D300778 0613 - piconet® I/O Modules 9-1

Type overview

The device type Sxxx-0800D-xxxx is designed for connection of 4 binary switches or sensors as well as 4 binary actuators. The devices come as stand-alone or extension modules and differ in their connection technology, the input filter speed and the various admissible output current ratings.

Table 39:

Type overview digital Combined modules

Sxxx-0404D-x00x Description Connection technology Sxxx-0404D-x003,

Page 9-3

– 4 digital inputs, 24 V DC, filter 3.0 ms – 4 digital outputs

24 V DC, Imax = 0.5 A M8

Sxxx-0404D-x004, Page 9-3

M12

Sxxx-0404D-x001, Page 9-3

– 4 digital inputs, 24 V DC, filter 0,2 ms – 4 digital outputs

24 V DC, Imax = 0.5 A M8

Sxxx-0404D-x002, Page 9-3

M12

Sxxx-0404D-x007, Page 9-9

– 4 digital inputs, 24 V DC, filter 3.0 ms – 4 digital outputs,

24 V DC, Imax = 2 A (IΣ = 4 A)

M8

Sxxx-0404D-x008, Page 9-9

M12

Sxxx-0404D-x005, Page 9-9

– 4 digital inputs, 24 V DC, filter 0,2 ms – 4 digital outputs,

24 V DC, Imax = 2 A (IΣ = 4 A)

M8

Sxxx-0404D-x006, Page 9-9

M12

Sxxx-0808D-x001, Page 9-15

– 8 digital inputs, 24 V DC, filter 3.0 ms

M8

D300778 0613 - piconet® I/O Modules 9-3 Sxxx-0404D-x003/-x004/-x001/-x002, 4-port digital input; 4-

port digital output

Sxxx-0404D-x003/-x004/-x001/-x002, 4-port digital input;

4-port digital output

These digital I/O modules combine 4 digital inputs with an input filter of 3.0 ms or 0.2 ms and 4 digital 24 V DC outputs in a single device.

The outputs are suited for load currents of 0.5 A; they are short- circuit-proof and reverse-polarity protected.

The signal status can be indicated separately for each channel via LEDs.

The inputs are located on the upper half of the modules. With M8 connection technology modules, these are the upper four connectors (C0 to C3), and with the M12 technology modules the two upper connectors (C0, C1) with two inputs on one connector.

Figure 37:

SDPB-0404D-x00x SNNE-0404D-000x

26,5

C0

C1 C3 C5 C7

C2 C4 C6

168

23

175

30 C0 C1 C2 C3

33 33

C0

C1 C3 C5 C7

C2 C4 C6

119

23

126

30 C0 C1 C2 C3

26,5 33

D300778 0613 - piconet® I/O Modules 9-5 Sxxx-0404D-x003/-x004/-x001/-x002, 4-port digital input; 4-

port digital output

Technical data Table 40:

Technical data

Designation Sxxx-0404D-x003, -x004,

-x001, -x002 Voltage supply

Operating voltage UB 24 VDC (- 15 %/+ 20 %) Load voltage UL 24 VDC (- 15 %/+ 20 %) Inputs

Number of inputs 4, according to EN 61131-2

Input voltage 24 VDC (-15%/+ 20%)

Supply current 500 mA, short-circuit protected

Input filter 0.2 ms or 3.0 ms

Max. input current < 7 mA

Switching point 0/1 -3... 5 V / 11...30 V, 6 mA input current (EN 61131-2, type 2)

Sensor supply from operating voltage UB, max.

0.5 A per module,

common short-circuit protection Outputs

Number of outputs 4, according to EN 61131-2

Output voltage 24 VDC (-15%/+ 20%)

Output current per channel max. 0.5 A per channel,

individually short-circuit protected

Load type ohmic, inductive, lamp load

Short-circuit current typically 1.5 A (cyclic) Switching frequency 500 Hz

Simultaneity factor 1

Wiring diagrams Figure 38:

Connection to M8

Inputs:

3 4

1 (–) ( ) (+)

Outputs:

3 4

1 (–)

(+) + 24 VDC Current consumption Load voltage

20 mA. typ.

