On Bond-slip of EB-FRP/Concrete Interface in Shear Under Fatigue Loading: Review and Synthesis of Experimental Studies and Models
Abbas Fathi, Georges El-Saikaly*, Omar Chaallal
Dept. of Construction Engineering, École de Technologie Supérieure (ÉTS), University of Quebec, Montreal (QC), H3C 1K3, Canada
E-mail: [email protected]; [email protected] (Corresponding author);
Received: 16 June 2021; Accepted: 29 September 2021; Available online: 20 November 2021
Abstract: Reinforced concrete (RC) structures subjected to cyclic fatigue loading are prone to progressive damage. Among the types of structural damage, those leading to shear deficiencies can result in sudden rupture of structures without warning. Hence, RC structures deficient in shear urgently need retrofitting. The use of externally bonded (EB) fiber-reinforced polymer (FRP) composites presents many advantages and is a very promising technology for shear strengthening of RC structures. This paper encompasses a wide range of research findings related to the interaction between concrete and FRP under fatigue loading. The behavior of the bond between FRP and concrete plays a major role in the failure mode of FRP shear-strengthened structures especially under fatigue.
Therefore, it is of interest to characterize the FRP/concrete interaction using appropriate models with respect to the influencing parameters. The paper will first discuss existing design guidelines and considerations related to the fatigue behavior of RC structures. A thorough review of available literature on EB-FRP/concrete bond in shear under cyclic fatigue loading will then be presented, with a focus on proposed bond-slip models and finite element studies of the FRP/concrete interface under fatigue loading.
Keywords: Fatigue loading; Bond-slip models; Shear; Reinforced concrete structures; Fiber-reinforced polymer (FRP); FRP/concrete interface; Finite element analysis (FEA).
1. Introduction
Many reinforced concrete (RC) structures such as bridge girders are expected to resist high numbers of cycles of fatigue loading, mainly due to traffic loads, during their life span. Many existing bridge structures in Canada and worldwide were designed according to old design codes in which the design loads did not consider the increased service loads caused by higher present-day traffic volume [1, 2]. Indeed, out of over 8,000 bridges reported on by the Canadian National Highway System, 60% are more than 30 years old, about 4% are rated as being in poor condition, and 80% need some sort of retrofitting [3]. In the United States, reports also show that out of 615,002 bridges, about 9% are classified as structurally deficient [4]. A large proportion of RC bridge structures show considerable signs of damage due to concrete deterioration, corrosion of steel reinforcement, and lack of sufficient load-carrying capacity according to current design guidelines [1]. Therefore, rehabilitation of such structures to withstand cyclic fatigue loads has always been a major concern for engineers. Shear failure, which is a common failure mode that can be caused by fatigue loading, often occurs suddenly and without warning.
This mode of failure is characterized by diagonal tension cracks that are mainly due to the combined effects of flexural (bending) and shearing action. The use of externally bonded (EB) fiber-reinforced polymer (FRP) composites to strengthen deficient RC beams is widely accepted. EB-FRP composites present many advantages such as high strength-to-weight ratio, corrosion resistance, fatigue resistance, light weight, and ease of application [5-7].
The fatigue life (fatigue strength) of an EB-FRP strengthened RC structure is defined as the number of load cycles leading up to the structural failure. Indeed, the stress level in the steel reinforcement is known as the main component that determines the fatigue life of RC structures EB-FRP strengthened, particularly in flexure.
Therefore, the fatigue life of a structure is generally represented by an S-N curve, which is in terms of stress versus the logarithm of the number of load cycles. Experimental investigations have revealed that the fatigue life of FRP strengthened RC structures depend on their failure modes. The most common failure modes that have been observed in EB-FRP shear-strengthened RC structures under fatigue loading include crushing of concrete struts, debonding of FRP from concrete, yielding and fracture of longitudinal tensile steel bars, and steel stirrup rupture [1, 8]. However, it is widely accepted that the fatigue life of FRP strengthened RC beams in flexure is typically
governed by the fatigue strength of the internal steel reinforcement. Indeed, it is reported that fracture of the steel reinforcement is the dominant failure mode in such structures [7]. As far as the fatigue strength of steel goes, a downward trend appears in the S-N curve until a stress level, known as the endurance limit, beyond which the curve progresses horizontally along the N-axis. Therefore, steel tends to resist an indefinite number of load cycles at its endurance limit. For concrete, however, the curve seems to drop to its fatigue strength, as shown in Fig. 1 [7]. More specifically, no endurance limit has been observed in the fatigue life of concrete under ten million cycles of fatigue load, but its fatigue strength in compression, tension, or flexure under the same number of load cycles has been found to be approximately 55% of its static strength. This level of residual strength is in fact the ultimate load reached by the specimens under quasi-static loading condition after they experienced 10 million cycles [9].
As for the fatigue performance of FRP composites, carbon FRP (CFRP) has been found to have the longest fatigue life among FRP materials [10]. Moreover, a typical CFRP composite can exhibit an endurance limit of 60% to 70% of its initial static ultimate strength [11].
Fig. 1. Schematic S-N curves of concrete and steel
Through extensive research investigations on the fatigue behavior of RC beams strengthened in flexure with EB-FRP, researchers have developed numerous S-N models to determine the fatigue failure of internal longitudinal tensile reinforcement, which has been known to be the governing factor in the fatigue life of EB-FRP strengthened RC beams in flexure [12-17].
Considering the performance of an EB-FRP shear-strengthened RC beam under fatigue loading, the FRP/concrete bond behavior can have a significant effect on the fatigue strength of the structure because premature debonding at the interface prevents the EB-FRP from attaining its full capacity. Hence, it is of great interest to evaluate the fatigue life of RC structures strengthened in shear with EB-FRP in terms of the behavior of the FRP/concrete bond and to investigate the influencing parameters affecting the interlaminar interaction between FRP and concrete.
Despite considerable research on shear strengthening of RC beams using EB-FRP systems under monotonic loading, the fatigue behavior of EB-FRP shear-strengthened RC structures has not been fully documented. Kim and Heffernan [5] presented the state of the art on the fatigue performance of FRP-strengthened RC structures in flexure. Various fatigue-related parameters were investigated, including applied load range, FRP bond behavior, crack propagation, environmental effects, and failure modes. Another state-of-the-art review was published by Oudah and El-Hacha [7], in which a parametric study was carried out on the fatigue behavior of RC structures strengthened in flexure with FRP composites. Furthermore, a few other literature reviews have been published on the fatigue behavior of FRP-strengthened RC beams [10, 18, 19]. It is noteworthy that these studies focused on the flexural performance of RC structures strengthened with EB-FRP under cyclic fatigue loading. In contrast, investigations related to shear behavior were not considered in previous literature reviews.
Prior investigations on the fatigue behavior of concrete/FRP bond have demonstrated the reliance of the resistance of FRP strengthened concrete structures on the bond failure mechanism, thereby making it necessary to determine the bond-slip model of concrete/FRP interface in such structures [20, 21]. An accurate bond-slip model needs to take into account all the influencing parameters including concrete strength, FRP bonded length, FRP-to- concrete width ratio, and fatigue loading amplitude. A review of related literature shows that a bond-slip model with the ability to consider all the aforementioned factors under fatigue conditions has yet to be developed. The aim of this paper is to introduce all the proposed models related to the bond behavior at FRP/concrete interface
and identify the pros and cons of each of them. Furthermore, the application of bond-slip models in finite element modeling (FEM) of FRP/concrete interface is evaluated through reported numerical studies. Based on the existing gaps identified herein, further investigations could be conducted on the FRP/concrete bond behavior under fatigue loading.
The state of our knowledge is presented in the following sections to shed light on the fatigue behavior of EB- FRP shear-strengthened RC structures by examining bond behavior. To that end, this paper is organized into several sections covering a wide range of aspects, which include: i) a review of existing design codes related to the fatigue life of concrete as well as FRP composites; ii) research findings regarding the fatigue behavior of the bond at the FRP/concrete interface; and iii) a review of finite-element simulations of the FRP/concrete bond under fatigue loading. Finally, the gaps and shortcomings in the available published research are identified, along with recommendations for further investigation.
2. Design code provisions
The fatigue stress limits of concrete and FRP materials are specified in many design code provisions. The stress in FRP should not exceed the maximum applied stress, including sustained and cyclic loading. For example, the maximum stress specified by ACI-440.2R [11] is equal to 20%, 30%, and 55% of ultimate FRP strength for glass FRP (GFRP), aramid FRP (AFRP), and CFRP, respectively, whereas these stress limits are 25%, 35%, and 65%
according to CSA-S6 [22].
