Perhitungan Beban Panas dan Selisih Temperatur Kondensor

N/A
N/A
Novita Ramadani

Academic year: 2024

Membagikan "Perhitungan Beban Panas dan Selisih Temperatur Kondensor"

Copied!
11
0
0

Teks penuh

(1)

Condensor-01 (CD-01)

Fungsi : Untuk mengembunkan top produk Kolom Destilasi-01 (KD-01) Type : Shell and Tube Heat Exchanger

Gambar :

Fluida Panas : Produk Kolom Destilasi-01 (KD-01) T1 = 72,7240 0C = 162,9032 0F

T2 = 69,2180 0C = 156,5924 0F

W = 54728,1204 kg/jam = 120652,8228 lb/jam Fluida Dingin : Amoniak

t1 = -33 0C = -27,4 0F t2 = -33 0C = -27,4 0F

W = 41869,059 kg/jam = 92303,922 lb/jam

Perhitungan berdasarkan “Process Heat Transfer’, D Q. Kern.

1. Beban Panas Condensor, Q Q = 59650906,9885 kJ/jam

= 56538142,9881 Btu/jam

(2)

2. Menghitung selisih temperatur rata-rata (∆T = LMTD)

No Fluida Panas Keterangan Fluida Dingin Selisih 1 162,9032 0F Temperatur Tinggi -27,4 0F 190,3032 0F 2 156,5924 0F Temperatur Rendah -27,4 0F 183,9924 0F

Selisih 0 6,3108

LMTD =

1 2

1 2

t t ln

t t

 

= ln 190,3032183,9924 3108

, 6

= 187,1301 0F

Ta = ½ (162,9032 + 156,5924) 0F = 159,7478 0F ta = ½ (-27,4 + -27,4) 0F = -27,4 0F 3. Trial UD

Untuk light organics

UD = 40 – 100 Btu/ jam ft2 0F (Tabel 8, Kern) Asumsi : UD = 100 Btu/jam ft2 0F

a. Area perpindahan panas (surface area), A A = UQ t

D

A = 56538142,9100187,1301881 , = 3021,3287 ft2

Karena surface area A > 200 ft2, maka direncanakan menggunakan Shell and Tube Heat Exchanger dengan spesifikasi : (Tabel 10, Kern)

(3)

 Panjang tube = 24 ft

 Outside Diameter = 1 inchi

 BWG = 16

 Pass = 4

 PT, pitch = 1,25 in triangular pitch

 a” = 0,26185 ft

4. Menghitung Jumlah tube, Nt

Nt =

L.a"

A

=243021,3278ft x 0,2618 ft ft

2

= 480,8583

Ambil Nt pada tabel 9 Kern (hal. 842) yang mendekati, sesuai dengan ukuran tube yang telah dipilih, Nt = 486

5. Koreksi design overall coefficient of heat transfer, UD

A = Nt.L.a”

= 486 x 24 ft x 0,2618 ft

= 3053,6352 ft2 UD=

T A.

Q

= 3053,6352ft x 187,1301 F Btu/jam

881 56538142,9

o 2

= 98,942 Btu/jam ft2 oF

(4)

Karena UD mendekati asumsi, maka dari tabel 9 Kern diperoleh data sebagai berikut :

Shell Side :

ID = 33 in

PT = 1,25 in triangular pitch C” = (PT – OD tube)

= 1,25 in – 1 in = 0,25 in Baffle space = 0,5 x 33 in = 16,5 in Tube Side :

OD = 1 in

ID = 0,87 in

BWG = 16

Panjang = 24 ft

PT, pitch = 1,25 in triangular pitch

Pass = 4

TUBE SIDE : Fluida panas

1. Menghitung flow area fluida panas yang mengalir pada tube side, at

ao = 0,594 in2 (flow area per tube) at =

n . ft / in 144

a . N

2 2

o

t (Pers. 7.48, Kern)

= 144in /ft .4 in 0,594 x 486

2 2

2

(5)

= 0,5012 ft2

2. Menghitung laju alir massa fluida panas pada tube side, Gt

Gt = at

W (Pers. 7.1, Kern)

