recorder internal (DFR, Event)
●
*)Keterangan *) : Inspeksi level -3 ( Shutdown measurment ) Pengujian individu relay jenis digital dan numeric dilakukan 6 tahun.
Lampiran 2 FMEA PROTEKSI DAN KONTROL PENGHANTAR
Lampiran 3 Jenis Pengujian Fungsi SPAR
PROTEKSI SIMULASI GANGGUAN SWITCH A/R
Zona 1 Fasa-Netral Injeksi Sekunder ФR ON
DEF Fasa-Netral +Receive Injeksi Sekunder ФS ON
ZONE 2 Fasa-Netral +Receive Injeksi Sekunder ФT ON
ZONE 1 Fasa-Fasa Injeksi Sekunder ФR-S/S-T/T-R ON
Lampiran 4 Jenis Pengujian Fungsi TPAR
PROTEKSI SIMULASI GANGGUAN SWITCH A/R
Zona 1 Fasa-Netral Injeksi Sekunder ФR/ ФS/ ФT ON
Zona 1 Fasa-Netral Injeksi Sekunder ФRS ON
Zona 1 Fasa-Netral Injeksi Sekunder ФST ON
Zona 1 Fasa-Fasa Injeksi Sekunder ФTR ON
Zona 2 Fasa-Fasa +Receive Injeksi Sekunder ФRS/ST/TR ON Zona 1 Fasa-Fasa (Permanen) Injeksi Sekunder ФRS/ST/TR
(pada saat reclaim time)
ON
Zona 1 3 Fasa Injeksi Sekunder ФR-S-T ON
Zona 1 Fasa-Netral Injeksi Sekunder ФR/ ФS/ ФT OFF Zona 1 Fasa-Fasa Injeksi Sekunder ФR-S/S-T/T-R OFF
Lampiran 5 Jenis Pengujian FungsiEvolving Fault
PROTEKSI SIMULASI GANGGUAN SWITCH A/R
Zona 1 Fasa-Netral Injeksi Sekunder ФR ON
Zona 1 Fasa-Netral Injeksi Sekunder ФS/T (setelah PMT trip)
ON Zona 2 Fasa-Netral +
Receive
Injeksi Sekunder ФS ON
Zona 2 Fasa-Netral + Receive
Injeksi Sekunder ФR/T (setelah PMT trip)
ON Zona 1 Fasa-Netral
(Permanen)
Injeksi Sekunder ФT ON
Zona 1 Fasa-Fasa Injeksi Sekunder ФR/S (setelah PMT trip)
ON
Lampiran 6 Jenis PengujianDistance RelaySkema PUTT
Type Of Fault/Zones
GI:
Type Of Fault/Zones
GI:
Signal
Time [s]
Indication Signal
Time [s]
Indication
R-N/ Zone 1 R-N/ Zone 2
S-N/ Zone 1 S-N/ Zone 2
T-N/ Zone 1 T-N/ Zone 2
S-T/ Zone 1 S-T/ Zone-2
R-N/ Zone 2 R-N/ Zone 1
S-N/ Zone 2 S-N/ Zone 1
T-N/ Zone 2 T-N/ Zone 1
R-S/ Zone-2 R-S/ Zone-1
R-N/ 10%
Zone 1 Reverse
R-N/ 110%
Z Line
S-N/ 110%
Z Line
S-N/ 10%
Zone 1 Reverse
S-N/ DEF Forward
S-N/ DEF Forward T-N/ DEF
Forward
T-N/ DEF Reverse R-N/ DEF
Reverse
R-N/ DEF Forward
Lampiran 7 Jenis PengujianDistance RelaySkema POTT
Type Of Fault/Zones
GI:
Type Of Fault/Zones
GI:
Signal
Time [s]
Indication Signal
Time [s]
Indication
R-N/ Zone 2 R-N/ Zone 2
S-N/ Zone 2 S-N/ Zone 2
T-N/ Zone 2 T-N/ Zone 2
R-T/ Zone-2 R-T/ Zone-2
R-N/ 10%
Zone 1 Reverse
R-N/ 110%
Z Line S-N/ 110%
Z Line
S-N/ 10%
Zone 1 Reverse
S-N/ DEF Forward
S-N/ DEF Forward T-N/ DEF
Forward
T-N/ DEF Reverse R-N/ DEF