For RC structures under flexural fatigue loading, ACI-215R [9] limits the stress range of concrete to 40% of its compressive strength, whereas according to ACI-440.2R [11], the compressive stress in concrete should be limited to 60% of its strength for RC structures strengthened with EB-FRP under cyclic service load.
On the basis of experimental observations, an EB-FRP strengthened RC member is exposed to fatigue damage when the cyclic load range is over 60% of its monotonic yield capacity [23]. Furthermore, in EB-FRP strengthened RC structures, the bond strength at the FRP/concrete interface is greatly affected by the tensile strength of the concrete substrate. The concrete substrate is the weakest link in the FRP/concrete interface, and its tensile strength and soundness govern the effectiveness of externally bonded FRP systems [11]. Therefore, it is recommended that the minimum required tensile strength of concrete in EB-FRP applications be greater than 1.5 MPa [11, 22, 23].
3. Fatigue behavior of FRP/concrete interface under cyclic loading
The FRP/concrete interface plays a major role in the shear performance of EB-FRP strengthened RC structures under fatigue loading. The FRP/concrete bond can be affected by numerous parameters including concrete strength, FRP bonded length, FRP-to-concrete width ratio and fatigue loading amplitude. An investigation by Ko and Sato [24] on the bond behavior of different FRP materials including carbon, aramid, and polyacetal revealed that concrete specimens bonded with carbon FRP (CFRP) materials featured superior performance in terms of load-carrying capacity and initial stiffness compared to those strengthened with aramid and polyacetal FRPs.
Increasing FRP stiffness by using multiple layers was also reported to increase the maximum bond strength [24].
In addition, the FRP/concrete bond is likely to undergo fatigue failure when the adhesive is exposed to temperatures higher than its glass transition temperature or as a result of freezing and thawing [10]. Furthermore, exposure to a hygrothermal environment (high temperature and moisture) can shorten the fatigue life of the CFRP- concrete interface and result in aggressive decay of the bond behavior [25]. Since the fatigue failure mode of RC structures shear-strengthened with EB-FRP depends on the FRP/concrete interaction, research has been carried out to develop bond-slip models for the FRP/concrete interface under cyclic loading considering various influencing factors such as concrete strength, FRP-to-concrete width ratio, fatigue loading amplitude, and bond length. Table 1 presents details of experimental investigations that were conducted to evaluate the behavior of bond between EB-FRP and concrete under fatigue loading. In the following sections, the proposed bond-slip models as well as the fatigue life models of FRP-to-concrete interface are presented. In addition, the influencing parameters of the bond between EB-FRP and concrete in fatigue loading conditions are thoroughly discussed.
3.1 Bond-slip models of FRP/concrete interface
A number of bond-slip models have been proposed to characterize the interfacial behavior of FRP/concrete bond under static loading. Table 2 lists the proposed local bond slip models under static loading reported in the literature. Fig. 2 shows the developed bond-slip curves for an FRP bonded concrete specimen under static loading with the following properties: 𝑓𝑓𝑐𝑐′= 30 MPa, 𝑓𝑓𝑡𝑡= 2.9 MPa, 𝑏𝑏𝑓𝑓= 75 mm, 𝑏𝑏𝑐𝑐=150 mm, 𝑡𝑡𝑓𝑓= 0.13 mm, 𝐸𝐸𝑓𝑓= 230 GPa, 𝐸𝐸𝑐𝑐= 32.5 GPa. The aforementioned symbols are defined in Table 2.
Table 1. Details of experimental investigations on the fatigue behavior of FRP/concrete bond along with the investigated parameters.
Authors
Number of specimens
Test specifications Fatigue loading condition Influencing parameters
Pull-out Test set-up
FRP system
Maximum number of load cycles Frequency (Hz) Lower bound load (Fmin) Upper bound load (Fmax ) Concrete strength FRP to concrete width ratio Loading amplitude Bond length FRP type FRP ratio Environmental condition
Bizindavyi et al. [26]
46 Single lap shear
FRP laminates
- 1 var var
Ko and Sato [24]
54 Double lap shear
CFRP sheets
- - - -
Diab et al.
[27]
17 Double lap shear
CFRP sheets
3 million 5 10% fu.b 30-80%
fu.b
Carloni et al.
