D300778 0613 - piconet® I/O Modules 9-1
Type overview
The device type Sxxx-0800D-xxxx is designed for connection of 4 binary switches or sensors as well as 4 binary actuators. The devices come as stand-alone or extension modules and differ in their connection technology, the input filter speed and the various admissible output current ratings.
Table 39:
Type overview digital Combined modules
Sxxx-0404D-x00x Description Connection technology Sxxx-0404D-x003,
Page 9-3
– 4 digital inputs, 24 V DC, filter 3.0 ms – 4 digital outputs
24 V DC, Imax = 0.5 A M8
Sxxx-0404D-x004, Page 9-3
M12
Sxxx-0404D-x001, Page 9-3
– 4 digital inputs, 24 V DC, filter 0,2 ms – 4 digital outputs
24 V DC, Imax = 0.5 A M8
Sxxx-0404D-x002, Page 9-3
M12
Sxxx-0404D-x007, Page 9-9
– 4 digital inputs, 24 V DC, filter 3.0 ms – 4 digital outputs,
24 V DC, Imax = 2 A (IΣ = 4 A)
M8
Sxxx-0404D-x008, Page 9-9
M12
Sxxx-0404D-x005, Page 9-9
– 4 digital inputs, 24 V DC, filter 0,2 ms – 4 digital outputs,
24 V DC, Imax = 2 A (IΣ = 4 A)
M8
Sxxx-0404D-x006, Page 9-9
M12
Sxxx-0808D-x001, Page 9-15
– 8 digital inputs, 24 V DC, filter 3.0 ms
M8
D300778 0613 - piconet® I/O Modules 9-3 Sxxx-0404D-x003/-x004/-x001/-x002, 4-port digital input; 4-
port digital output
Sxxx-0404D-x003/-x004/-x001/-x002, 4-port digital input;
4-port digital output
These digital I/O modules combine 4 digital inputs with an input filter of 3.0 ms or 0.2 ms and 4 digital 24 V DC outputs in a single device.
The outputs are suited for load currents of 0.5 A; they are short- circuit-proof and reverse-polarity protected.
The signal status can be indicated separately for each channel via LEDs.
The inputs are located on the upper half of the modules. With M8 connection technology modules, these are the upper four connectors (C0 to C3), and with the M12 technology modules the two upper connectors (C0, C1) with two inputs on one connector.
Figure 37:
SDPB-0404D-x00x SNNE-0404D-000x
26,5
C0
C1 C3 C5 C7
C2 C4 C6
168
23
175
30 C0 C1 C2 C3
33 33
C0
C1 C3 C5 C7
C2 C4 C6
119
23
126
30 C0 C1 C2 C3
26,5 33
D300778 0613 - piconet® I/O Modules 9-5 Sxxx-0404D-x003/-x004/-x001/-x002, 4-port digital input; 4-
port digital output
Technical data Table 40:
Technical data
Designation Sxxx-0404D-x003, -x004,
-x001, -x002 Voltage supply
Operating voltage UB 24 VDC (- 15 %/+ 20 %) Load voltage UL 24 VDC (- 15 %/+ 20 %) Inputs
Number of inputs 4, according to EN 61131-2
Input voltage 24 VDC (-15%/+ 20%)
Supply current 500 mA, short-circuit protected
Input filter 0.2 ms or 3.0 ms
Max. input current < 7 mA
Switching point 0/1 -3... 5 V / 11...30 V, 6 mA input current (EN 61131-2, type 2)
Sensor supply from operating voltage UB, max.
0.5 A per module,
common short-circuit protection Outputs
Number of outputs 4, according to EN 61131-2
Output voltage 24 VDC (-15%/+ 20%)
Output current per channel max. 0.5 A per channel,
individually short-circuit protected
Load type ohmic, inductive, lamp load
Short-circuit current typically 1.5 A (cyclic) Switching frequency 500 Hz
Simultaneity factor 1
Wiring diagrams Figure 38:
Connection to M8
Inputs:
3 4
1 () ( ) (+)
Outputs:
3 4
1 ()
(+) + 24 VDC Current consumption Load voltage
20 mA. typ.
