Standard Of Procedure (SOP)
NCU M830B Settings
A. Koneksi Notebook ke Controller (NCU M830B)
A.1 Web browser yang di gunakan :
● Internet Explorer
● Firefox
● Google Chrome
● Safari
A.2 NCU M830B (Controller)
● IP default 192.168.100.100, Subnet Mask : 255.255.255.0 A.3 Setting Notebook
● Setting ip 192.168.100.103
● Disable proxy
● Kabel Ethernet (straight)
A.4 Koneksi dan login ke Controller NCU M830B
● User : admin
● Password : 640275 (default)
Tampilan NCU M830B
B. Parameter Settings
B.1 Site Settings
o Settings Quick Settings Site Settings
▪ Isi Site Name pada “Set Value” : JKT234, lalu click “Set” (contoh)
▪ Isi Site location pada “Set Value” : Jaksel, lalu click “Set” (contoh)
▪ Isi System Name pada “Set Value” : 3M2B, lalu click “Set” (contoh)
B.2 Time Settings
o Settings Quick Settings Time Settings
▪ Click “ Get Local Time from Connected PC” Click “Set”
Catatan : Pastikan time pada controller sesuai dengan waktu di PC
B.3 Setting input low voltage alarm
o Settings System AC Equipment
▪ Main failure Alarm Limit 1 : isi pada “Set Value” : 9 lalu click “Set”
▪ Main failure Alarm Limit 2 : isi pada “Set Value” : 9 lalu click “Set”
B.3 Settings Battery Charge
o Settings Battery Charge
▪ Float Charge Voltage : isi pada “set value” : 54 lalu click “Set”
▪ Equalize Charge Voltage : isi pada “set value” : 56.5 lalu click “Set”
▪ Battery Current Limit : isi pada “set value” : 0.1 lalu click “Set”
▪ Temp Comp Coeffecient (Slope): isi pada “set value” : 72 lalu click “Set”
▪ Comp Temp High 1 : isi pada “set value” : 45 lalu click “Set”
▪ Comp Temp High 2 : isi pada “set value” : 45 lalu click “Set”
▪ Over Voltage 1 alarm : isi pada “set value” : 57 lalu click “Set”
▪ Over Voltage 2 alarm : isi pada “set value” : 58 lalu click “Set”
▪ Under Voltage 1 Alarm : isi pada “set value” : 48 lalu click “Set”
▪ Under Voltage 2 Alarm : isi pada “set value” : 48 lalu click “Set”
▪ Batt1 Rated Capacity : isi pada “set value” : 300 lalu click “Set”
⮚ (di sesuaikan dengan kapasitas battery yang di install)
⮚ Lakukan “Reset Battery Capacity” setiap dilakukan perubahan
▪ Batt1 Shunt Current : isi pada “set value” : 300 lalu click “Set”
▪ Batt1 Shunt Voltage : isi pada “set value” : 25 lalu click “Set”
B.4 Settings LVD (Low Voltage Disconnect) o Settings LVD
▪ LVD1 (LLVD) :
⮚ LVD 1 : pada set value “Enable” lalu click “Set”
⮚ LVD 1 Mode : pada set value “Voltage” lalu click “Set”
⮚ LVD 1 Voltage : pada set value “45” lalu click “Set”
▪ LVD2 (BLVD) :
⮚ LVD 2 : pada set value “Enable” lalu click “Set”
⮚ LVD 2 Mode : pada set value “Voltage” lalu click “Set”
⮚ LVD 2 Voltage : pada set value “43.2” lalu click “Set”
⮚ LVD Contactor Type : pada set value “Mono Stable” lalu click “Set”
B.5 Alarm Relay (Digital output) B.5.1 Main failure Alarm
o Advanced Settings Alarm Please select Equipment type : Rectifier AC
▪ Pilih index 25. Main failure, click “Modify” lalu isi “ relay number” : 1, click “Set”
B.5.2 Over Voltage dan Under Voltage Alarm
o Advanced Settings Alarm Please select Equipment type : Power System
▪ Pilih index 32. Over Voltage 1, click “Modify”, lalu isi “relay number”:
2, click “Set”
▪ Pilih index 33. Over Voltage 2, click “Modifiy” lalu isi “ relay number” : 2, click “Set”
▪ Pilih index 34. Under Voltage 1, click “Modify” lalu isi “ relay number”:
2, click “Set”
▪ Pilih index 35. Under Voltage 2, Click “Modify” lalu isi “ relay number”
2, click “Set”
B.5.3 Rectifier Alarm
o Advanced Settings Alarm Please select Equipment type : Rectifier Group
▪ Pilih index 3. ECO Active, Click “Modify” lalu isi “relay number” : 3, click “Set”
▪ Pilih index 4. All rectifier Comm fail, click “Modify” lalu isi “relay number” : 3, click “Set”
▪ Pilih index 5. ECO Cycle Alarm, click “Modify” lalu isi “relay number” : 3, click “Set”
o Advanced Settings Alarm Please select Equipment type : Rectifier
▪ Pilih index 1, AC Input Fail lalu click “Modify” isi “relay number” : 3, click set.