[28]
7 Single lap shear
CFRP sheets
- 1 var var
Li et al. [29] 21 Four point bending
CFRP sheets
2 million 2.5 15% fu.b 45-80%
fu.b
Zheng et al.
[25]
17 Double lap shear
CFRP laminates
- 10 var var
Zhu et al. [30] 9 Four point bending
CFRP sheets
2.5 million 2.5 15% fu.b var Li et al. [31] 15 Four point
bending
CFRP sheets
- 2.5 15% fu.b var
Zhang [32] 15 Double lap shear
CFRP laminates
1 million
1 10% fu.b 50- 90% fu.b
Xie et al. [33] 26 Four point
bending
BFRP sheets
2 million
10 var var
* Note: f_(u.b)= Static bond capacity
Table 2. Available bond-slip models under static loading.
Authors Bond-slip models
Neubauer and Rostasy [34]
𝜏𝜏=�𝜏𝜏𝑚𝑚𝑚𝑚𝑚𝑚 �𝑠𝑠
𝑠𝑠0� 𝑠𝑠 ≤ 𝑠𝑠0 0 𝑠𝑠>𝑠𝑠0
𝜏𝜏𝑚𝑚𝑚𝑚𝑚𝑚 = 1.8 𝑘𝑘𝑏𝑏𝑓𝑓𝑡𝑡 , 𝑠𝑠0= 0.202 𝑘𝑘𝑏𝑏 , 𝛽𝛽𝑤𝑤=�1.25 × 1+𝑏𝑏2−𝑏𝑏𝑓𝑓/𝑏𝑏𝑐𝑐
𝑓𝑓/400
De Lorenzis et al. [35]
𝜏𝜏=𝐾𝐾𝑖𝑖𝑖𝑖𝑡𝑡×𝑠𝑠
𝐾𝐾𝑖𝑖𝑖𝑖𝑡𝑡=𝐺𝐺𝑖𝑖𝑖𝑖𝑡𝑡/𝑡𝑡𝑖𝑖𝑖𝑖𝑡𝑡 , 𝜏𝜏𝑚𝑚𝑚𝑚𝑚𝑚= 0.0182 (𝑛𝑛𝑓𝑓𝑡𝑡𝑓𝑓𝐸𝐸𝑓𝑓)0.5 , (𝑛𝑛𝑓𝑓𝑡𝑡𝑓𝑓𝐸𝐸𝑓𝑓 in MPa , mm)
Nakaba et al. [36] 𝜏𝜏=𝜏𝜏𝑚𝑚𝑚𝑚𝑚𝑚 �𝑠𝑠
𝑠𝑠0� �3/(2 + (𝑠𝑠 𝑠𝑠0)3)�
𝜏𝜏𝑚𝑚𝑚𝑚𝑚𝑚= 3.5 𝑓𝑓𝑐𝑐′0.19 , 𝑠𝑠0= 0.065
Monti et al. [37]
𝜏𝜏=�𝜏𝜏𝑚𝑚𝑚𝑚𝑚𝑚 �𝑠𝑠
𝑠𝑠0� 𝑠𝑠 ≤ 𝑠𝑠0
𝜏𝜏𝑚𝑚𝑚𝑚𝑚𝑚 �𝑠𝑠𝑢𝑢𝑢𝑢𝑡𝑡− 𝑠𝑠
𝑠𝑠𝑢𝑢𝑢𝑢𝑡𝑡− 𝑠𝑠0� 𝑠𝑠>𝑠𝑠0
𝜏𝜏𝑚𝑚𝑚𝑚𝑚𝑚= 1.8 𝑘𝑘𝑏𝑏𝑓𝑓𝑡𝑡 , 𝑠𝑠0= 2.5 𝜏𝜏𝑚𝑚𝑚𝑚𝑚𝑚 (𝑛𝑛𝑓𝑓𝑡𝑡𝑓𝑓/𝐸𝐸𝑓𝑓+ 50/𝐸𝐸𝑐𝑐) 𝑠𝑠𝑢𝑢𝑢𝑢𝑡𝑡= 0.33𝑘𝑘𝑏𝑏 , 𝛽𝛽𝑤𝑤=�1.5 × 1+𝑏𝑏2−𝑏𝑏𝑓𝑓/𝑏𝑏𝑐𝑐
𝑓𝑓/100
Savoia et al. [38] 𝜏𝜏=𝜏𝜏𝑚𝑚𝑚𝑚𝑚𝑚 �𝑠𝑠
𝑠𝑠0� �2.86/(1.86 + (𝑠𝑠 𝑠𝑠0)2.86)�
𝜏𝜏𝑚𝑚𝑚𝑚𝑚𝑚= 3.5 𝑓𝑓𝑐𝑐′0.19 , 𝑠𝑠0= 0.051
Lu et al. [20]
𝜏𝜏=
⎩⎪
⎨
⎪⎧ 𝜏𝜏𝑚𝑚𝑚𝑚𝑚𝑚 �𝑠𝑠
𝑠𝑠0� 𝑠𝑠 ≤ 𝑠𝑠0
𝜏𝜏𝑚𝑚𝑚𝑚𝑚𝑚 �𝑠𝑠𝑢𝑢𝑢𝑢𝑡𝑡− 𝑠𝑠
𝑠𝑠𝑢𝑢𝑢𝑢𝑡𝑡− 𝑠𝑠0� 𝑠𝑠0< 𝑠𝑠 ≤ 𝑠𝑠0
0 𝑠𝑠>𝑠𝑠𝑢𝑢𝑢𝑢𝑡𝑡
𝜏𝜏𝑚𝑚𝑚𝑚𝑚𝑚 = 1.5 𝑘𝑘𝑏𝑏𝑓𝑓𝑡𝑡 , 𝑠𝑠0= 0.0195 𝑘𝑘𝑏𝑏𝑓𝑓𝑡𝑡≤0.06
𝑠𝑠𝑢𝑢𝑢𝑢𝑡𝑡 = 2𝐺𝐺𝑓𝑓/𝜏𝜏𝑚𝑚𝑚𝑚𝑚𝑚 , 𝐺𝐺𝑓𝑓= 0.308 𝑘𝑘𝑏𝑏2�𝑓𝑓𝑡𝑡 , 𝛽𝛽𝑤𝑤=�2.25−𝑏𝑏1.25+𝑏𝑏𝑓𝑓/𝑏𝑏𝑐𝑐
𝑓𝑓/𝑏𝑏𝑐𝑐
Pellegrino et al. [39]
𝜏𝜏=�𝜏𝜏𝑚𝑚𝑚𝑚𝑚𝑚 �𝑠𝑠
𝑠𝑠0� 𝑠𝑠 ≤ 𝑠𝑠0 𝜏𝜏𝑚𝑚𝑚𝑚𝑚𝑚 �𝑠𝑠𝑢𝑢𝑢𝑢𝑡𝑡− 𝑠𝑠
𝑠𝑠𝑢𝑢𝑢𝑢𝑡𝑡− 𝑠𝑠0� 𝑠𝑠>𝑠𝑠0
𝜏𝜏𝑚𝑚𝑚𝑚𝑚𝑚= 3.1 (𝑛𝑛𝑓𝑓𝑡𝑡𝑓𝑓𝐸𝐸𝑓𝑓)0.32 , 𝑠𝑠0= 0.075 (𝑛𝑛⁄ 𝑓𝑓𝑡𝑡𝑓𝑓𝐸𝐸𝑓𝑓)0.2 𝑠𝑠𝑢𝑢𝑢𝑢𝑡𝑡= 10.5 (𝑛𝑛⁄ 𝑓𝑓𝑡𝑡𝑓𝑓𝐸𝐸𝑓𝑓)0.6 , (𝑛𝑛𝑓𝑓𝑡𝑡𝑓𝑓𝐸𝐸𝑓𝑓 in GPa , mm) Note:
𝜏𝜏𝑚𝑚𝑚𝑚𝑚𝑚: Maximum interfacial shear stress
𝑠𝑠0: Peak slip at which shear stress reaches maximum 𝑠𝑠𝑢𝑢𝑢𝑢𝑡𝑡: Ultimate slip value
𝑛𝑛𝑓𝑓𝑡𝑡𝑓𝑓𝐸𝐸𝑓𝑓: FRP stiffness 𝐸𝐸𝑐𝑐: Concrete elastic modulus
𝐾𝐾𝑖𝑖𝑖𝑖𝑡𝑡: Slip modulus of the interface , 𝐾𝐾𝑖𝑖𝑖𝑖𝑡𝑡= 1386 𝑘𝑘𝑠𝑠𝑘𝑘/
𝑘𝑘𝑛𝑛 (376 𝑀𝑀𝑀𝑀𝑀𝑀/𝑚𝑚𝑚𝑚)
𝑓𝑓𝑐𝑐′: Concrete cylinder compressive strength 𝑓𝑓𝑡𝑡: Concrete tensile strength
𝛽𝛽𝑤𝑤: Width ratio factor
𝑏𝑏𝑓𝑓/𝑏𝑏𝑐𝑐: FRP-to-concrete width ratio 𝐺𝐺𝑓𝑓: Fracture energy
𝐺𝐺𝑖𝑖𝑖𝑖𝑡𝑡: Interfacial shear modulus , 𝐺𝐺𝑖𝑖𝑖𝑖𝑡𝑡 = 74.86 𝑘𝑘𝑠𝑠𝑘𝑘 (515.8 𝑀𝑀𝑀𝑀𝑀𝑀)
𝑡𝑡𝑖𝑖𝑖𝑖𝑡𝑡: Interfacial thickness
Fig. 2. Existing bond-slip models under static loading
Ko and Sato [24] developed a bond stress-slip model under cyclic loading based on Popovics [40] that agreed well with their own experimental results of double shear pull-out tests on 54 specimens. Indeed, two cyclic loading conditions (Cyclic 1 and 2) were considered in their experiments. During both cyclic loading conditions, a limited number of unload/reload paths were set. For Cyclic 1, the unloading loads corresponded to the maximum monotonic load capacity as well as the maximum monotonic displacement, whereas for Cyclic 2 condition, unloading of specimens was performed according to the maximum slips reached at each strain gauge location. Fig.
3 depicts the bond-stress curve of a tested specimen based on the envelopes derived from the cyclic hysteresis of the interfacial stress-slip relation. The proposed model, expressed in Eq. (1) and Eq. (2), involved several empirical
parameters, including the maximum bond stress, 𝜏𝜏𝑚𝑚𝑚𝑚𝑚𝑚 , the corresponding slip, 𝑠𝑠0, the curve characteristic constants, 𝑐𝑐, 𝑐𝑐2, 𝑐𝑐3, the unloading stiffness, 𝐾𝐾𝑢𝑢𝑖𝑖, the ultimate slip, 𝑠𝑠𝑢𝑢𝑢𝑢𝑡𝑡, the friction stress, 𝜏𝜏𝑓𝑓𝑓𝑓, the negative friction stress, 𝜏𝜏𝑓𝑓𝑖𝑖 and the unloading slip 𝑠𝑠𝑢𝑢𝑖𝑖:
𝜏𝜏= 𝜏𝜏𝑚𝑚𝑚𝑚𝑚𝑚
× 𝑐𝑐×𝑠𝑠 𝑠𝑠0
�(𝑐𝑐+1)+�𝑠𝑠0𝑠𝑠�𝑚𝑚� (1)
𝐾𝐾𝑢𝑢𝑖𝑖=𝑐𝑐2×𝑠𝑠𝑢𝑢𝑖𝑖𝑐𝑐3 (2)
Where, 𝜏𝜏 and 𝑠𝑠 are the bond stress and slip of the FRP/concrete interface, respectively. Also, the constant values of 𝑐𝑐, 𝑐𝑐2, 𝑐𝑐3, and 𝑀𝑀 can be found from the experimental data in Ko and Sato [24]. Despite the fact that the results predicted by the model and the experimental data showed a good agreement, the proposed model was nevertheless developed on the basis of a limited number of loading/unloading repetitions. In addition, a linear approximation was adopted for the unload/reload path in the model for simplicity, which is inconsistent with the actual oval- shaped curves featured in the experiments [24].