Bits in the process image 4 input or 4 output bits
Potential isolation – Channels/Operating voltage: no – Between the channels: no – Operating voltage/fieldbus: yes
Figure 39:
Connection to the M12
Inputs:
() ( ) (+) () ( ) (+) 4
1 3
2
5
outputs:
() (+)
4
1 3
2
5 ()
(+)
D300778 0613 - piconet® I/O Modules 9-7
Sxxx-0404D-x003/-x004/-x001/-x002, 4-port digital input; 4- port digital output
Parameters
Detailed information on fieldbus-dependent parameterisation of the modules is contained in the chapter "Parameters of the piconet® I/O modules" of the following manuals:
Profibus-DP
German: „piconet® for PROFIBUS-DP“, D300775 English: „piconet® for PROFIBUS-DP“, D300776
DeviceNet Not yet published
CANopen Not yet published
Diagnosis
Diagnostics via LEDs
Please read the description of the diagnostic LEDs in the event of local errors of the coupling and extension modules in Chapter 5 of this manual: Fieldbus-specific diagnostic indications via LEDs are described in the chapter "Error treatment and diagnostics" of the above mentioned manuals.
Diagnostics via software
Detailed information on fieldbus-dependent diagnostics of the modules is contained in the chapter "Error treatment and diagnostics" of the above mentioned manuals.
D300778 0613 - piconet® I/O Modules 9-9 Sxxx-0404D-x007/-x008/-x005/-x006, 4-port digital input; 4-
port digital output
Sxxx-0404D-x007/-x008/-x005/-x006, 4-port digital input; 4-port digital output
These digital I/O modules combine 4 digital inputs with an input filter of 3.0 ms or 0.2 ms and 4 digital 24 V DC outputs in a single device.
The 8 outputs process load currents of up to 2 A each; the maximum total current is limited to IΣ = 4 A.
The outputs are short-circuit and reverse-polarity protected.
The signal status can be indicated separately for each channel via LEDs.
The inputs are located on the upper half of the modules. With M8 connection technology modules, these are the upper four connectors (C0 to C3), and with the M12 technology modules the two upper connectors (C0, C1) with two inputs on one connector.
Figure 40:
SDPB-0404D-x00x SNNE-0404D-000x
26,5
C0
C1 C3 C5 C7
C2 C4 C6
168
23
175
30 C0 C1 C2 C3
33 33
C0
C1 C3 C5 C7
C2 C4 C6
119
23
126
30 C0 C1 C2 C3
26,5 33
D300778 0613 - piconet® I/O Modules 9-11 Sxxx-0404D-x007/-x008/-x005/-x006, 4-port digital input; 4-
port digital output
Technical data Table 41:
Technical data
Designation Sxxx-0404D-x007/ -x008/
-x005/ -x006 Voltage supply
Operating voltage UB 24 VDC (- 15 %/+ 20 %) Load voltage UL 24 VDC (- 15 %/+ 20 %) Inputs
Number of inputs 4, according to EN 61131-2
Input voltage 24 VDC (-15%/+ 20%)
Supply current 500 mA, short-circuit protected
Input filter 3.0 ms and 0.2 ms
Max. input current < 7 mA
Switching point 0/1 -3... 5 V / 11...30 V, 6 mA Input current
(EN 61131-2, type 2)
Sensor supply from operating voltage UB, max.
0.5 A per module,
common short-circuit protection Outputs
Number of outputs 4, according to EN 61131-2
Output voltage 24 VDC (-15%/+ 20%)
Output current per channel max. 2 A per channel; IΣ = 4 A;
individually short-circuit protected
Load type ohmic, inductive, lamp load
Short-circuit current typically 1.5 A (cyclic) Switching frequency 500 Hz
Simultaneity factor 1
Wiring diagrams Figure 41:
Connection to M8
Inputs:
3 4
1 () ( ) (+)
Outputs:
3 4
1 ()
(+) + 24 VDC Current consumption Load voltage
20 mA. typ.
