DIVISION V-FIRE DIVISION V-FIRE SAFETY AND FIRE RESISTANCE
PART 22-LOCATION PART 22-LOCATION AND PROTECTION OF OPENINGS
22.1 Application. This Part shall apply to every building except
a
building of Class I or ClassX.
22.2 Qpening Defined.
For
the purpose of thisPart an
openingin an
external wall includes-(a)
a doorway;(b) a window or other glazed area, whether fixed or openable;
and
(c) any part
of
the wall, such as a panel-filled part, that does not have the relevant fire-resistance rating specified byPart
16 or other provision in these By-laws for the structural partsof
the wall.As amended by Order in Council published Gazette 15 May 1982, pp. 335-399.
22.3 Vertical Separation of Openings in External Walls, ( I ) Application
of
By-law. This By-law shall apply to buildings requiredto
be of Type 1 and Type 2 construction, but shall not extend to-(a) a building
or
portionof a
building designed, constructed or adapted asan
open-deck parking station; or(b) openings above one another within a stairway.
(2) Alternative Methods of Separation. Where any part of an opening in
an external
wall is situated vertically above another opening in the storey next below, there shall be provided between those openings-(a)
a spandrelor
other vertical construction not less than 900mm
in height and complying with the following con&tions:-- (i) The construction shall extendnot
less than 600mm
abovethe upper surface of the intervening floor.
BUILDING ACT 1975-1 984
(ii) The construction shall comprise non-combustibIe material having the relevant fire-resistance rating prescribed for external walls by By-law 16,7 (where required to be of Type 1 construction) or By-law 16.8 (where required to be of Type 2 construction).
(iii)
There
shall be no voids between the edge of the floor and the inside face of the spandrel or other vertical construction, as the casemay
be;or
(b)
a
slab or other horizontal construction that:(i) projects outwards from the face of the wall for a distance of not less than 1 100
mm;
(ii) extends along the wall not
less
than 450mm
beyond the lateral limitsof
the openings concerned; and(iii)
is
non-combustibleand has
a fire-resistance rating of not less than one hour.(3)
Combined vertical-horizontal separation. The following variations from the provisions set out in subclause(2) shall
be permissible:-(a)
It shalt not be necessary for the slab or other horizontal construction to comply with paragraph (b) of subclause(2)
ifa
combination of the followingdimensions produces
an overall dimension ofnot
less than2 200 mm:-
(i) The horizontal dimension fkom the plane
of
theopening
in the lower storey to the outside edge of the slabor
other horizontal construction. If the plane of the opening in the lower storey is behind the plane of the opening above, themeasurement
shall be takenas
though the lower opening were in the same planeas
thatof
the opening above.(ii) The vertical dimension,
measured
fiom the level of the top of the opening in the lower storey (or from any partof
the slab or other horizontal construction which extends below that level)to
the bottom level of the opening in the upper storey (or to any part of the slab or other horizontal construction which extends above that level).If such
vertical dimension is bss than 300mm,
it shall not be countedin
the calculations,(iii)
The
horizontal dimension from the outside edgeof
the slab or other horizontal construction to the plane of the openingin the
upper storey.(b)
It
shall not be necessaryfor the
construction at any side of the two openingsto
comply with paragraph (b) (ii) of subclause (2) if-(i) the constmction
is
provided with a vertical upstand ator
beyond the lateral limits of thetwo
openings;(ii) the height of the vertical upstand
is
not less than300 mm;
and
BUILDING ACT 1975-1 984 22.4 183
(5)
the combination of the height of the vertical upstand plus twice the distance, if any, by which the construction extends beyond the lateral limits of the two openings producesan
overall dimension of not less than 900 mm.(4) Approval of other construction. Notwithstanding anything to the contrary in this By-law, the Local Authority may,
in
lieu of requiring compliance with the foregoing provisions, approve theuse in an
external wall of a form of construction which-(a)
comprises
non-combustible material havinga fire-resistance
rating of not less thanone
hour; and(b) is capable,
in
the opinionof
the Local Authority, of inhibiting the spreadof fire from
storey to storey via openings in the wall either betteror as
effectuallyas
construction complying with subclause(2)
or (3).22.4 Protection of Openings in External Walls. ( 1 ) Where Protection Required.
