Standard Of Procedure (SOP)

NCU M830B Settings

(2)

A. Koneksi Notebook ke Controller (NCU M830B)

A.1 Web browser yang di gunakan :

● Internet Explorer

● Firefox

● Google Chrome

● Safari

A.2 NCU M830B (Controller)

● IP default 192.168.100.100, Subnet Mask : 255.255.255.0 A.3 Setting Notebook

● Setting ip 192.168.100.103

● Disable proxy

● Kabel Ethernet (straight)

A.4 Koneksi dan login ke Controller NCU M830B

● User : admin

● Password : 640275 (default)

(3)

Tampilan NCU M830B

(4)

B. Parameter Settings

B.1 Site Settings

o Settings Quick Settings  Site Settings

▪ Isi Site Name pada “Set Value” : JKT234, lalu click “Set” (contoh)

▪ Isi Site location pada “Set Value” : Jaksel, lalu click “Set” (contoh)

▪ Isi System Name pada “Set Value” : 3M2B, lalu click “Set” (contoh)

B.2 Time Settings

o Settings  Quick Settings  Time Settings

▪ Click “ Get Local Time from Connected PC”  Click “Set”

Catatan : Pastikan time pada controller sesuai dengan waktu di PC

(5)

B.3 Setting input low voltage alarm

o Settings System AC Equipment

▪ Main failure Alarm Limit 1 : isi pada “Set Value” : 9 lalu click “Set”

▪ Main failure Alarm Limit 2 : isi pada “Set Value” : 9 lalu click “Set”

(6)

B.3 Settings Battery Charge

o Settings Battery Charge

▪ Float Charge Voltage : isi pada “set value” : 54 lalu click “Set”

▪ Equalize Charge Voltage : isi pada “set value” : 56.5 lalu click “Set”

▪ Battery Current Limit : isi pada “set value” : 0.1 lalu click “Set”

▪ Temp Comp Coeffecient (Slope): isi pada “set value” : 72 lalu click “Set”

▪ Comp Temp High 1 : isi pada “set value” : 45 lalu click “Set”

▪ Comp Temp High 2 : isi pada “set value” : 45 lalu click “Set”

▪ Over Voltage 1 alarm : isi pada “set value” : 57 lalu click “Set”

▪ Over Voltage 2 alarm : isi pada “set value” : 58 lalu click “Set”

▪ Under Voltage 1 Alarm : isi pada “set value” : 48 lalu click “Set”

▪ Under Voltage 2 Alarm : isi pada “set value” : 48 lalu click “Set”

▪ Batt1 Rated Capacity : isi pada “set value” : 300 lalu click “Set”

⮚ (di sesuaikan dengan kapasitas battery yang di install)

⮚ Lakukan “Reset Battery Capacity” setiap dilakukan perubahan

▪ Batt1 Shunt Current : isi pada “set value” : 300 lalu click “Set”

▪ Batt1 Shunt Voltage : isi pada “set value” : 25 lalu click “Set”

(7)
(8)

B.4 Settings LVD (Low Voltage Disconnect) o Settings LVD

▪ LVD1 (LLVD) :

⮚ LVD 1 : pada set value “Enable” lalu click “Set”

⮚ LVD 1 Mode : pada set value “Voltage” lalu click “Set”

⮚ LVD 1 Voltage : pada set value “45” lalu click “Set”

▪ LVD2 (BLVD) :

⮚ LVD 2 : pada set value “Enable” lalu click “Set”

⮚ LVD 2 Mode : pada set value “Voltage” lalu click “Set”

⮚ LVD 2 Voltage : pada set value “43.2” lalu click “Set”

⮚ LVD Contactor Type : pada set value “Mono Stable” lalu click “Set”

(9)

B.5 Alarm Relay (Digital output) B.5.1 Main failure Alarm

o Advanced Settings Alarm Please select Equipment type : Rectifier AC

▪ Pilih index 25. Main failure, click “Modify” lalu isi “ relay number” : 1, click “Set”

(10)

B.5.2 Over Voltage dan Under Voltage Alarm

o Advanced Settings Alarm Please select Equipment type : Power System

▪ Pilih index 32. Over Voltage 1, click “Modify”, lalu isi “relay number”:

2, click “Set”

▪ Pilih index 33. Over Voltage 2, click “Modifiy” lalu isi “ relay number” : 2, click “Set”

▪ Pilih index 34. Under Voltage 1, click “Modify” lalu isi “ relay number”:

2, click “Set”

▪ Pilih index 35. Under Voltage 2, Click “Modify” lalu isi “ relay number”

2, click “Set”

(11)

B.5.3 Rectifier Alarm

o Advanced Settings Alarm Please select Equipment type : Rectifier Group

▪ Pilih index 3. ECO Active, Click “Modify” lalu isi “relay number” : 3, click “Set”

▪ Pilih index 4. All rectifier Comm fail, click “Modify” lalu isi “relay number” : 3, click “Set”

▪ Pilih index 5. ECO Cycle Alarm, click “Modify” lalu isi “relay number” : 3, click “Set”

(12)

o Advanced Settings Alarm Please select Equipment type : Rectifier

▪ Pilih index 1, AC Input Fail lalu click “Modify” isi “relay number” : 3, click set.