= 0,5012ft2

lb/jam 8 120652,822

= 240733,9025 lb/ft2 jam

3. Menghitung bilangan reynold fluida pada tube side, Ret

Pada temperatur rata-rata, tc = 159,7478 oF diperoleh data sebagai berikut : µ = 0,0313 cP = 0,0756 lb/ft hr

De= ID = 0,87 in = 0,0752 ft Cp = 0,9561 Btu/lb oF k = 0,0932 Btu/hr ft oF Ret= Gt x De

= 240733,9020,07565 lb/jamlb/ft fthr x 0,0752ft

2

= 230756,6837

Dengan menghitung reynold number maka diperoleh :

Heat transfer factor, JH = 380 (Fig. 24, Kern) 4. Menghitung koefisien perpindahan panas inside fluida, hio

hi =

14 , 0

w 1/3

H .

k Cp . D . k

J 



(Pers. 6.15a, Kern)

(6)

1

14 , 0

w





= .1

0,0932 9561 , 0 0756 , . 0 0,0752 0,0932 .

380

1/3

x

hi = 448,8969 Btu/ft2 jam oF

Nilai hi yang diperoleh digunakan untuk menghitung heat transfer coefficient outside diameter, hio

hio= hi x (ID/OD)

= 448,8969 Btu/ ft2 hr oF x (0,87/1)

= 390,5403 Btu/ft2 hr oF

SHELL SIDE :Fluida dingin

1. Menghitung flow area fluida dingin yang mengalir pada shell side, as

as =

P

T

x 144

B x C"

x ID

(Pers. 7.1, Kern)

= 33 x 1440,25 x 1,25 x 16,5

= 0,7563 ft2

2. Menghitung laju alir massa fluida dingin pada shell side, Gs

Gs= as

W

= 2

ft 0,7563

lb/jam 92303,922

(7)

= 159540,9226 lb/jam ft2

3. Menghitung bilangan reynold fluida pada shell side, Res

Pada temperatur rata-rata, Tc = -27,40 oF diperoleh data sebagai berikut : µ = 0,2415 cP = 0,5845 lb/ft jam

De= 0,72 in = 0,06 ft Cp = 1,2134 Btu/lb oF k = 0,3544 Btu/hr ft oF Res= Gs x De

= 0,5845lb/ft jam

ft 0,06 x ft lb/jam 6

159540,922 2

= 16376,4183

Dengan menghitung reynold number maka diperoleh :

Heat transfer factor, JH = 220 (Fig. 28, Kern)

4. Menghitung koefisien perpindahan panas, ho

ho=

14 , 0

w 1/3

H .

k c . D . k

J 



, (Pers.

6.15b, Kern)

1

14 , 0

w





= .1

3544 , 0

1,2134 x 5845 , . 0 06 , 0 0,3544 220.

3 / 1

ho = 1637,4908 Btu/ft2 jam oF

(8)

Uc=

o io

o io

h h

h x h

(Pers. 6.7, Kern)

= (390,5403Btu/ft jam F) (1637,4908 Btu/ft jam F) F) jam Btu/ft 908 F).(1637,4 jam

Btu/ft (390,5403

o 2 o

2

o 2 o

2

= 315,3335 Btu/ft2 jam oF 7. Menghitung dirt factor, Rd

Rd=

D C

D C

x U U

U U 

= (315,3335Btu/ft jam F) x (98,942Btu/ft jam F) F) jam Btu/ft (98,942 -

F) jam Btu/ft (315,3335

o 2 o

2

o 2 o

2

= 0,0069 jam ft2oF/Btu

PRESSURE DROP

TUBE SIDE : Fluida panas 1. Friction factor, f

Ret= 230756,6837

f = 0,0001 (Fig. 26, Kern)

s = 0,7391 2. Pressure drop

ΔPt =

x s x D x x10 22 , 5

n x L x G x f

t e

10 2 t

(Pers. 7.47, Kern)

= 5,22x10 x 0,0725 x 0,7391 x 1 4 x 24 x 5 240733,902 x

0,0001

10

2

(9)