In a fire
zone, the following openin s inan
external wall shall be protected in accordance with subclause (27:-(a)
An opening that faces and is less than 6m from
the farther boundaryof
a road adjoining the allotment of land, other than one located ina
storey at ornear ground
Ievel.(b) An opening that
faces and is
less than 3m
from the boundaryof
the allotmentof land
(not beinga boundary
to a road).(ba) An opening
in
that portionof
a wall prescribed in paragraph (b)of
subclause (3a) of By-law 23.1.(2) Protection Required. The protection referred to in subclause (1) shall be
as
follows:-(a) Doorways-one-hour
fire
doors (self-closing or automatic).(b) Windows and
other
glazed areas-one-hour fire windows(automatic or
permanently fixedin
closed position)or one-
hour automatic
fire
shutters.(c) Other
openings-construction
having a fire-resistance ratingof
notless
than onehour.
22.5 Limitations of Openings in External Walls. Openings between successive
floors in an
external wall referred to in By-law .22.4 shall not occupy more than one-thirdof
the area of the wall between those floors, except where the openings face a publicroad
andare
located ina
storey at ground level.22.6 Openings in Fire Walls. ( 1 ) Permissible Openings. No opening shall be permitted in
a
fire wall except-(a) doorways protected
in
accordance with this By-law;or
(b)openings
for services installedor protected
in accordancewith By-law 22.13.
184 22.7 BUILDING ACT 1975-1 984
(2) Protection of doorways. A doorway in a fire wall shall be protected by one of the following alternative methods:-
(a)
Two fire doors or fire shutters,one
on each side of the doorway, each of which shall-(i) have a fire-resistance rating of not less than half that
required
by Part 16 for the fire wall; and(ii) is self-closing, or automatic if the automatic closing device is so designed as to operate in the event of fire in a section
on
either side of thefire
wall;or
(b) A
fire
door on one side anda
fire shutteron
the other side of the doorway, each of which shall comply with sub- paragraphs (i) and (ii) of paragraph (a); or(c) A
singJe fire
door or fire shutter which-(i) has
a
fire-resistance rating of not less than that required by Pafi 16 for the fire wall;and
(ii) is self-closing, or automatic if the automatic closing device is
so
designed as to o erate in the event of fire ina section on
either sideo f
the fire wall.(3) Limitation on Doorway Openings. The aggregate width o f openings for doorways in
a
fire wall shall not exceed one-half of the length of the fire wall concerned.22.7 Doorways in Fie-isolated Stairways, Passageways, and Ramps.
Every doorway that opens to a fire-isolated stairway, fire-isdated passageway, or fire-isolated ramp (not being
a
doorway opening to a road or open space) shall be protected bya
self-closingone-hour
fire door.22.8 Openings in Fire-isolated Lift Shafts. (1) Doorways. Where, pursuant to Part 23, a lift shaft
is
required to be fire-isolated, theentrance
doorways to that shaft shall be protected by one-hour fire doors that-(a)
comply with the provisions of AS 1735, SAA Lift Code, reiating to fire-rated Iift landing doors;and
(b) are set to remain in the closed position at all times except where they
are
required to be open for the reception or discharge of passengers, goods or vehicles.(2) Lift Indicator Panels, etc. Lift call panels, indicator panels and other panels in the walls of a fire-isolated Iift shaA shall, if they exceed 32.5 x 103 m m * in area, be backed by construction having
a
fire- resistance rating of not less than one hour.As amended by Order in Council published Gazette 15 May 1982, pp. 335-399.
22.9 Doorways in Buildings of Class I1 or 111. ( I ) Doorways to Public Corridors, Etc. In a building of Class I1 or Class 111, every
BUILDING ACT 1975- 1984 22.10 18.5
doonvay providing access from a sole-occupancy unit or
a
room not withina
sole-occupancy unit to-(a)
a
public corridor, public hallway, or the like; or(b) the landing of an internal non-fire-isolated stairway serving
as
a required exit,shall be protected in accordance with subclause (3).
(2) Doorways Between Sole-Occupancy units, etc. In a building of Class
II
or Class I11 a doorway providing access from a sole-occupancy unit to another sole-occupancy unit or to a room not withina
sole- occupancy unit shall be protected in accordance with subclause (3).(3) Protection Required. The protection required by subcIauses (1) and (2) shall be as follows:-
(a) In a building
of
Type 1 or Type 2 construction-a self- closing one-hour fire door.(b) In a building
of
Type 3, 4 or5
construction-a self-closing, tight-fitting, solid core door, not less than35 mm
thick.22.10 Entrance Doorways of Class IV Buildings. The doorway of
a
Class IV portion ofa
building providing access to any internal portion of the building not within the Class IV portion shaIl he protected as follows:-(a) In
a
buildingof
Type 1 or Type 2 construction-a self- closing one-hour fire door.(b) In a building of Type 3, 4 or
5
construction-a self-closing, tight-fitting, solid core door, not less than35 mm
thick.As amended by Order in Council published Gazette 15 May 1982, pp. 335-399.