Fig. 3. Envelope-base bond-slip curve of a specimen tested by Ko and Sato [24] under cyclic loading The following cyclic bilinear bond-slip model, as stated in Eqs. (3)–(7) and illustrated in Fig. 4, was proposed by Diab et al. [27] to characterize the fatigue behavior of the CFRP/concrete interface :
𝜏𝜏=�
𝜏𝜏𝑚𝑚𝑚𝑚𝑚𝑚.𝑡𝑡
𝑠𝑠0 𝑠𝑠 0≤ 𝑠𝑠 ≤ 𝑠𝑠0
𝜏𝜏𝑚𝑚𝑚𝑚𝑚𝑚.𝑡𝑡
𝑠𝑠𝑢𝑢𝑢𝑢𝑡𝑡.𝑡𝑡−𝑠𝑠0(𝑠𝑠𝑢𝑢𝑢𝑢𝑡𝑡.𝑡𝑡− 𝑠𝑠) 𝑠𝑠0<𝑠𝑠 ≤ 𝑠𝑠𝑢𝑢𝑢𝑢𝑡𝑡.𝑡𝑡
(3)
𝜏𝜏𝑚𝑚𝑚𝑚𝑚𝑚.𝑡𝑡=𝜏𝜏1+𝜑𝜑∙𝛼𝛼𝑚𝑚𝑚𝑚𝑚𝑚.0 (4)
𝑠𝑠𝑢𝑢𝑢𝑢𝑡𝑡.𝑡𝑡=𝜏𝜏𝑚𝑚𝑚𝑚𝑚𝑚.0𝜏𝜏 ×𝑠𝑠0
𝑚𝑚𝑚𝑚𝑚𝑚.𝑡𝑡 (5)
𝐾𝐾𝑏𝑏𝑡𝑡=1+𝜑𝜑∙𝛼𝛼𝐾𝐾𝑏𝑏0 (6)
𝜑𝜑=�0.046(𝑡𝑡)0.4 𝑡𝑡 ≤2000
1.2(1−exp (−𝑡𝑡/1200) 𝑡𝑡> 2000 (7)
Where, 𝑡𝑡 is the cyclic loading time (in seconds), 𝜏𝜏𝑚𝑚𝑚𝑚𝑚𝑚.0 and 𝜏𝜏𝑚𝑚𝑚𝑚𝑚𝑚.𝑡𝑡 are the cyclic bond strengths of the adhesive at time zero and time 𝑡𝑡, respectively, 𝐾𝐾𝑏𝑏0 and 𝐾𝐾𝑏𝑏𝑡𝑡 are the cyclic stiffness values of the bond at time zero and time 𝑡𝑡, respectively, 𝑠𝑠𝑢𝑢𝑢𝑢𝑡𝑡.𝑡𝑡 is the cyclic ultimate slip (at time 𝑡𝑡), 𝜑𝜑 is the creep fatigue coefficient, and 𝛼𝛼 is a frequency- dependent factor that is equal to 1 for a frequency of 5 Hz. As can be seen, the cyclic dependent bilinear model successfully takes into account the degradation of interfacial stiffness under fatigue loading by adopting a simple creep-fatigue coefficient (𝜑𝜑) in the equations. It should be noted that the model presented above was developed for the case of simple shear pull-out test. However, it has been argued that in actual debonding phenomenon, failure occurs due to the combined effects of shear and normal stresses near the cut-off points of bonded FRP [10].
Fig. 4. Cyclic bilinear bond-slip model proposed by Diab et al. [27]
By examining the interfacial behavior of concrete and FRP in EB-FRP flexural strengthened RC beams under cyclic loading, Loo et al. [41] proposed a bond-slip model for concrete/FRP interaction. The proposed model, illustrated in Fig. 5, can be expressed by the following equations:
𝑠𝑠𝑏𝑏.𝑚𝑚𝑚𝑚𝑚𝑚=𝜏𝜏𝑏𝑏.𝑚𝑚𝑚𝑚𝑚𝑚𝐸𝐸
𝑏𝑏0 [1 +𝐾𝐾𝑚𝑚×𝑀𝑀(log𝑛𝑛)𝑏𝑏× (𝜏𝜏𝛥𝛥𝜏𝜏𝑏𝑏
𝑏𝑏.𝑢𝑢𝑢𝑢𝑡𝑡)ℎ] (8)
𝐸𝐸𝑏𝑏 =𝐸𝐸𝑏𝑏0[1 +𝐾𝐾2×𝜇𝜇(log𝑛𝑛)𝛽𝛽×�𝜏𝜏𝛥𝛥𝜏𝜏𝑏𝑏
𝑏𝑏.𝑢𝑢𝑢𝑢𝑡𝑡)𝜆𝜆� (9)
Where, 𝑠𝑠𝑏𝑏.𝑚𝑚𝑚𝑚𝑚𝑚 is the slip (in mm) corresponding to the maximum applied average bond stress (𝜏𝜏𝑏𝑏.𝑚𝑚𝑚𝑚𝑚𝑚), 𝛥𝛥𝜏𝜏𝑏𝑏 is the difference between the average bond stress at maximum cyclic load and the average stress at minimum load cycle, 𝜏𝜏𝑏𝑏.𝑢𝑢𝑢𝑢𝑡𝑡 is the average bond stress at the maximum load cycle, 𝑁𝑁𝑏𝑏, leading to bond failure (in N/mm2), 𝑛𝑛 is the number of load cycles, 𝐸𝐸𝑏𝑏 and 𝐸𝐸𝑏𝑏0 are the moduli of elasticity of the bond (in N/mm2) at cycle 𝑛𝑛 and at the first loading cycle, respectively, and 𝐾𝐾𝑚𝑚=𝐾𝐾1log (𝑛𝑛) and 𝐾𝐾2 are factors defining the relationship between average bond stress and bonding length. By validating these equations with the limited literature data, the following parameters were determined: = 1.068 , 𝑏𝑏= 1.402, ℎ= 2.612, 𝜇𝜇=−190.3, 𝛽𝛽= 0.990 and 𝜆𝜆= 8.797. Based on numerical results, the proposed FE model showed good agreement with experimental results in terms of beam displacements at maximum loads, CFRP strains, and the number of load cycles to failure.
Fig. 5. Constitutive bond-slip model of Concrete/FRP interface under fatigue loading by Loo et al. [41]
Based on a regression analysis with limited experimental data, another bond stress-slip relationship was proposed by considering the effects of concrete strength and load amplitude under fatigue loading [30], as follows:
𝜏𝜏𝑚𝑚𝑚𝑚𝑚𝑚 =𝛾𝛾𝛽𝛽𝑤𝑤(1.085−0.648𝑇𝑇)(0.2233𝑓𝑓𝑐𝑐𝑢𝑢−2.1433)𝑒𝑒(38.46−112𝑇𝑇)𝑁𝑁𝑛𝑛 (10)
Where, 𝜏𝜏𝑚𝑚𝑚𝑚𝑚𝑚 is the maximum shear stress of the CFRP/concrete interface, 𝑓𝑓𝑐𝑐𝑢𝑢 is the concrete cubic compressive strength, and n and N are the number of fatigue loading cycles and the fatigue life of specimens, respectively. 𝑇𝑇 is
the ratio of the applied fatigue loading amplitude , 𝑀𝑀𝑚𝑚𝑚𝑚𝑚𝑚− 𝑀𝑀𝑚𝑚𝑖𝑖𝑖𝑖, to the monotonic capacity, 𝑀𝑀𝑢𝑢, (𝑃𝑃𝑚𝑚𝑚𝑚𝑚𝑚−𝑃𝑃𝑚𝑚𝑚𝑚𝑛𝑛
𝑃𝑃𝑢𝑢 ) for each specimen, 𝛽𝛽𝑤𝑤 is the coefficient related to the ratio of the CFRP and concrete specimen’s widths, 𝑏𝑏𝑓𝑓/𝑏𝑏𝑐𝑐, and the coefficient γ can be expressed as:
𝛽𝛽𝑤𝑤=�2.25−𝑏𝑏1.25+𝑏𝑏𝑓𝑓/𝑏𝑏𝑐𝑐
𝑓𝑓/𝑏𝑏𝑐𝑐 ; 𝛾𝛾= 0.005𝑓𝑓𝑐𝑐𝑢𝑢+ 0.7≤1 (11) The proposed nonlinear bond-slip relationship successfully took into consideration the effect of fatigue degradation on the FRP/concrete bond behavior due to cyclic loading when calculating the maximum bond shear stress. However, in their experimental data analysis based on which the above-mentioned bond-slip model was developed, the effect of CFRP-to-concrete width ratio was not considered as a variable despite its demonstrated influence on the bond property of FRP/concrete interface as evidenced by reported experimental studies [31].