▪ Ulangi langkah di atas untuk index 2 – 12.

(13)

B.5.4 LVD2 Disconnect Alarm

o Advanced Settings  Alarms  Please select equipment type : LVD Unit Pilih index 2. LVD 2 Disconnect, lalu click “Modify” isi “relay number” : 4, click “Set”

(14)

B.5.5 Door Open Alarm

o Advanced Settings  DI Alarm

▪ Pilih index 2. Door Open Alarm, lalu click “Modify” isi “relay number” : 5, click set

(15)

B.5.6 Battery Stolen Alarm

o Advanced Settings  DI Alarm

▪ Pilih index 6, lalu click “Modify” isi “Signal Alarm” : Battery Stolen 1 Alarm, isi “alarm relay” : 6, click “Set”

▪ Pilih index 7, lalu click “Modify” isi “Signal Alarm” : Battery Stolen 2 Alarm, isi “alarm relay” : 6, click “Set”

o Settings  System

▪ Pilih DI6 Alarm state, tick “ low” lalu click “Set”

▪ Pilih DI7 Alarm state, tick “ low” lalu click “Set”

o Advanced Settings  Alarm  Please select equipment type : EIB

▪ Pilih index 2, bad battery block, click “Modify” isi “relay number” : None, isi “alarm level” : None

(16)
(17)

B.5.7 Smoke Alarm

o Advanced Settings  DI Alarm

▪ Pilih index 5. Click “Modify” lalu isi “Signal Name” : Smoke Alarm, isi

“Alarm relay” : 7, click “Set”

(18)

B.5.8 High Temp Alarm

o Advanced Settings  Alarm  Please select equipment type : power system

▪ Pilih index 69. System Temp1 High 1, Click “Modify” isi “relay number” : 8, click “Set”

o Advanced Settings Alarm Please select equipment type : Battery Group

▪ Pilih index 18. Comp Temp High1, Click “Modify” isi “relay number” : 8, click “Set”

▪ Pilih index 19. Comp Temp High2, Click “Modify” isi “relay number” : 8, click “Set”

(19)
(20)

C. Reboot Controller

o Advanced Settings  SW Maintenance  Reboot Controller

(21)

D. EIB 1 dan IB 1 Board

Extended Interface Board (EIB 1) Interface Board ( IB 1) Extended Interface Board (EIB)

DO1 DO2 DO3 DO4 DO5

S h u n t - 1 -

S h u n t - 1 +

S h u n t - 2 -

S h u n t - 2 +

S h u n t - 3 -

S h u n t - 3 +

D C V - 1

D C V - 2

D C V - 3

D C V - 4

D C V - 5

D C V - 6

D C V - 7

D C V - 8

N A

N C

C O M

N O

N C

C O M

N O

N C

C O M

N O

N C

C O M

N O

N C

C O M

N O

1 2 3 4 5 6 1 2 3 4 5 6 1 3 5 2 4 6 1 3 5 2 4 6 1 3 5 2 4 6

DI DO

J6 1 J6 2

1 3 5 2 4 6

J5 J6 J7 J8 J9

1 3 5 1 3 5 1 3 5 1 3 5 2 4 6 2 4 6 2 4 6 2 4 6

Bank-1 Bank-2

(22)

J5 J6 J7 J8 J8

Interface Board (IB1) o Digital Input (DI)

o Digital Output (DO)

+ + + + + + + + _ _ _ _ _ _ _ _

DI1+ DI2+ DI3+ DI4+ DI5+ DI6+ DI7+ DI8+

DI1- DI2- DI3- DI4- DI5- DI6- DI7- DI8-

+ _

Door open

FUCP alarm

TEC alarm TEC

Battery Stolen 1 alarm

Battery Stolen 2 alarm

1 2

3

4 6

5 1

2 3

4 6

5 1

2 3

4 6

5 1

2 3

4 6

5

NC COM NC COM NC COM NC COM NC COM NC COM NC COM NC COM

Relay-1 Relay-2

Relay- Relay-

Relay-5 Relay-6

Relay-7 Relay-8

Main Failure Over and Under Voltage

Rectifier Alarm LVD2 Disconnect

Door Open alarm Battery Stolen

Smoke Alarm High Temperature

(23)