ECE 476 – Power System Analysis Fall 2012

Homework 2

Reading: For lectures 4-6, read Chapter 4 from textbook. Sections 4.7, and 4.11-4.12 will not be covered in detail.

Due Date: Thursday September 13, 2012

Problem 1. In PowerWorld Simulator Problem 2.32 (see Figure 1 below) a 8 MW/4 Mvar load is supplied at 13.8 kV through a feeder with an impedance of (1+ j2) Ω. The load is compensated with a capacitor whose output, Qcap, can be varied in 0.5 Mvar steps between 0 and 10.0 Mvars. What value of Qcap minimizes the real power line losses? What value of Qcapminimizes the MVA power flow into the feeder?

Problem 2. A three-phase line, which has an impedance of (2 + j4) Ω per phase, feeds two balanced three- phase loads that are connected in parallel. One of the loads is Y-connected with an impedance of (30 + j40) Ω per phase, and the other is ∆-connected with an impedance of (60 – j45) Ω per phase. The line is energized at the sending end from a 60-Hz, three-phase, balanced voltage source of 120√

3 V (rms, line-to-line). Determine:

1. The current, real power, and reactive power delivered by the sending-end source.

2. The line-to-line voltage at the load.

3. The current per phase in each load.

4. The total three-phase real and reactive powers absorbed by each load and by the line.

Check that the total three-phase complex power delivered by the source equals the total three- phase power absorbed by the line and loads.

Problem 3. Two three-phase generators supply a three-phase load through separate three-phase lines. The load absorbs 30 kW at 0.8 power factor lagging. The line impedance is (1.4 + j1.6) Ω per phase between generator G1 and the load, and (0.8 + j1) Ω per phase between generator G2 and the load. If generator G1 supplies 15 kW at 0.8 power factor lagging, with a terminal voltage of 460 V line-to-line, determine:

1. The voltage at the load terminals.

2. The voltage at the terminals of generator G2.

3. The real and reactive power supplied by generator G2.

Assume balanced operation.

Figure 1: Screen for Problem 1.

Referensi

Dokumen terkait

The three phase shunt active power filter is used as a solution to mitigate harmonic disturbances which can interfere the power quality performance in electrical

In this paper, three-phase power flow for unbalance distribution system is carried out using Forward-Backward Propagation Technique.. The equivalent injection current method

With the availability of synchrophasor data measurement, it makes possible to establish the power system monitoring by directly employing spectral analysis of power or phase

Nomenclature ng Number of generators in the network nb Number of buses in the network nbr Number of branches in the network nl Number of loads in the network αk,βk,γk Generator k

Fig.4 Daily solar radiation profile In order to perform the reliability studies, three different cases are considered where all the generators synchronous and PV are subject to

It is equivalent to an adjustable voltage or current source that can be controlled by its amplitude and phase to change the reactive power delivered to the grid[7].A STATCOM positive

have studied the ability ofthe North American electric power grid to transfer power between generators and consumers when a percentage ofthe nodes ofthe networks, representing the

Price $/MWh Capacity MWh Critical Appliances & Passive users Non-dispatchable VREs & Baseloads dispatchable loads & generators The Power Pricing at a Competitive Wholesale