Bits in the process image 4 input or 4 output bits
Potential isolation – Channels/Operating voltage: no – Between the channels: no – Operating voltage/fieldbus: yes
Figure 42:
Connection to the M12
Inputs:
() ( ) (+) () ( ) (+) 4
1 3
2
5
outputs:
() (+)
4
1 3
2
5 ()
(+)
D300778 0613 - piconet® I/O Modules 9-13
Sxxx-0404D-x007/-x008/-x005/-x006, 4-port digital input; 4- port digital output
Parameters
Detailed information on fieldbus-dependent parameterisation of the modules is contained in the chapter "Parameters of the piconet® I/O modules" of the following manuals:
Profibus-DP
German: „piconet® for PROFIBUS-DP“, D300775 English: „piconet® for PROFIBUS-DP“, D300776
DeviceNet Not yet published
CANopen Not yet published
Diagnosis
Diagnostics via LEDs
Please read the description of the diagnostic LEDs in the event of local errors of the coupling and extension modules in Chapter 5 of this manual: Fieldbus-specific diagnostic indications via LEDs are described in the chapter "Error treatment and diagnostics" of the above mentioned manuals.
Diagnostics via software
Detailed information on fieldbus-dependent diagnostics of the modules is contained in the chapter "Error treatment and diagnostics" of the above mentioned manuals.
D300778 0613 - piconet® I/O Modules 9-15 Sxxx-0008D-x001, 8-port digital combined module
Sxxx-0008D-x001, 8-port digital combined module
The device type Sxxx-0800D is designed for connection of 8 binary switches or sensors and 8 binary actuators.
These digital I/O modules provide 8 digital inputs with an input filter of 3.0 ms or alternatively 8 digital 24 V DC outputs.
A maximum current of 0.5 A per actuator is permitted. The outputs are short-circuit and reverse-polarity protected.
An LED is assigned to each input and output for switching status indications.
Figure 43:
SDPB-0808D-x001 SNNE-0808D-0001
26,5
168
23
175
30 C0
C1 C3 C5 C7
C2 C4 C6 33 33
26,5 33
119
23
126
30 C0 C2 C4 C6
C1 C3 C5 C7
D300778 0613 - piconet® I/O Modules 9-17 Sxxx-0008D-x001, 8-port digital combined module
Technical data Table 42:
Technical data
Designation Sxxx-0808D-x001
Voltage supply
Operating voltage UB 24 VDC (- 15 %/+ 20 %) Load voltage UL 24 VDC (- 15 %/+ 20 %) Inputs
Number of inputs 8, according to EN 61131-2
Input voltage 24 VDC (-15%/+ 20%)
Supply current 500 mA, short-circuit protected
Input filter 3.0 ms
Max. input current < 7 mA
Switching point 0/1 -3... 5 V / 11...30 V, 6 mA input current (EN 61131-2, type 2) Sensor supply from operating voltage UB,
max. 0.5 A per module,
common short-circuit protection Outputs
Number of outputs 8, according to EN 61131-2
Output voltage 24 VDC (-15%/+ 20%)
Output current per channel 0.5 A max.
individually short-circuit protected
Load type ohmic, inductive, lamp load
Short-circuit current typically 1.5 A (cyclic) Switching frequency 500 Hz
Simultaneity factor 1
Wiring diagrams Figure 44:
Connection to M8
Inputs:
ç C0...C7 3
4 1 2
()( ) (+)
Outputs:
ç C0...C7 3
4 1 2
() (+)
Current consumption Load voltage
20 mA. typ.
Bits in the process image 8 input or 8 output bits
Potential isolation – Channels/Operating voltage: no – Between the channels: no – Operating voltage/fieldbus: yes
D300778 0613 - piconet® I/O Modules 9-19 Sxxx-0008D-x001, 8-port digital combined module
Parameters
Detailed information on fieldbus-dependent parameterisation of the modules is contained in the chapter "Parameters of the piconet® I/O modules" of the following manuals:
Profibus-DP
German: „piconet® for PROFIBUS-DP“, D300775 English: „piconet® for PROFIBUS-DP", D300776
DeviceNet Not yet published
CANopen Not yet published
Diagnosis
Diagnostics via LEDs
Please read the description of the diagnostic LEDs in the event of local errors of the coupling and extension modules in Chapter 5 of this manual: Fieldbus-specific diagnostic indications via LEDs are described in the chapter "Error treatment and diagnostics" of the above mentioned manuals.
Diagnostics via software
Detailed information on fieldbus-dependent diagnostics of the modules is contained in the chapter "Error treatment and diagnostics" of the above mentioned manuals.
SNNE-0808D-0003, 8-port digital combined module with IP20 terminals The digital combi module SNNE-0808D-0003 has 16 channels with 8 inputs and 8 outputs.