▪ Ulangi langkah di atas untuk index 2 – 12.
B.5.4 LVD2 Disconnect Alarm
o Advanced Settings Alarms Please select equipment type : LVD Unit Pilih index 2. LVD 2 Disconnect, lalu click “Modify” isi “relay number” : 4, click “Set”
B.5.5 Door Open Alarm
o Advanced Settings DI Alarm
▪ Pilih index 2. Door Open Alarm, lalu click “Modify” isi “relay number” : 5, click set
B.5.6 Battery Stolen Alarm
o Advanced Settings DI Alarm
▪ Pilih index 6, lalu click “Modify” isi “Signal Alarm” : Battery Stolen 1 Alarm, isi “alarm relay” : 6, click “Set”
▪ Pilih index 7, lalu click “Modify” isi “Signal Alarm” : Battery Stolen 2 Alarm, isi “alarm relay” : 6, click “Set”
o Settings System
▪ Pilih DI6 Alarm state, tick “ low” lalu click “Set”
▪ Pilih DI7 Alarm state, tick “ low” lalu click “Set”
o Advanced Settings Alarm Please select equipment type : EIB
▪ Pilih index 2, bad battery block, click “Modify” isi “relay number” : None, isi “alarm level” : None
B.5.7 Smoke Alarm
o Advanced Settings DI Alarm
▪ Pilih index 5. Click “Modify” lalu isi “Signal Name” : Smoke Alarm, isi
“Alarm relay” : 7, click “Set”
B.5.8 High Temp Alarm
o Advanced Settings Alarm Please select equipment type : power system
▪ Pilih index 69. System Temp1 High 1, Click “Modify” isi “relay number” : 8, click “Set”
o Advanced Settings Alarm Please select equipment type : Battery Group
▪ Pilih index 18. Comp Temp High1, Click “Modify” isi “relay number” : 8, click “Set”
▪ Pilih index 19. Comp Temp High2, Click “Modify” isi “relay number” : 8, click “Set”
C. Reboot Controller
o Advanced Settings SW Maintenance Reboot Controller
D. EIB 1 dan IB 1 Board
Extended Interface Board (EIB 1) Interface Board ( IB 1) Extended Interface Board (EIB)
DO1 DO2 DO3 DO4 DO5
S h u n t - 1 -
S h u n t - 1 +
S h u n t - 2 -
S h u n t - 2 +
S h u n t - 3 -
S h u n t - 3 +
D C V - 1
D C V - 2
D C V - 3
D C V - 4
D C V - 5
D C V - 6
D C V - 7
D C V - 8
N A
N C
C O M
N O
N C
C O M
N O
N C
C O M
N O
N C
C O M
N O
N C
C O M
N O
1 2 3 4 5 6 1 2 3 4 5 6 1 3 5 2 4 6 1 3 5 2 4 6 1 3 5 2 4 6
DI DO
J6 1 J6 2
1 3 5 2 4 6
J5 J6 J7 J8 J9
1 3 5 1 3 5 1 3 5 1 3 5 2 4 6 2 4 6 2 4 6 2 4 6
Bank-1 Bank-2
J5 J6 J7 J8 J8
Interface Board (IB1) o Digital Input (DI)
o Digital Output (DO)
+ + + + + + + + _ _ _ _ _ _ _ _
DI1+ DI2+ DI3+ DI4+ DI5+ DI6+ DI7+ DI8+
DI1- DI2- DI3- DI4- DI5- DI6- DI7- DI8-
+ _
Door open
FUCP alarm
TEC alarm TEC
Battery Stolen 1 alarm
Battery Stolen 2 alarm
1 2
3
4 6
5 1
2 3
4 6
5 1
2 3
4 6
5 1
2 3
4 6
5
NC COM NC COM NC COM NC COM NC COM NC COM NC COM NC COM
Relay-1 Relay-2
Relay- Relay-
Relay-5 Relay-6
Relay-7 Relay-8
Main Failure Over and Under Voltage
Rectifier Alarm LVD2 Disconnect
Door Open alarm Battery Stolen
Smoke Alarm High Temperature