Reverse
R-N/ DEF Forward
Lampiran 8 Jenis PengujianDistance RelaySkema Blocking
Type Of Fault/Zones
GI:
Type Of Fault/Zones
GI:
Signal
Time [s]
Indication Signal
Time [s]
Indication
R-N/ Zona 1 R-N/ Zona 2
R-S/ Zona 1 R-S/ Zona 2
S-N/ Zona 3
Reverse S-N/ Zona 2
S-T/ Zona 3
Reverse S-T/ Zona 2
T-N/ Zona 2 T-N/ Zona 1
R-T/ Zona 2 R-T/ Zona 1
R-N/ Zona 2 R-N/ Zona 3
Reverse
R-S/ Zona 2 R-S/ Zona 2
Reverse
S-N/ DEF Forward
S-N/ DEF Forward T-N/ DEF
Forward
T-N/ DEF Reverse R-N/ DEF
Reverse
R-N/ DEF Forward
Lampiran 9 Uji Fungsi Trip PMTSingle Phase
No Simulasi
Gangguan Indikasi Relai
Kondisi PMT
R S T
1. Injeksi Fasa R R-N Trip NTrip NTrip
2. Injeksi Fasa S S-N NTrip Trip NTrip
3. Injeksi Fasa T T-N NTrip NTrip Trip
Lampiran 10 Uji FungsiTripPMTThree Phase
No Simulasi
Gangguan
Indikasi Relai
Kondisi PMT
R S T
1. Injeksi Fasa R R-N Trip Trip Trip
2. Injeksi Fasa S S-N Trip Trip Trip
3. Injeksi Fasa T T-N Trip Trip Trip
Lampiran 11 Formulir Rekap Pengujian Sistem Proteksi
NO URAIAN Check List KETERANGAN
1 Daerah kerja Distance Relay Uji individu
2 Power Swing Block (PSB) Uji individu
3 Switch On to Fault (SOTF) Uji fungsi
4 Fuse Failure Uji fungsi
5 Syncrho Check Relay Uji individu
6 Auto Reclose Uji fungsi
7 Intertripping PUTT Uji individu
8 Weak end Infeed 9 Fault Locator 10 Oscillography
11 TCS (Trip Circuit Supervision) 12 MCB CVT Trip
13 Sinyal Teleproteksi (PLC)
14 Arah Pengamanan Distance relay 15 Karakteristik OCR / GFR
16 Trip PMT dari Distance Relay 15 Trip PMT dari OCR / GFR
REKAP PENGUJIAN SISTEM PROTEKSI BAY LINE ...
Region / UPT :
GI :
Bay :
Tanggal / Jam Inpeksi :
Pelaksana :
I. Kondisi Relai Proteksi
1 Proteksi Utama Distance Relay (21) / Pilot Differential Cable (87PW) 9 Normal 1 Tidak Normal
2 Proteksi Cadangan Over Current / Ground Fault Relay 9 Normal 1 Tidak Normal
3 Trip Circuit Supervision 9 Normal 1 Tidak Normal
4 Recloser 9 Normal 1 Tidak Normal ket : Internal / eksternal
Counter Reclose …. 1 phasa …. 3 phase
5 Synchrocheck 9 Normal 1 Tidak Normal
6 Breaker Failure 9 Normal 1 Tidak Normal
7 Proteksi Skema Khusus
Under Frequency Relay Frekuensi Relai 9 Normal 1 Tidak Normal Tidak Terpasang
Relai Tegangan Nol 9 Normal 1 Tidak Normal Tidak Terpasang
Overload Shedding Overcurrent Relai 9 Normal 1 Tidak Normal Tidak Terpasang
8 Differential Cable 9 Normal 1 Tidak Normal Tidak Terpasang
Mengetahui, Pemeriksa,
Supervisor…….