The device can therefore be flexibly adapted to the requirements of the application.
The outputs handle load currents of up to 0.5 A. They are short- circuit-proof and protected against inverse polarity.
IP20 terminal tension spring connectors are used for the signal connection. These connectors are optionally available with 1 or 3 rows.
Note
The IP20 terminal tension spring connectors (1-row: SNNE-BL I/O 3,5-10/LED-SET, Ident.-No. 6824475 and 3-rows SNNE-BL I/O 3,5- 30/LED-SET, Ident.-Nr. 6824474) are not supplied with the module but can be ordered seperately.
Figure 45:
SNNE-0808D-0003
26,5 33
119
23
126
30 44
C0 C1
D300778 0613 - piconet® I/O Modules 9-21 SNNE-0808D-0003, 8-port digital combined module with IP20
terminals
Technical Data Table 43:
Technical data
Designation SNNE-0808D-0003
Voltage supply
Operating voltage UB 24 VDC (- 15 %/+ 20 %) Load voltage UL 24 VDC (- 15 %/+ 20 %) Inputs
Number of inputs 8, according to EN 61131-2
Input voltage 24 VDC (-15 %/+ 20 %)
Supply current 500 mA, short-circuit protected
Input filter 3.0 ms
Max. input current < 7 mA
Input type 3-wire pnp sensors
Switching point 0/1 -3... 5 V / 11...30 V, 6 mA input current (EN 61131-2, type 2) Sensor supply from operating voltage UB,
max. 0.5 A per module,
common short-circuit protection Connection technology terminals with spring connectors Outputs
Number of outputs 8, according to EN 61131-2
Output voltage 24 VDC (-15 %/+ 20 %)
Output current per channel 0.5 A max.
individually short-circuit protected
Load type ohmic, inductive, lamp load
Short-circuit current typically 1.5 A (cyclic) Switching frequency 500 Hz
Simultaneity factor 1 Current consumption
Load voltage
20 mA. typ.
Connection technology terminals with spring connectors Bits in the process image 8 input or 8 output bits
Potential isolation – Channels/Operating voltage: no – Between the channels: no – Operating voltage/fieldbus: yes
D300778 0613 - piconet® I/O Modules 9-23 SNNE-0808D-0003, 8-port digital combined module with IP20
terminals
Wiring diagrams Figure 46:
Connection IP20 terminals
Inputs:
+ 24 V (RD) P1 (GY) P2 (GY) P3 (GY) P4 (GY) P5 (GY) P6 (GY) P7 (GY) P8 (GY) 0 V(BU) + 24 V (RD)
P1 (GY) P2 (GY) P3 (GY) P4 (GY) P5 (GY) P6 (GY) P7 (GY) P8 (GY)
SNNE-BL I/O 3,5-10/LED-SET SNNE-BL I/O 3,5-30/LED-SET
Outputs:
+ 24 V (RD) + P1 (GY) + P2 (GY) + P3 (GY) + P4 (GY) + P5 (GY) + P6 (GY) + P7 (GY) + P8 (GY) 0 V(BU) +P1 (GY)
+P2 (GY) +P3 (GY) +P4 (GY) +P5 (GY) +P6 (GY) +P7 (GY) +P8 (GY) 0 V(BU)
SNNE-BL I/O 3,5-10/LED-SET SNNE-BL I/O 3,5-30/LED-SET
Parameters
Detailed information on fieldbus-dependent parameterisation of the modules is contained in the chapter "Parameters of the piconet® I/O modules" of the following manuals:
Profibus-DP
German: „piconet® for PROFIBUS-DP“, D300775 English: „piconet® for PROFIBUS-DP", D300776
DeviceNet Not yet published
CANopen Not yet published
Diagnosis
Diagnostics via LEDs
Please read the description of the diagnostic LEDs in the event of local errors of the coupling and extension modules in Chapter 5 of this manual: Fieldbus-specific diagnostic indications via LEDs are described in the chapter "Error treatment and diagnostics" of the above mentioned manuals.
Diagnostics via software
Detailed information on fieldbus-dependent diagnostics of the modules is contained in the chapter "Error treatment and diagnostics" of the above mentioned manuals.
D300778 0613 - piconet® I/O Modules 10-1