PATIMBAN PORT ADDITIONAL HIGHMAST LAMPS PROJECT
INSTALLATION METHOD
HIGHMAST LIGHTING
1. OVERVIEW OF THE SYSTEM
HIGH MAST LIGHTING SYSTEM
ADDITIONAL LIGHTING SIMULATION 3. OPERATING THE EQUIPMENT
OPERATING THE HIGH MAST POLE
WORKING AREA COVERAGE
PANEL BOX HIGH MAST
LIGHTING INSTALLATION
AIMING HIGH MAST LIGHTING SYSTEMINSTALLATION METHOD :
2. INTRODUCTION OF THE MAIN EQUIPMENT
HIGH MAST LIGHTING ADDITIONAL
DRAWING POWER SUPPLY3. ADDITIONAL METHOD 4. TIME LINE
PATIMBAN PORT ADDITIONAL HIGHMAST LAMPS PROJECT
: High Mast Lighting System Existing
: High Mast Lighting System Additional
LEGEND:
2
set
5
set
5set
1.1 High Mast Lighting Additional
GENSET 650KVA, 0.4KV TR G
1250KVA LIGHTING SYSTEM
POWER SUPPLY
LVSB‐AD (LVMDB)
MDB‐L
T.1 MDB‐L
T.2 MDB‐L
T.3
HMP1.1 HMP
5.1 HMP
HMP 2.3
3.1 HMP
5.2 HMP
HMP 2.3
2.1 HMP
3.2 HMP
5.3 HMP
HMP 4.1
1.2 HMP
5.4 HMP
4.2
LP‐ FEG LP‐ OM LVDB
LVDB EF LVDB B CD
LVDB A LVSB‐XR
C A P
N P
P L N
A T S
E P MV‐SWGR
RMU‐AD
1.2 Drawing Power Supply
HMP SPARE MCB
NYM CABLE 3x4mm2 + FLEXIBLE CONDUIT
ADD LIGHTING UNIT
2.1. HIGH MAST LIGHTING SYSTEM
PATIMBAN PORT ADDITIONAL HIGHMAST LAMPS PROJECT
NYM Cable 3x4mm2 + Flexible Conduit Connecting for Additional Lamps
Spare MCB for each group
2.2 ADDITIONAL LIGHTING SIMULATION LEGEND:
: New Additional Lamps Directions (12 set) : Existing Wide Lamps
Directions
: Existing Narrow Lamps Directions
2
set
5
set
5set
2.2A. ADDITIONAL LIGHTING SIMULATION (BEFORE & AFTER)
PATIMBAN PORT ADDITIONAL HIGHMAST LAMPS PROJECT
BEFORE AFTER
Ensure to Check all the locking
the cable so it will not entangled
Lower until all support holds the ring safely
Lower the ring carefully while arranging
Install Ring Support
Turn OFF all sub mcb except for motor
Take off socket Clear Surround Area before lowering plug inside HMP
Lower the ring using provided remote
3.1. Operating The High Mass Pole (By Others)
PATIMBAN PORT ADDITIONAL HIGHMAST LAMPS PROJECT 3.2. Panel Box High Mast
813 Watt 813 Watt 749 Watt
Existing Lamp
Existing Lamp Each Ring Layer 8 set with 3 Layer the total lighting unit 24 set
Spare MCB Slot 12
3 4 5
6 7
Existing MCB 10A is 7 set Maximum for 35 set Lighting Unit
MCB 3P 20A
749 Watt
ADD LIGHTING UNIT 960 Watt ADD LIGHTING UNIT
960 Watt
3.3. Working Area Coverage
PATIMBAN PORT ADDITIONAL HIGHMAST LAMPS PROJECT
Additional Lamps can be mounted using scaffolding with wheels approx. 2 layers about 3 meters height
New Type Panasonic Lamps will be mounted using : 1. Mounted Direct Drill & Mounting using Nut & Bolt
15 cm Galvanized
2. NYM 3x4mm2 Cable c/w Flexible Conduit
Following Lighting Simulation Each Pole Each Ring
3.3. Lighting Installation
Aiming Process still using Scaffolding c/w Wheels & Following from Lighting Simulations Coordinate One By One during Day Light Work Hours
3.4. Aiming High Mast Lighting System
PATIMBAN PORT ADDITIONAL HIGHMAST LAMPS PROJECT
4. ADDITIONAL METHODE
5. TIME LINE
TIME SCHEDULE
PEKERJAAN PEMASANGAN LAMPU HIGH MAST PATIMBAN INTERNATIONAL CAR TERMINAL
NO KETERANGAN
DECEMBER 2023
MINGGU 1 MINGGU 2 MINGGU 3 MINGGU 4
4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 1 Pekerjaan pendahuluan
MINGGU MINGGU MINGGU MINGGU
2 Pemasangan instalasi kabel & lampu 3 Pemasangan instalasi di box panel dan
control
4 Perapihan support out door 5 Test Comm
Keterangan :
Pekerjaan Pendahuluan a. Persiapan Tempat b. Persiapan Alat Kerja c. Perijinan Kerja d. Persiapan Direksi Kit e. Persiapan Mess Pekerja
Pemasangan Instalasi Kabel & Lampu a. Persiapan Zona Area Instalasi b. Off Panel Utama
c. Off Panel Sekunder
d. Peniurunan ring Lampu Pole via Operator e. Persiapan alat bantu kerja (Scaffolding) f. Pembolongan lubang diudukan bracket lamppu g. Pemasangan lampu
h. Penyambungan kabel & flexible conduit
Pemasangan Instalasi Box Panel a. Penambahan/Penggantian MCB 20A Perapihan support out door
a. Penaikkan ring lampu Pole via Operator b. Pembersihan area kerja
Test Commisioning
a. Test nyala dan iluminasi sesuai design dari Pak Agung Principal Panasonic
PATIMBAN PORT ADDITIONAL HIGHMAST LAMPS PROJECT