Also, an analytical study along with an experimental investigation by Li et al. [31] led to a bond-slip model for the concrete/FRP interface under cyclic loading, as expressed in Eqs. (12) – (20):
𝜏𝜏=�
𝜏𝜏𝑚𝑚𝑚𝑚𝑚𝑚.𝑡𝑡
𝑠𝑠0 𝑠𝑠 0≤ 𝑠𝑠 ≤ 𝑠𝑠0
𝜏𝜏𝑚𝑚𝑚𝑚𝑚𝑚.𝑡𝑡
𝑠𝑠𝑢𝑢𝑢𝑢𝑡𝑡.𝑡𝑡−𝑠𝑠0(𝑠𝑠𝑢𝑢𝑢𝑢𝑡𝑡.𝑡𝑡− 𝑠𝑠) 𝑠𝑠0<𝑠𝑠 ≤ 𝑠𝑠𝑢𝑢𝑢𝑢𝑡𝑡.𝑡𝑡
𝜏𝜏= 0 𝑠𝑠>𝑠𝑠𝑢𝑢𝑢𝑢𝑡𝑡.𝑡𝑡
(12)
𝑠𝑠𝑢𝑢𝑢𝑢𝑡𝑡.𝑡𝑡= 𝜏𝜏2𝐺𝐺𝑓𝑓
𝑚𝑚𝑚𝑚𝑚𝑚.𝑡𝑡 (13)
𝐺𝐺𝑓𝑓= 𝛽𝛽𝑤𝑤2(0.029𝑓𝑓𝑐𝑐𝑢𝑢−0.2668) (14)
𝜏𝜏𝑚𝑚𝑚𝑚𝑚𝑚.𝑡𝑡=𝐾𝐾𝑡𝑡 𝑠𝑠0 (15)
𝐾𝐾𝑡𝑡=1+𝑐𝑐𝐾𝐾0
𝑘𝑘×𝑖𝑖𝑏𝑏𝑘𝑘 (16)
𝑐𝑐𝑘𝑘= 0.0007 ×𝑒𝑒2.919×𝑆𝑆𝑐𝑐2 (17)
𝑏𝑏𝑘𝑘= (0.873 ×𝑆𝑆𝑐𝑐+ 0.0198)(1.208−0.00337 ×𝑓𝑓𝑐𝑐𝑢𝑢)(0.619 ×𝑏𝑏𝑏𝑏𝑓𝑓
𝑐𝑐+ 0.838) (18)
𝑆𝑆𝑐𝑐 =1−𝑆𝑆𝑇𝑇
𝑚𝑚 (19)
𝑆𝑆𝑚𝑚=𝑃𝑃𝑚𝑚𝑚𝑚𝑚𝑚2𝑃𝑃+𝑃𝑃𝑚𝑚𝑚𝑚𝑛𝑛
𝑢𝑢 (20)
Where, 𝑠𝑠0 and 𝑠𝑠𝑢𝑢𝑢𝑢𝑡𝑡.𝑡𝑡 are the slip corresponding to the maximum shear stress (𝜏𝜏𝑚𝑚𝑚𝑚𝑚𝑚.𝑡𝑡) and the ultimate slip within the load cycles, respectively, 𝐾𝐾0 and 𝐾𝐾𝑡𝑡 are the slopes of the ascending segment of the bond-slip curve at the initial load cycle and cycle n, respectively, 𝐺𝐺𝑓𝑓 is the interfacial fracture energy, 𝑐𝑐𝑘𝑘 , 𝑏𝑏𝑘𝑘 are coeffcients obtained from the test results. 𝑆𝑆𝑐𝑐 is the cyclic load level, which is a function of the applied loading amplitude-to-ultimate load capacity ratio (𝑇𝑇) and the average cyclic loading-to-ultimate load capacity ratio (𝑆𝑆𝑚𝑚). It has been reported that the local slip at the maximum interfacial shear stress (𝑠𝑠0) remains constant during the load cycles. However, the maximum cyclic shear stress (𝜏𝜏𝑚𝑚𝑚𝑚𝑚𝑚.𝑡𝑡) and the maximum cyclic slip (𝑠𝑠𝑢𝑢𝑢𝑢𝑡𝑡.𝑡𝑡) are both dependent on the number of load cycles, thereby keeping the interfacial fracture energy (𝐺𝐺𝑓𝑓) unchanged during cyclic loading. During the experimental testing, the performance of a series of specimens within four groups (A, B, C and D) was observed.
The effects of loading amplitude and concrete strength were taken into consideration in group A and B, whereas in groups C and D, the bond length and FRP-to-concrete width ratio (𝑏𝑏𝑓𝑓/𝑏𝑏𝑐𝑐) were chosen as the variables. Fig. 6 shows the bond-slip curves of a specimen (from group D) with respect to different number of load cycles, n, (0, 420, 2500 and 6500) obtained from the proposed model. It can be understood from the cyclic bond-slip curve that the slope of the ascending segment decreases as the number of cycles increases without causing a noticeable change in the amount of slip corresponding to the maximum bond shear stress (𝑠𝑠0). The bond-slip curves derived from the two models developed by Zhu et al. [30] and Li et al. [31] are illustrated in Fig. 7 and Fig. 8 under different number of load cycles for specimens selected from group B and group C, with the following properties: 𝑓𝑓𝑐𝑐𝑢𝑢= 35.3 MPa, 𝑏𝑏𝑓𝑓/𝑏𝑏𝑐𝑐= 0.25 mm, 𝛾𝛾= 0.8765, 𝑇𝑇= 0.5, N = 88300, for the specimen from group B and 𝑓𝑓𝑐𝑐𝑢𝑢= 62.2 MPa, 𝑏𝑏𝑓𝑓/𝑏𝑏𝑐𝑐= 0.35 mm, 𝛾𝛾= 1, 𝑇𝑇= 0.55, N = 20680, for the specimen from group C. As can be observed from the two figures, the results from both models tend to agree more with group-B specimens compared to group-C specimens. This is attributed to the fact that the parameter of FRP-to-concrete width ratio was considered in specimens from group B when developing the bond-slip model. Therefore, the superiority of the developed bond-slip model against the
previous proposed models was that the effect of the CFRP-to-concrete width ratio was taken into account when deriving the bond-slip curves. In addition, the bilinear bond-slip model was reported to be simpler and more efficient for identifying the fatigue interfacial behavior of CFRP/concrete bond [31].
Fig. 6. Bond-slip curves of a tested specimen under different number of load cycles (n) by Li et al. [31]
Fig. 7. Bond-slip model curves of a specimen from Group B (considering loading amplitude and concrete strength as variables)
Fig. 8. Bond-slip model curves of a specimen from Group C (considering bond length and FRP-to-concrete width ratio as variables)
Zhang [32] carried out some research to develop a bond stress-slip model and proposed the following equations to determine the local bond stress-slip relationship of specimens reinforced with high-strength (HS) CFRP plate.
The proposed model, which was based on the model first presented by Popovics [40], showed good agreement with their own experimental results from a series of double-lap fatigue shear tests:
𝑠𝑠𝑒𝑒𝑢𝑢= 0.046𝐸𝐸𝐸𝐸𝑀𝑀(0.26 log(𝑛𝑛)) (21)
𝐾𝐾𝑢𝑢𝑛𝑛.𝑚𝑚
𝐾𝐾𝑢𝑢𝑛𝑛.1= 1.25−0.20 log(𝑛𝑛) (22)
𝜏𝜏𝑒𝑒𝑢𝑢 =𝜏𝜏𝑚𝑚𝑚𝑚𝑚𝑚𝑠𝑠𝑒𝑒𝑢𝑢
𝑠𝑠0 ×(𝑚𝑚−1)+(𝑚𝑚𝑠𝑠𝑒𝑒𝑢𝑢 𝑠𝑠0
� )𝑚𝑚 (23)
Where 𝑠𝑠𝑒𝑒𝑢𝑢 and 𝜏𝜏𝑒𝑒𝑢𝑢 are the slip and stress values on the envelope curve, respectively, 𝑛𝑛 is the number of fatigue cycles, 𝐾𝐾𝑢𝑢𝑖𝑖.𝑖𝑖 and 𝐾𝐾𝑢𝑢𝑖𝑖.1 are the unloading stiffness at cycle 𝑛𝑛 and the unloading stiffness during the first cycle, respectively, which can be determined by the unloading slope from the envelope curve, 𝜏𝜏𝑚𝑚𝑚𝑚𝑚𝑚 and 𝑠𝑠0 are the maximum bond stress and the corresponding slip, respectively and 𝑚𝑚 is the curve characteristic constant which is equal to 3.44. The proposed model showed good agreement with the experimental results of specimens strengthened with HS CFRP plates. However, the applicability of the aforementioned model on other types of CFRP reinforcement requires further investigation.
Considering the cyclic bond-slip models discussed above, it is fair to say that the model developed by Li et al.
[31], expressed in equations (12) – (20), has successfully taken into account the influencing factors, in particular FRP-to-concrete width ratio, and is able to predict interfacial shear stress of FRP-to-concrete bond under fatigue loading with adequate accuracy. Nevertheless, the proposed model was developed on the basis of limited experimental data and therefore its effectiveness can be enhanced by encompassing a wider range of test results.