Bits in the process image 4 input or 4 output bits

Potential isolation – Channels/Operating voltage: no – Between the channels: no – Operating voltage/fieldbus: yes

Figure 39:

Connection to the M12

Inputs:

(–) ( ) (+) (–) ( ) (+) 4

1 3

2

5

outputs:

(–) (+)

4

1 3

2

5 (–)

(+)

D300778 0613 - piconet® I/O Modules 9-7

Sxxx-0404D-x003/-x004/-x001/-x002, 4-port digital input; 4- port digital output

Parameters

Detailed information on fieldbus-dependent parameterisation of the modules is contained in the chapter "Parameters of the piconet® I/O modules" of the following manuals:

„ Profibus-DP

German: „piconet® for PROFIBUS-DP“, D300775 English: „piconet® for PROFIBUS-DP“, D300776

„ DeviceNet Not yet published

„ CANopen Not yet published

Diagnosis

Diagnostics via LEDs

Please read the description of the diagnostic LEDs in the event of local errors of the coupling and extension modules in Chapter 5 of this manual: Fieldbus-specific diagnostic indications via LEDs are described in the chapter "Error treatment and diagnostics" of the above mentioned manuals.

Diagnostics via software

Detailed information on fieldbus-dependent diagnostics of the modules is contained in the chapter "Error treatment and diagnostics" of the above mentioned manuals.

D300778 0613 - piconet® I/O Modules 9-9 Sxxx-0404D-x007/-x008/-x005/-x006, 4-port digital input; 4-

port digital output

Sxxx-0404D-x007/-x008/-x005/-x006, 4-port digital input; 4-port digital output

These digital I/O modules combine 4 digital inputs with an input filter of 3.0 ms or 0.2 ms and 4 digital 24 V DC outputs in a single device.

The 8 outputs process load currents of up to 2 A each; the maximum total current is limited to IΣ = 4 A.

The outputs are short-circuit and reverse-polarity protected.

The signal status can be indicated separately for each channel via LEDs.

The inputs are located on the upper half of the modules. With M8 connection technology modules, these are the upper four connectors (C0 to C3), and with the M12 technology modules the two upper connectors (C0, C1) with two inputs on one connector.

Figure 40:

SDPB-0404D-x00x SNNE-0404D-000x

26,5

C0

C1 C3 C5 C7

C2 C4 C6

168

23

175

30 C0 C1 C2 C3

33 33

C0

C1 C3 C5 C7

C2 C4 C6

119

23

126

30 C0 C1 C2 C3

26,5 33

D300778 0613 - piconet® I/O Modules 9-11 Sxxx-0404D-x007/-x008/-x005/-x006, 4-port digital input; 4-

port digital output

Technical data Table 41:

Technical data

Designation Sxxx-0404D-x007/ -x008/

-x005/ -x006 Voltage supply

Operating voltage UB 24 VDC (- 15 %/+ 20 %) Load voltage UL 24 VDC (- 15 %/+ 20 %) Inputs

Number of inputs 4, according to EN 61131-2

Input voltage 24 VDC (-15%/+ 20%)

Supply current 500 mA, short-circuit protected

Input filter 3.0 ms and 0.2 ms

Max. input current < 7 mA

Switching point 0/1 -3... 5 V / 11...30 V, 6 mA Input current

(EN 61131-2, type 2)

Sensor supply from operating voltage UB, max.

0.5 A per module,

common short-circuit protection Outputs

Number of outputs 4, according to EN 61131-2

Output voltage 24 VDC (-15%/+ 20%)

Output current per channel max. 2 A per channel; IΣ = 4 A;

individually short-circuit protected

Load type ohmic, inductive, lamp load

Short-circuit current typically 1.5 A (cyclic) Switching frequency 500 Hz

Simultaneity factor 1

Wiring diagrams Figure 41:

Connection to M8

Inputs:

3 4

1 (–) ( ) (+)

Outputs:

3 4

1 (–)

(+) + 24 VDC Current consumption Load voltage

20 mA. typ.