= 0,2387 psi 3. Persamaan velocity head :

Gt = 2407333,9025 lb/ft2jam

Dari fig.27 Kern (hal. 837) dengan Gt = 2407333,9025 lb/ft2jam, maka V2/2g = 0,008 lb/ft2jam

Perubahan arah adanya penambahan pressure drop (ΔPt) disebut return loss dan dihitung untuk 4 velocity head per pass, maka return loss untuk beberapa fluida menjadi :

ΔPr = 4.ns x 2gv 0.73914.4 x 0,008 0.1732psi

2

Total tube side pressure drop (ΔPT) menjadi : ΔPT = ΔPt + ΔPr

= (0,2387 + 0,1732) psi

= 0,4119 psi

SHELL SIDE : Fluida dingin

Pressure drop yang terjadi pada shell sebanding dengan jumlah fluida yang melewati sekat (bundle) di antara baffle.

1. Friction factor, f Res= 16376,4183

f = 0,0012 (Fig. 29, Kern)

s = 0,6740 2. Jumlah lintasan

(10)

Jumlah sekat (bundle) yang dilalui (N+1), dimana N yaitu jumlah baffle dan L yaitu panjang tube

Nt + 1 = 12.LB 121,375 x 24ftft 209,4545 Ds=

12

ID 0,2292ft

12 ft 2,75

3. Persamaan isotermal untuk pressure drop fluida yang dipanaskan atau didinginkan dan termasuk yang diserap atau hilang yaitu :

ΔPs =

x s x D x x10 22 , 5

) 1 (N x D x G x f

s e

10

t s 2 s

(Pers. 7.44, Kern)

= 5,22x10 x 0,06 x 0,6740 x 1

) (209,4545 x

0,2292 x

6 159540,922 x

0,0012

10 2

= 0,6945 psi

SUMMARY

Nama Alat Condensor– 01

(11)

Kode CD-01

Operasi Kontinyu

Jumlah 1 Unit

Fungsi Untuk mengembunkan top produk Kolom Destilasi-01 (KD-01)

DATA DESAIN

Tipe Shell and Tube Heat Exchanger

Bahan Konstruksi Carbon Steel

Luas area 3053,6352 ft2

LMTD 187,1301 oF

UC 315,3335 Btu / hr. ft2oF

UD 98,942 Btu / hr. ft2oF

Rd 0,0069

Shell Tube

ho 1637,4908 Btu/jam ft2 hio 390,5403 Btu/jam ft2

∆P 0,6945 Psi ∆P 0,4119 Psi

Referensi

Dokumen terkait

Untuk mengetahui temperatur fluida panas dan fluida dingin yang keluar dari alat penukar kalor tabung sepusat dengan arah aliran sejajar, yakni yang terjadi di lapangan,

Proses perpindahan panas dapat terjadi dari benda ke benda lain yg mempunyai temperatur lebih rendah, dimana mekanisme proses perpindahan dapat terjadi dengan

Hasil pengujian terhadap campuran fluida radiator 80% air dan 20% radiator coolant menunjukkan rata – rata selisih temperatur inlet radiator dengan temperatur

Untuk perhitungan metode NTU diperoleh efektifitas APK terbesar adalah 96.56460 % pada temperatur fluida panas masuk (Th,i) 60 °C dan temperatur fluida dingin masuk (Tc,i)

Fenomena ini disebabkan oleh semakin meningkatnya beban panas (Q*) yang menyebabkan gradient temperatur pelat rerata semakin meningkat dengan temperatur sekeliling yang

Alat penukar panas adalah alat yang berfungsi untuk mengakomodasikan perpindahan panas dari fluida panas ke fluida dingin dengan adanya perbedaan temperatur, karena panas

Hal ini terjadi karena pada temperatur fluida masuk yang bersuhu tinggi yaitu 70°C terjadi proses pertukaran panas dengan temperatur udara luar (fluida pendingin)

Tujuan dari penelitian ini adalah mengetahui pengaruh beban pendinginan terhadap temperatur sistem pengkondisian udara hibrida dengan kondensor dummy tipe trombone coil menggunakan