3.2 FRP/concrete bond fatigue life models
A fatigue life model was proposed by Bizindavyi et al. [26] in the form of the following power-law relationship for FRP/concrete bonded members:
𝑆𝑆= (𝑁𝑁𝑏𝑏×𝐶𝐶𝑏𝑏)−𝜔𝜔 (24)
Where, 𝑆𝑆 is the cyclic mean bond stress range, and can be obtained from the maximum and minimum applied stresses, 𝑆𝑆𝑚𝑚𝑚𝑚𝑚𝑚− 𝑆𝑆𝑚𝑚𝑖𝑖𝑖𝑖, 𝑁𝑁𝑏𝑏 is the number of cycles to the bond failure, and 𝐶𝐶𝑏𝑏 and 𝜔𝜔 are constants obtained from test data. In their experimental investigation, which led to the aforementioned S-N model, two different FRP types, i.e., Glass FRP (GFRP) and Carbon FRP (CFRP), were applied to the specimens. It was observed from the S-N curves that the fatigue life of the FRP/concrete interface can be reduced by either increasing the applied stress level or decreasing the bond length.
Following an analytical investigation of the shear behavior of the FRP/concrete interface under fatigue loading, Diab et al. [27] proposed a prediction methodology to determine the fatigue life of the FRP/concrete interface. A nonlinear interfacial constitutive law was proposed to calculate the rate of debonding growth per loading cycle (𝑑𝑑𝑚𝑚𝑑𝑑
𝑑𝑑𝑖𝑖), which can be expressed as follows:
𝑑𝑑𝑚𝑚𝑑𝑑
𝑑𝑑𝑖𝑖 =𝑚𝑚1�𝐺𝐺𝑚𝑚𝑚𝑚𝑚𝑚𝐺𝐺
𝑐𝑐 �𝑖𝑖1𝛽𝛽𝑑𝑑 (25)
Where 𝑀𝑀𝑑𝑑 is the debonding length, 𝑛𝑛 is the number of cycles, 𝑚𝑚1 and 𝑛𝑛1 are parameters obtained from regression analysis of experimental tests, and 𝐺𝐺𝑚𝑚𝑚𝑚𝑚𝑚 and 𝐺𝐺𝑐𝑐 are the maximum strain-energy release rate and the quasi-static fracture energy, respectively. Finally, 𝛽𝛽𝑑𝑑 is the fatigue debonding growth coefficient, which is used to account for the reduction in debonding propagation rate with increasing debonding length, 𝑀𝑀𝑑𝑑.
Li et al. [29] proposed a prediction model for the fatigue life of the FRP/concrete interface that takes into account the concrete cube compressive strength (𝑓𝑓𝑐𝑐𝑢𝑢) and the CFRP-to-concrete width ratio (𝑏𝑏𝑓𝑓/𝑏𝑏𝑐𝑐) as follows:
𝑆𝑆𝑓𝑓
�1−𝑆𝑆𝑓𝑓.𝑚𝑚�= 1.90−0.0902� 0.0902 ln 𝑁𝑁𝑏𝑏
[(2.06×10−3𝑓𝑓𝑐𝑐𝑢𝑢)+0.872]�1.094−�0.382𝑏𝑏𝑓𝑓⁄ ��𝑏𝑏𝑐𝑐 � for
𝑆𝑆𝑓𝑓/�1− 𝑆𝑆𝑓𝑓.𝑚𝑚�> 1.90− � 1.90−(0.3 0.7)⁄
[(2.06×10−3𝑓𝑓𝑐𝑐𝑢𝑢)+0.872]�1.094−�0.382𝑏𝑏𝑓𝑓⁄ ��𝑏𝑏𝑐𝑐 � (26)
𝑁𝑁𝑏𝑏 > 2 million for 𝑆𝑆/�1− 𝑆𝑆𝑓𝑓.𝑚𝑚� ≤1.90− � 1.90−(0.3 0.7)⁄
[(2.06×10−3𝑓𝑓𝑐𝑐𝑢𝑢)+0.872]�1.094−�0.382𝑏𝑏𝑓𝑓⁄ ��𝑏𝑏𝑐𝑐 � (27)
In Eqs. (26) and (27), 𝑁𝑁𝑏𝑏 represents the fatigue life of the FRP/concrete interface, and 𝑆𝑆𝑓𝑓 and 𝑆𝑆𝑓𝑓.𝑚𝑚 are the stress amplitude and related mean stress of the CFRP sheet at the mid-span of the four-point bending test, respectively and are given by:
𝑆𝑆𝑓𝑓 =𝑆𝑆𝑓𝑓.𝑚𝑚𝑚𝑚𝑚𝑚𝑆𝑆−𝑆𝑆𝑓𝑓.𝑚𝑚𝑚𝑚𝑛𝑛
𝑓𝑓.𝑢𝑢 ; 𝑆𝑆𝑓𝑓.𝑚𝑚=𝑆𝑆𝑓𝑓.𝑚𝑚𝑚𝑚𝑚𝑚2𝑆𝑆+𝑆𝑆𝑓𝑓.𝑚𝑚𝑚𝑚𝑛𝑛
𝑓𝑓.𝑢𝑢 (28)
Where 𝑆𝑆𝑓𝑓.𝑢𝑢 = ultimate stress in the CFRP sheet at mid-span obtained from the monotonic test and 𝑆𝑆𝑓𝑓.𝑚𝑚𝑚𝑚𝑚𝑚 and
𝑆𝑆𝑓𝑓.𝑚𝑚𝑖𝑖𝑖𝑖 are the maximum and minimum stress in the CFRP sheet at the mid-span (in the four-point bending test
setup), obtained from the fatigue test, respectively. Hence, as can be understood from the prediction model, by measuring the applied stresses to CFRP and calculating the ratio 𝑆𝑆/(1− 𝑆𝑆𝑓𝑓.𝑚𝑚), the fatigue life of CFRP-to-concrete interface (𝑁𝑁𝑏𝑏) can be determined [29].
An S-N relationship of the CFRP/concrete bond was proposed by Zheng et al. [25] based on an experimental program including a series of double-lap shear tests on specimens with hygrothermal pre-treatment in which the temperature and relative humidity of environmental chambers were set according to the considerations stated in Zheng et al. [25]. It should be noted that by using Eq. (29), the CFRP/concrete bond fatigue strength (𝑆𝑆𝑏𝑏) was determined as 59% of static bond strength within 2 million load cycles (𝑁𝑁𝑏𝑏) :
𝑆𝑆𝑏𝑏 = 1.65−0.167 log𝑁𝑁𝑏𝑏 (29)
In an experimental study by Xie et al. [33], the fatigue behavior of the interface between basalt-FRP (BFRP) sheets and concrete under marine environmental conditions (i.e., environment with large temperature variations and over repeated wet-dry cycles) was investigated. The following empirical equation was proposed to determine the fatigue life of the BFRP/concrete bond:
𝑆𝑆𝑏𝑏 = 1.16−0.088 log𝑁𝑁𝑏𝑏 (30)
Where 𝑆𝑆𝑏𝑏 is the stress ratio of BFRP and 𝑁𝑁𝑏𝑏 is the number of cycles at which fatigue failure of the BFRP/concrete interface occurs. It is noteworthy that the measured fatigue strength of the BFRP/concrete interface with exposure to marine conditions was approximately 60% of its ultimate monotonic load-carrying capacity.
It can be understood from the S-N models discussed above that the interface between the FRP and concrete tends to comply with a different fatigue life relationship depending on various conditions, namely, Glass or Carbon FRP-to-concrete bond, bond in hygrothermal environment and also Basalt FRP-to-concrete interface. Hence, when applying the fatigue life model at the interface between FRP and concrete, it is of importance to ensure that the model corresponds to the right condition and predicts the fatigue behavior of the bond accordingly.
3.3 Concrete compressive strength
The influence of concrete compressive strength on the bond behavior of the FRP/concrete interface has been investigated through many experimental studies. Experimental investigations on the FRP-to-concrete bonded members have revealed different forms of debonding failure including concrete cover separation and intermediate crack-induced debonding [42]. In cases where the interfacial failure of the FRP/concrete bond is due to the concrete cover separation, it is reasonable to believe that increasing the concrete compressive strength could result in an enhancement in the ultimate load capacity of the bond between concrete and FRP under static loading [43].
Likewise, results of another investigation showed that increasing the concrete compressive contributes to reaching higher cohesive stress at the FRP/concrete interface as well as delaying the activation of FRP strain under static loading [44].