(………) (………)
FORMULIR CHECK LIST INSPEKSI LEVEL 1 : PANEL PROTEKSI & KONTROL BAY LINE
Catatan Tambahan
PT. PLN ( PERSERO )
PENYALURAN DAN PUSAT PENGATUR BEBAN JAWA BALI
Lampiran 12 Formulir Check List Inspeksi Harian
Region / UPT :
GI :
Bay :
Tanggal / Jam Inpeksi :
Pelaksana :
I. Kondisi Lingkungan : Ruang Proteksi
1 Suhu Ruangan ….. Celcius 9 <25 deg 6 25 deg<T< 50deg 1 > 50 deg
2 Kelembaban ….. % 9 90%
II. Kondisi Umum Panel Proteksi
1 Kondisi dalam Panel 9 Normal 6 Kotor 6 Lembab
2 Lampu Penerangan 9 Normal 6 Redup 6 Tidak berfungsi 6 Hilang
3 Heater 9 Normal 6 Rusak 6 Hilang
4 Pintu Panel 9 Normal 6 Korosi 6 Tidak bisa dikunci 6 Hilang
5 Door Sealant 9 Normal 6 Tidak elastis 6 Putus 6 Hilang
6 Lubang Kabel Kontrol 9 Normal 6 Tidak rapat 6 Glen Kabel tidak ada
7 Suara 9 Normal 6 Tidak Normal
8 Bau 9 Normal 6 Bangkai 1 Gosong
9 Grounding Panel 9 Normal 6 Korosi 6 Rantas 1 Kendor 1 Putus 1 Hilang
10 9 Normal 6 Korosi 1 Panas (pengukuran thermovision)
11 Kabel Kontrol 9 Normal 6 Terkelupas
III. Kondisi Lingkungan : Ruang Kontrol
1 Suhu Ruangan ….. Celcius 9 <25 deg 6 25 deg<T< 50deg 1 > 50 deg
2 Kelembaban ….. % 9 45 % - 85 % 6 < 45 % atau > 85%
IV. Kondisi Umum Panel Kontrol
1 Kondisi dalam Panel 9 Normal 6 Kotor 6 Lembab
2 Lampu Penerangan 9 Normal 6 Redup 6 Tidak berfungsi 6 Hilang
3 Heater 9 Normal 6 Rusak 6 Hilang
4 Pintu Panel 9 Normal 6 Korosi 6 Tidak bisa dikunci 6 Hilang
5 Door Sealant 9 Normal 6 Tidak elastis 6 Putus 6 Hilang
6 Lubang Kabel Kontrol 9 Normal 6 Tidak rapat 6 Glen Kabel tidak ada
7 Suara 9 Normal 6 Tidak Normal
8 Bau 9 Normal 6 Bangkai 1 Gosong
9 Grounding Panel 9 Normal 6 Korosi 6 Rantas 1 Kendor 1 Putus 1 Hilang
10 9 Normal 6 Korosi 1 Panas (pengukuran thermovision)
11 Kabel Kontrol 9 Normal 6 Terkelupas
V. Kondisi Alat Ukur & Indikasi
1 Ampere Meter 9 Normal 1 Rusak Ket:
2 KV Meter RST 9 Normal 1 Rusak Ket:
Selector Switch 9 Normal 1 Tidak Normal ket:
3 MW Meter 9 Normal 1 Rusak Ket:
4 Mvar Meter 9 Normal 1 Rusak Ket:
5 kWh Meter
a KWh IN 9 Normal 1 Rusak Ket:
b KWh OUT 9 Normal 1 Rusak Ket:
6 Announciator Lampu 9 Normal 1 tidak normal
ket : Normal ketika tombol test ditekan semua Lampu menyala
Mengetahui, Pemeriksa,
Supervisor…….
FORMULIR CHECK LIST INSPEKSI LEVEL 1 : PANEL PROTEKSI & KONTROL BAY LINE
Terminasi Wiring
Terminasi Wiring
Catatan Tambahan
PT. PLN ( PERSERO )
PENYALURAN DAN PUSAT PENGATUR BEBAN JAWA BALI
Lampiran 13 Formulir Check List Inspeksi Bulanan
DAFTAR ISTILAH
1. Inservice
Peralatan penyaluran tenaga listrik dalam kondisi bertegangan.
2. Inservice Inspection
Pemeriksaan Peralatan penyaluran tenaga listrik dalam kondisi bertegangan menggunakan panca indera.
3. Inservice Measurement
Pengujian atau pengukuran peralatan penyaluran tenaga listrik dalam kondisi bertegangan menggunakan alat bantu.
4. Shutdown Testing/Measurement
Pengujian/pengukuran Peralatan penyaluran tenaga listrik dalam kondisi tidak bertegangan.
5. Shutdown Function Check
Pengujian fungsi peralatan penyaluran tenaga listrik dalam kondisi tidak bertegangan.
6. Pengujian /Pemeriksaan Setelah Gangguan
Pengujian / Pemeriksaan yang dilakukan setelah terjadi gangguan pada peralatan penyaluran tenaga listrik.
7. FMEA (Failure Mode Effect Analysis)
Metode evaluasi peralatan untuk meningkatkan availability dengan cara mendeteksi kemungkinan – kemungkinan kelemahan desain dan penyebab kerusakan dominan.
8. Tuning
Penalaan relai elektromekanik sehingga sesuai dengan nilai setting yang diinginkan.
9. Level Tegangan 66 KV
Level tegangan 66 KV termasuk untuk peralatan yang dioperasikan 70 KV.
10. Waktu Pembebasan Gangguan (Fault Clearing Time)
Rentang waktu sejak gangguan muncul sampai gangguan dibebaskan dari sistem.