Bits in the process image 4 input or 4 output bits

Potential isolation – Channels/Operating voltage: no – Between the channels: no – Operating voltage/fieldbus: yes

Figure 42:

Connection to the M12

Inputs:

(–) ( ) (+) (–) ( ) (+) 4

1 3

2

5

outputs:

(–) (+)

4

1 3

2

5 (–)

(+)

D300778 0613 - piconet® I/O Modules 9-13

Sxxx-0404D-x007/-x008/-x005/-x006, 4-port digital input; 4- port digital output

Parameters

Detailed information on fieldbus-dependent parameterisation of the modules is contained in the chapter "Parameters of the piconet® I/O modules" of the following manuals:

„ Profibus-DP

German: „piconet® for PROFIBUS-DP“, D300775 English: „piconet® for PROFIBUS-DP“, D300776

„ DeviceNet Not yet published

„ CANopen Not yet published

Diagnosis

Diagnostics via LEDs

Please read the description of the diagnostic LEDs in the event of local errors of the coupling and extension modules in Chapter 5 of this manual: Fieldbus-specific diagnostic indications via LEDs are described in the chapter "Error treatment and diagnostics" of the above mentioned manuals.

Diagnostics via software

Detailed information on fieldbus-dependent diagnostics of the modules is contained in the chapter "Error treatment and diagnostics" of the above mentioned manuals.

D300778 0613 - piconet® I/O Modules 9-15 Sxxx-0008D-x001, 8-port digital combined module

Sxxx-0008D-x001, 8-port digital combined module

The device type Sxxx-0800D is designed for connection of 8 binary switches or sensors and 8 binary actuators.

These digital I/O modules provide 8 digital inputs with an input filter of 3.0 ms or alternatively 8 digital 24 V DC outputs.

A maximum current of 0.5 A per actuator is permitted. The outputs are short-circuit and reverse-polarity protected.

An LED is assigned to each input and output for switching status indications.

Figure 43:

SDPB-0808D-x001 SNNE-0808D-0001

26,5

168

23

175

30 C0

C1 C3 C5 C7

C2 C4 C6 33 33

26,5 33

119

23

126

30 C0 C2 C4 C6

C1 C3 C5 C7

D300778 0613 - piconet® I/O Modules 9-17 Sxxx-0008D-x001, 8-port digital combined module

Technical data Table 42:

Technical data

Designation Sxxx-0808D-x001

Voltage supply

Operating voltage UB 24 VDC (- 15 %/+ 20 %) Load voltage UL 24 VDC (- 15 %/+ 20 %) Inputs

Number of inputs 8, according to EN 61131-2

Input voltage 24 VDC (-15%/+ 20%)

Supply current 500 mA, short-circuit protected

Input filter 3.0 ms

Max. input current < 7 mA

Switching point 0/1 -3... 5 V / 11...30 V, 6 mA input current (EN 61131-2, type 2) Sensor supply from operating voltage UB,

max. 0.5 A per module,

common short-circuit protection Outputs

Number of outputs 8, according to EN 61131-2

Output voltage 24 VDC (-15%/+ 20%)

Output current per channel 0.5 A max.

individually short-circuit protected

Load type ohmic, inductive, lamp load

Short-circuit current typically 1.5 A (cyclic) Switching frequency 500 Hz

Simultaneity factor 1

Wiring diagrams Figure 44:

Connection to M8

Inputs:

ç C0...C7 3

4 1 2

(–)( ) (+)

Outputs:

ç C0...C7 3

4 1 2

(–) (+)

Current consumption Load voltage

20 mA. typ.

Bits in the process image 8 input or 8 output bits

Potential isolation – Channels/Operating voltage: no – Between the channels: no – Operating voltage/fieldbus: yes

D300778 0613 - piconet® I/O Modules 9-19 Sxxx-0008D-x001, 8-port digital combined module

Parameters

Detailed information on fieldbus-dependent parameterisation of the modules is contained in the chapter "Parameters of the piconet® I/O modules" of the following manuals:

„ Profibus-DP

German: „piconet® for PROFIBUS-DP“, D300775 English: „piconet® for PROFIBUS-DP", D300776

„ DeviceNet Not yet published

„ CANopen Not yet published

Diagnosis

Diagnostics via LEDs

Please read the description of the diagnostic LEDs in the event of local errors of the coupling and extension modules in Chapter 5 of this manual: Fieldbus-specific diagnostic indications via LEDs are described in the chapter "Error treatment and diagnostics" of the above mentioned manuals.

Diagnostics via software

Detailed information on fieldbus-dependent diagnostics of the modules is contained in the chapter "Error treatment and diagnostics" of the above mentioned manuals.

SNNE-0808D-0003, 8-port digital combined module with IP20 terminals The digital combi module SNNE-0808D-0003 has 16 channels with 8 inputs and 8 outputs.