As far as fatigue loading is concerned, test observations have indicated that increasing the concrete strength extends the fatigue life of FRP/concrete interface [29, 30]. In an experimental study by Li et al. [29], specimens with three concrete cube compressive strengths of 62.2, 35.3, and 25.1 MPa bonded with CFRP were tested under the same fatigue loading ratio (𝑀𝑀𝑚𝑚𝑚𝑚𝑚𝑚/𝑀𝑀𝑢𝑢= 0.65). It was shown that increasing the concrete strength from 25.1 MPa to 35.3 MPa and from 35.3 MPa to 62.2 MPa enhanced the number of load cycles to failure of CFRP/concrete interface by approximately 30% and 90 %, respectively. Similarly, it was reported by Chen and Cheng [45] that concrete with a higher compressive strength, and hence a higher tensile strength, could help hinder the fatigue crack propagation and lower the distributed axial strain on the FRP reinforcement, thereby improving the performance of the bond between FRP and concrete. An experimental program was carried out by Zhu et al. [30]
on nine concrete beam specimens strengthened with EB-CFRP to study the bond-slip behavior of the CFRP/concrete interface under fatigue loading conditions for the same three concrete cube compressive strengths investigated by Li et al. [29] (i.e., 25.1 MPa, 35.3 MPa, and 62.2 MPa). It was observed that debonding may occur in one of the three regions of concrete cover, interface between concrete and epoxy, and interface between CFRP
and epoxy. Furthermore, it has appeared that as concrete compressive strength increases, the fatigue life of the CFRP/concrete interface reaches higher levels, leading to an improvement in the performance of the bonding system. In addition, the maximum interfacial shear stress at the first cycle was seen to rise with an increase in the concrete strength. Indeed, an increase of about 40% and 230% in the shear stress of concrete/FRP interface was observed when the concrete strength increased from 25.1 MPa to 35.3 MPa and then from 35.3 MPa to 62.2 MPa, respectively. It may be of interest to note that higher concrete strength triggers the failure to occur as a result of CFRP sheet debonding from the epoxy resin rather than the concrete cover separation in the specimen [30].
Another study by Li et al. [31] showed that variations in the concrete compressive strength can affect the bond- slip relationship of the FRP/concrete interface during the cyclic loading. Indeed, the slope of the ascending branch of the bond-slip curve tends to decrease at a lower rate during the load cycles, with an increase in the concrete strength.
3.4 Bond length
The effect of bond length on the fatigue behavior of the CFRP/concrete interface has been evaluated in many research studies. It was concluded in a research review that increasing FRP bond length enhances the fatigue life of the FRP/concrete interface [10]. In an experimental investigation by Li et al. [29], the fatigue endurance of the CFRP/concrete bond was evaluated with respect to bond lengths of 60, 160, and 240 mm, where increased bond length contributed to higher bond fatigue endurance of the FRP/concrete interface. Indeed, test observations indicated that increasing the bond length from 60 mm to 160 mm resulted in an increase of about 338% in the fatigue life of CFRP/concrete interface, and when the bond length increased from 160 mm to 240 mm, the number of cycles to failure of specimens has almost tripled. It was reported that, when the bond length increases, the increase in the fatigue life of the bond between CFRP and concrete was attributed to the fact that more loading cycles were needed to delaminate the CFRP sheets from the concrete [31]. Similar experimental results were observed in an study by Bizindavyi et al. [26], in which shorter bonded length seemed to reduce the fatigue life of the FRP/concrete interface by creating higher stress intensity levels at the FRP-to-concrete bond.
The effective bond length in FRP-strengthened concrete structures is defined as the minimum FRP bonded length at which the maximum force is transferred between the concrete substrate and the EB-FRP composite [23].
The effective bond length can be determined in experimental programs by taking the average of the bonded lengths of three specimens with the same load-carrying capacity at failure that have been tested constitutively, within a tolerance of 10% [46]. In the case of monotonic loading, the effective bond length (𝑙𝑙𝑒𝑒) can be obtained from the following equations according to existing guidelines:
𝑙𝑙𝑒𝑒= (𝑖𝑖 23300
𝑓𝑓×𝐸𝐸𝑓𝑓×𝑡𝑡𝑓𝑓)0.58 [11] (31) 𝑙𝑙𝑒𝑒= (𝑖𝑖 25350
𝑓𝑓×𝐸𝐸𝑓𝑓×𝑡𝑡𝑓𝑓)0.58 [46] (32) 𝑙𝑙𝑒𝑒= 𝑘𝑘𝜋𝜋
𝑏𝑏�𝑖𝑖8 𝑓𝑓𝑓𝑓×𝐸𝐸𝑓𝑓×𝑡𝑡𝑓𝑓
𝑐𝑐𝑚𝑚2/3 , 𝑘𝑘𝑏𝑏=�2−𝑏𝑏1+𝑏𝑏𝑓𝑓𝑓𝑓/𝑏𝑏/𝑏𝑏𝑐𝑐𝑐𝑐 [23] (33) Where, 𝑛𝑛𝑓𝑓 is the number of FRP layers, 𝐸𝐸𝑓𝑓 and 𝑡𝑡𝑓𝑓 are the elastic modulus and thickness of FRP, respectively, 𝑓𝑓𝑐𝑐𝑚𝑚 is the concrete mean compressive strength and 𝑏𝑏𝑓𝑓/𝑏𝑏𝑐𝑐 is the FRP-to-concrete width ratio.
It has been reported by Li et al. [29] that the effective bond length obtained experimentally under fatigue loading with the frequency of 2.5 Hz is less than that under monotonic loading at a rate of 0.001 mm/s. This can be attributed to the fact that the debonding failure of the specimen initiates at a lower load level during fatigue loading in comparison with that under quasi-static loading. Moreover, the interfacial crack propagation tends to occur in the epoxy adhesive rather than in the concrete under the fatigue condition [28, 29, 47]. It has also been experimentally observed that increasing the bond length beyond the effective bond length does not seem to affect either the debonding load level or the bond strength of the CFRP/concrete interface [29, 31].
3.5 FRP-to-concrete width ratio
As discussed in the bond-slip models, the factor of FRP-to-concrete width ratio (𝑏𝑏𝑓𝑓/𝑏𝑏𝑐𝑐), included in some of the proposed bond slip models (see Eq. 11), plays a key role in determining the bond behavior of the FRP/concrete interface under fatigue loading; therefore, neglecting its effect could lower the accuracy of the bond-stress slip predictions obtained from the models. Considering the effect of FRP width on the fatigue behavior of the FRP/concrete interface, it has been experimentally observed that using narrower FRP laminates leads to higher slip values [26], which could be attributed to the greater stress concentration imposed on the FRP-to-concrete interface. Furthermore, a series of other experimental tests has revealed that the fatigue life of the FRP/concrete interface drops with increasing CFRP-to-concrete width ratio, which may be due to the fact that the interfacial
bond capacity tends to increase at lower FRP-to-concrete ratios [29]. Another study by Li et al. [31] also showed that increasing the CFRP-to-concrete width ratio in strengthened concrete specimens during a sequence of load cycles reduces the fatigue resistance of the CFRP/concrete interface and accelerates the reduction in the slope of the ascending segment of the corresponding bond-slip curve.
3.6 Fatigue loading amplitude
Test results on the effect of fatigue loading amplitude revealed that the fatigue life of the CFRP/concrete interface tends to decline with increasing loading amplitude [25, 29, 33]. It has also been reported that at higher loads, the fatigue life of the concrete/FRP interface is dominated by crack initiation, whereas at lower fatigue load limits, crack propagation plays the main role in determining bond fatigue strength [28]. Experimental observations of cyclic single-lap shear tests conducted by Bizindavyi et al. [26] revealed that CFRP-strengthened concrete specimens are likely to fail due to rupture of laminates at higher applied cyclic stresses, particularly when the maximum stress is close to the static load-bearing strength of the CFRP laminate. This effect was also observed on the bond performance of near-surface mounted (NSM) strips under fatigue loading, where it has been demonstrated that the bond strength of NSM strips does not undergo a significant decrease provided that the upper applied load is less than 60% of the monotonic debonding load and that the stress amplitude of the FRP strip is kept below 250 MPa [23]. Finally, an experimental study on the effect of fatigue loading amplitude by Zhu et al.
[30] showed that an increase in the number of load cycles leads to a degradation of the bond stress-slip curve, meaning that shear stress is reduced under the same slip condition.