22.11
* * * *
Substituted by Order in Council published Gazette 15 May 1982, pp. 335-399.
22.11s Openings in Floors for Certain Services. ( I ) Metal Pipes, etc. In
a
building of Type 1 or Type 2 construction, services associated with the functioningof a
building and passing through a floor shall either be in individual metal pipes, metal conduits, metal ducts,or
the like,or
be installed in shafts complying with Part 16.(2) PVC Pipes, etc, in certain cases. Notwithstanding the provisions of subclause (1)
hereof
ina
building of Type 1 or Type 2 construction, plumbing services associated with the functioningof
the building and passing througha
floormay
be in polyvinyl chloride pipes and fittings provided-(a) the building contains not more than 2 storeys and compIies with the provisions
of
Part 19; or(b) the floors passed through are those between sanitary compartments which-
(i) are
separated
fromother
portions of the buildingas
though they were ventilating, pipe, garbage, or like shafts, notBUILDING ACT 1975-1 984
intended for the discharge of hot products of combustion;
and
(ii) have all doorways opening therefrom protected by self- closing one-hour fire doors,
and the openings for those polyvinyl chloride pipes and fittings comply with the provisions of clause 22.13 relating to openings
for
metal pipes, metal conduits, or the like.Inserted by Order in Council published Gazette 15 May 1982, pp. 335-399.
22.12 Openings to Shafts, Etc. (1) Protection in Type 1 and 2 Construction.
In
a building of Type 1 or Type 2 construction, an opening in a wall providing access to a ventilating, pipe, garbage, or other service shaft shall, except as provided in subclause (2), be protected by-(a)
a
self-closing one-hour fire door; or(b) an access panel having a fire-resistance rating of not less than one hour; or
(c) one of the devices referred to in paragraphs (a) and (b or
shaft is
a
garbage shaft,f'
by a door or hopper of non-combustibIe construction
i
the (2) En Sanitary Compartments. An opening referred to in subclause (1) shall not be subject to that subclause if it IS-(a)
located within a sanitary compartment; and(b) provided with a door or panel which, together with its frame, is nan-combustible or has a fire-resistance rating of not less than one-half hour.
22.13 Openings for Service Installations. (1) Application of By-law. This By-law shall apply to openings through a wall, floor, or ceiling that
is
required to have a fire-resistance rating or a resistance tothe
incipient spread of fire.(2) Pipes and Conduits. Individual openings
for metal
pipes, metal conduits, or the like, conveying-(a) wires or cables for electrical or telephone services; or (b) gas, including liquefied petroleum gas; or
(c) other . . services associated with the functioning of the building, shall be no larger than is necessary to permit of their installation and all gaps
around
them shall be packed or otherwise treated to the full thickness of the wall, floor, or ceiling, as the case requires, so that its fire-resisting performance will not be impaired.(3) Wiring Not in PSpes, etc. Wires
or
cables for electrical, telephone, or other services that-(a) are not enclosed in metal pipes, metal conduits, or other non-combustible material; and
(b) are installed within
or
pass througha
wall,floor, or
ceiling, shall be installed accordingto
Part 55, including any relevant provisions of that Part for the protection of openings made for those services.BUILDING ACT 1975- 1 984 22.13a 187
(4) Ventiiating and Air-Conditioning Ducts. Openings for ventilating or air-conditioning ducts or other equipment shall be protected as required by
Part
55 (Specification No. 7).( 5 ) Other Services. Openings for other services not mentioned in subclauses f2), (3), and (4) shall be protected in an approved manner.
22.13a Other Openings.
Openings
in floors, walls, and roofs, not provided for elsewherein
these By-laws, shall be protected in an approved manner to resist effectively the spread of fire and the products of combustion, and shall beof
such approved dimensions and constructionas
notto
endanger persons using the building.DlVISION V-FIRE SAFETY AND FIRE-RESISTANCE