The device can therefore be flexibly adapted to the requirements of the application.

The outputs handle load currents of up to 0.5 A. They are short- circuit-proof and protected against inverse polarity.

IP20 terminal tension spring connectors are used for the signal connection. These connectors are optionally available with 1 or 3 rows.

Note

The IP20 terminal tension spring connectors (1-row: SNNE-BL I/O 3,5-10/LED-SET, Ident.-No. 6824475 and 3-rows SNNE-BL I/O 3,5- 30/LED-SET, Ident.-Nr. 6824474) are not supplied with the module but can be ordered seperately.

Figure 45:

SNNE-0808D-0003

26,5 33

119

23

126

30 44

C0 C1

D300778 0613 - piconet® I/O Modules 9-21 SNNE-0808D-0003, 8-port digital combined module with IP20

terminals

Technical Data Table 43:

Technical data

Designation SNNE-0808D-0003

Voltage supply

Operating voltage UB 24 VDC (- 15 %/+ 20 %) Load voltage UL 24 VDC (- 15 %/+ 20 %) Inputs

Number of inputs 8, according to EN 61131-2

Input voltage 24 VDC (-15 %/+ 20 %)

Supply current 500 mA, short-circuit protected

Input filter 3.0 ms

Max. input current < 7 mA

Input type 3-wire pnp sensors

Switching point 0/1 -3... 5 V / 11...30 V, 6 mA input current (EN 61131-2, type 2) Sensor supply from operating voltage UB,

max. 0.5 A per module,

common short-circuit protection Connection technology terminals with spring connectors Outputs

Number of outputs 8, according to EN 61131-2

Output voltage 24 VDC (-15 %/+ 20 %)

Output current per channel 0.5 A max.

individually short-circuit protected

Load type ohmic, inductive, lamp load

Short-circuit current typically 1.5 A (cyclic) Switching frequency 500 Hz

Simultaneity factor 1 Current consumption

Load voltage

20 mA. typ.

Connection technology terminals with spring connectors Bits in the process image 8 input or 8 output bits

Potential isolation – Channels/Operating voltage: no – Between the channels: no – Operating voltage/fieldbus: yes

D300778 0613 - piconet® I/O Modules 9-23 SNNE-0808D-0003, 8-port digital combined module with IP20

terminals

Wiring diagrams Figure 46:

Connection IP20 terminals

Inputs:

+ 24 V (RD) P1 (GY) P2 (GY) P3 (GY) P4 (GY) P5 (GY) P6 (GY) P7 (GY) P8 (GY) 0 V(BU) + 24 V (RD)

P1 (GY) P2 (GY) P3 (GY) P4 (GY) P5 (GY) P6 (GY) P7 (GY) P8 (GY)

SNNE-BL I/O 3,5-10/LED-SET SNNE-BL I/O 3,5-30/LED-SET

Outputs:

+ 24 V (RD) + P1 (GY) + P2 (GY) + P3 (GY) + P4 (GY) + P5 (GY) + P6 (GY) + P7 (GY) + P8 (GY) 0 V(BU) +P1 (GY)

+P2 (GY) +P3 (GY) +P4 (GY) +P5 (GY) +P6 (GY) +P7 (GY) +P8 (GY) 0 V(BU)

SNNE-BL I/O 3,5-10/LED-SET SNNE-BL I/O 3,5-30/LED-SET

Parameters

Detailed information on fieldbus-dependent parameterisation of the modules is contained in the chapter "Parameters of the piconet® I/O modules" of the following manuals:

„ Profibus-DP

German: „piconet® for PROFIBUS-DP“, D300775 English: „piconet® for PROFIBUS-DP", D300776

„ DeviceNet Not yet published

„ CANopen Not yet published

Diagnosis

Diagnostics via LEDs

Please read the description of the diagnostic LEDs in the event of local errors of the coupling and extension modules in Chapter 5 of this manual: Fieldbus-specific diagnostic indications via LEDs are described in the chapter "Error treatment and diagnostics" of the above mentioned manuals.

Diagnostics via software

Detailed information on fieldbus-dependent diagnostics of the modules is contained in the chapter "Error treatment and diagnostics" of the above mentioned manuals.

D300778 0613 - piconet® I/O Modules 10-1

Dalam dokumen PDF www.turckbanner.my (Halaman 111-135)

Dokumen terkait