4. Finite-element analysis of EB-FRP/concrete interface under fatigue loading
Finite-element analysis (FEA) provides a cost-effective tool to evaluate structural behavior by taking into account a wide spectrum of influencing parameters without having to perform time-consuming and costly experiments [48]. Numerous studies have been carried out on the use of finite-element (FE) simulations of EB- FRP strengthened RC structures and particularly of FE modeling of the FRP/concrete interface under both static and fatigue loading. It has been reported that applying an appropriate model for the FRP/concrete bond as well as the interface between the internal steel and concrete in FRP shear strengthened RC beams could significantly alter the numerical responses, in particular, the shear capacity of the beam under static loading [49]. However, Loo et al. [41] found that there is a negligible slippage between concrete and steel reinforcement in FRP strengthened RC structures during fatigue loading cycles. Hence, the FE modeling of steel/concrete interface does not affect the cyclic behavior of the structure as much as modeling of the bond between FRP and concrete. It should be noted that regarding numerical analysis of RC beams strengthened with EB-FRP under fatigue loading, researchers have investigated only the flexural behavior of structures, and to the authors’ knowledge, there has been no investigation on FE modeling of the FRP/concrete interface in EB-FRP shear-strengthened RC beams under cyclic loading.
Nevertheless, a few FE studies have been conducted on the fatigue behavior of the bond between concrete prisms and FRP materials in pull-out shear tests [50, 51].
4.1 FE modeling of the FRP/concrete bond
The modeling of the FRP/concrete interface has a significant effect on the numerical results derived from FE simulations. It is now well established that assuming a perfect bond between EB-FRP and concrete under monotonic loading results in over-estimation of the shear resistance of shear-strengthened RC beams [48, 49, 52].
The FE modeling of the interface between FRP and concrete under fatigue loading has been performed in a few studies, which led to an enhancement in the numerical results validated with the experimental observations. In a numerical investigation on the fatigue performance of EB-FRP strengthened RC beams in flexure by Wang et al.
[53], the concrete/FRP bond behavior was defined using the bilinear bond-slip model proposed by Lu et al. [20].
As for the bond geometry modeling, contact elements (TARGE170 and CONTA174) in ANSYS were used. The contact elements were able to take into account the shear stresses between the two interfacial surfaces by applying a Coulomb friction model. Also, in FE simulations performed by Pathak and Zhang [54] on EB-FRP strengthened RC beams in flexure under cyclic loading, the model developed by Loo et al. [41] was adopted to characterize the bond-slip behavior of the interface between FRP and concrete. Spring elements in ANSYS were used to simulate the interfaces between concrete, adhesive and FRP. This two-node nonlinear element has no physical mass and dimension and can incorporate the cyclic bond-slip model for the interfacial behavior. Indeed, through the implementation of the cyclic bond-slip models in the FEA of FRP-strengthened RC structures, a more accurate prediction of the bond behavior was achieved.
In another study, the EB-CFRP/concrete interface was simulated based on the Mohr-Coulomb criterion with tension cut-off [55]. Accordingly, the linear relationship between the interfacial stresses and the corresponding displacements in the tangential and normal directions (𝛥𝛥𝛥𝛥1 .𝛥𝛥𝛥𝛥2 .𝛥𝛥𝛥𝛥) was expressed according to the following equation:
�𝜏𝜏1 𝜏𝜏2
𝜎𝜎�=�𝑘𝑘𝑡𝑡𝑡𝑡 0 0 00 𝑘𝑘𝑡𝑡𝑡𝑡
0 0
𝑘𝑘𝑖𝑖𝑖𝑖
� �𝛥𝛥𝛥𝛥1 𝛥𝛥𝛥𝛥2
𝛥𝛥𝛥𝛥� (34)
Where 𝜏𝜏 and 𝜎𝜎 are the shear and normal stresses, respectively and 𝑘𝑘𝑡𝑡𝑡𝑡 and 𝑘𝑘𝑖𝑖𝑖𝑖 are the initial elastic normal and shear stiffnesses, respectively. The numerical model successfully evaluated the fatigue life of RC beams with different levels of flexural deficiencies when compared to the corresponding experimental data.
Fatigue modeling of the EB-FRP/concrete interaction has also been investigated in numerical studies of shear pull-out tests. Daud et al. [50] performed a numerical analysis on a single shear pull-out test and evaluated the interfacial behavior between the concrete block and the bonded CFRP plate under post-fatigue loading condition.
The bond between the concrete and the EB-CFRP was represented using cohesive elements in which a traction separation model was applied. In another numerical investigation simulating a series of single shear pull-out tests of CFRP bonded concrete blocks under fatigue loading [51], the interaction between the concrete and the CFRP laminate was modeled using two techniques. In the first technique, a solid element with a perfect bond was used to represent the adhesive between the concrete and the CFRP, whereas in the second, an interface element was assumed between the two components. It was concluded that using a solid element with a perfect bond exhibited more realistic specimen behavior under fatigue loading than using an interface element.
4.2 Numerical parametric studies on the FRP/concrete bond
Numerical investigations have been conducted to evaluate the influence of different parameters on the behavior of bond between FRP and concrete, specially in FRP strengthened RC beams, under both monotonic and fatigue loading. In a numerical study by Al-Rousan and Issa [56] under fatigue loading, the effects of applied stress range, CFRP-to-concrete contact area, and number of CFRP layers on the flexural capacity and deflection of the strengthened beam were assessed. The applied load range corresponded to various ratios of steel yielding stress (𝑓𝑓𝑠𝑠.𝑦𝑦), including 0.25𝑓𝑓𝑠𝑠.𝑦𝑦–0.35𝑓𝑓𝑠𝑠.𝑦𝑦, 0.45𝑓𝑓𝑠𝑠.𝑦𝑦–0.65𝑓𝑓𝑠𝑠.𝑦𝑦, 0.65𝑓𝑓𝑠𝑠.𝑦𝑦–0.90𝑓𝑓𝑠𝑠.𝑦𝑦, and 0.45𝑓𝑓𝑠𝑠.𝑦𝑦–0.90𝑓𝑓𝑠𝑠.𝑦𝑦. The stress range had a considerable influence on the structural behavior in terms of mid-span deflection, stiffness degradation, and failure mode, particularly for the fatigue stress range of 0.45𝑓𝑓𝑠𝑠.𝑦𝑦–0.90𝑓𝑓𝑠𝑠.𝑦𝑦. Further numerical results proved that increasing either the CFRP contact area with concrete or the number of CFRP layers leads to an enhancement in stiffness and ultimate load capacity, as well as a reduction in mid-span beam deflection. Likewise, through nonlinear FEA of CFRP-strengthened RC beams in flexure under cyclic loading, Pathak and Zhang [54] indicated that increasing the FRP thickness resulted in a decrease in beam deflection as well as FRP strain. However, in a numerical parametric study of the number of CFRP layers on the fatigue life of FRP strengthened RC beams by Banjara and Ramanjaneyulu [55], it was shown that using three CFRP layers did not significantly increase the load-carrying capacity of beams over that achieved with two layers of CFRP.
According to the numerical results, it was also observed that carbon FRP (CFRP) strips exhibited a better performance in reducing beam deflection and increasing beam fatigue life when compared to glass FRP (GFRP) strips. Furthermore, the computational results demonstrated that beams strengthened with longer FRP sheets underwent less central deflection and showed lower FRP strain [54].
The effect of prestressing CFRP on the fatigue behavior of flexural strengthened RC beams was analyzed in a FE study by Guo et al. [57]. Various prestressing levels (0%, 10%, 15%, and 22%) were modelled by applying initial stress values to the CFRP laminates. Increasing the prestressing level resulted in enhanced beam fatigue life by reducing the stresses on the reinforcing bars. However, using prestressed laminates tended to increase damage to the CFRP/concrete interface, increasing thereby the possibility of debonding failure. Similar conclusions were made by Wang et al. [58] upon FEA of RC beams strengthened in flexure with prestressed hybrid FRP (HFRP), consisting of hybrid carbon and glass FRP (C/GFRP), under fatigue loading. It was stated that applying too much prestressing could lead to a large reversed arch and premature fracture of C/GFRP composites.
Environmental conditions can also affect the fatigue behavior of FRP-strengthened beams in flexure. Indeed, numerical observations have shown that hygrothermal conditions (high temperature, high humidity) can decrease the strength of the CFRP/concrete interface and increase the stress level of internal steel reinforcement, in turn leading to an accelerated rate of damage at the CFRP/concrete interface and at the main longitudinal steel reinforcement under fatigue loading [59]. It has also been observed that CFRP-strengthened beams in an indoor environment tend to fail as a result of steel reinforcing rupture under fatigue loading, whereas the failure mode of beams in hygrothermal environments was found to be debonding of the CFRP/concrete interface [59].
An assessment of the effect of various design parameters such as concrete compressive strength, CFRP stiffness, CFRP-to-concrete width ratio, and CFRP bond length on the post-fatigue performance of the CFRP/concrete interface was conducted in a numerical investigation consisting of a single pull-out test [50]. The study revealed that increasing the bond length increases the ultimate load capacity until the effective bond length is provided, after which the ultimate load tends to stabilize. As for variation in concrete compressive strength, higher concrete