5.3.1 Winding short-circuit emulation
The transformer winding short-circuit scenario is emulated via installation of the
variable resistance rheostat in parallel to winding terminals. The maximum value of the
rheostat represents the open circuit scenario, since it significantly exceeds the winding
impedance and all the current coming from the source will flow the structure of the winding
(see Figure 5.2(a) [110] ©2019 IEEE). The open circuit scenario corresponds to the healthy
working mode of the transformer. In this work, the maximum value of the rheostat is 5 kΩ
and 5 MΩ for distribution and power transformers, respectively, and both values are high
enough to be compatible with windings’ total impedance. The worst-case scenario
corresponds to the full short-circuit of the transformer winding, where all the current
coming from the source flows through the rheostat as illustrated in Figure 5.2(b) [110]
Figure 5.3. Circuit representation of the winding short-circuit emulation The paralleled resistance is decreased with 500 Ω from highest (either 5 kΩ or 5 MΩ) to lowest (~Zero Ω) resistance. Generally, the relationship between input and output signal can be expressed in terms of the impedances as following:
V
out/V
in= Z
out/(Z
w+ Z
out) (54) V
out/V
in= Z
out/(Z
w|| Z
R+ Z
out) (55) where V
inand V
outrepresent the input and output voltages, correspondingly, Z
outis the cable impedance, Z
Ris the rheostat’s value, and Z
wrepresents the winding impedance. Therefore, it is observed that the transfer function becomes the function of the new equivalent impedance.
Figure 5.4 illustrates the behavior of the frequency response signature towards the different short-circuit scenarios, where 5 kΩ parallel resistance corresponds to the 0%
short-circuit (healthy state) and 1 Ω corresponds to 100% short-circuit (critical). One of the major observations is that the magnitude of the transfer function increases along with severity of the winding short-circuit, which results in flattening of the signature around the first anti-resonance point (depicted by blue vertical line in Figure 5.4 [110] ©2019 IEEE).
The first anti-resonant peak corresponds to the frequency at which the winding self- inductance L resonates with the equivalent capacitance C, represented via following expression [175]:
f
anti-resonance= 1/2π√LC (56)
Figure 5.4. FRA signatures for different short-circuit severities 5.3.2 Green-to-yellow decision boundary
The green-to-yellow decision boundary B
G|Ycorresponds to the transition point from healthy (green) to suspicious (yellow) working mode. In this work, the boundary B
G|Yrepresents the case where the short circuit current starts to flow in the system and is expressed in terms of the SIs values estimated from the corresponding FRA measurement.
For each iteration step, short-circuit monitoring and FRA signature measurement is conducted via experimental setup depicted in Figure 5.5(a)-(b), respectively [20] ©2022 IEEE.
(a) (b)
Figure 5.5. Practical setup for: (a) short-circuit current monitoring and (b) FRA test
The short circuit current monitoring results given in Table 6 [181] ©2022 IEEE
demonstrate the transition point (green colored) from green to yellow working mode. In
the next short-circuit scenario the current flowing through the rheostat becomes measurable
by the ammeter. Hence the following observations, in particular, T1-12V at 500 Ω, T1-
24V at 1.5 kΩ, T2-22V at 500 Ω, T2-42V at 1.5 kΩ, T3-24V at 500 Ω, and T3-36V at 1 kΩ, are considered as the green-to-yellow boundary B
G|Y. It was mentioned above, that for each fault scenario the FRA measurements are conducted to calculate 12 statistical indicators.
Table 7 [181] ©2022 IEEE illustrates the corresponding CC values for the scenarios presented in Table 6. Similarly, the green colored observations represent the critical CC value, i.e. the green-to-yellow B
G|Ydecision boundary. All collected B
G|Ysample points expressed by other statistical indicators are also estimated from the obtained FRA signatures and presented in the Appendix H.
Table 6 – Short-circuit current monitoring results for different fault scenarios
Rating Taps Winding % 5 kΩ 4.5 kΩ 4 kΩ 3.5 kΩ 3 kΩ 2.5 kΩ 2 kΩ 1.5 kΩ 1 kΩ 500 Ω 200 Ω 0 Ω
400 VA T1 12V 33.33% 0 0 0 0 0 0 0 0 0 0 0.034 -
T1 24V 66.67% 0 0 0 0 0 0 0 0 0.024 0.031 0.054 -
630 VA T2 22V 10.00% 0 0 0 0 0 0 0 0 0 0 0.022 -
T2 42V 19.10% 0 0 0 0 0 0 0 0 0.027 0.041 0.218 -
1 kVA T3 24V 10.90% 0 0 0 0 0 0 0 0 0 0 0.022 -
T3 36V 16.36% 0 0 0 0 0 0 0 0 0 0.027 0.215 -
Table 7 – Estimated CC values for the emulated fault scenarios
Rating Taps Winding % 5 kΩ 4.5 kΩ 4 kΩ 3.5 kΩ 3 kΩ 2.5 kΩ 2 kΩ 1.5 kΩ 1 kΩ 500 Ω 200 Ω 0 Ω 400 VA T1 12V 33.33% 0.9997 0.9997 0.9997 0.9998 0.9999 0.9997 0.9998 0.9997 0.9998 0.9997 0.9992 0.8983
T1 24V 66.67% 0.9999 0.9999 0.9999 0.9999 0.9999 0.9999 0.9998 0.9998 0.9995 0.9985 0.9939 0.8985 630 VA T2 22V 10.00% 1.0000 1.0000 0.9999 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 0.9998 0.9992 0.8296 T2 42V 19.10% 1.0000 1.0000 0.9997 0.9999 0.9999 0.9999 0.9999 0.9998 0.9996 0.9987 0.9953 0.7701 1 kVA T3 24V 10.90% 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 0.9999 0.9996 0.8472 T3 36V 16.36% 1.0000 1.0000 0.9999 0.9999 0.9999 0.9999 0.9999 0.9999 0.9997 0.9992 0.9966 0.7446