Iqbal Dinoer Aditama, 2016

Analisis Setting Relay Diferensial pada Trafo Tenaga 60 Mva di Gardu Induk Cigereleng 150 kV / 20 kV

Universitas Pendidikan Indonesia | repository.upi.edu | perpustakaan.upi.edu

ANALISIS SETTING RELAY DIFERENSIAL PADA TRAFO TENAGA 60

MVA DI GARDU INDUK CIGERELENG 150 kV / 20 kV

IQBAL DINOER ADITAMA

E5051.1100106

ABSTRAK

Penelitian ini bertempat di PT.PLN (PERSERO) Transmisi Jawa Bagian Tengah APP

Bandung dengan subjek yang diangkat adalah perhitungan setting relay diferensial pada

trafo tenaga 60 MVA di Gardu Induk Cigereleng 150 kV / 20 kV. Tujuan dari penelitian

ini adalah untuk mengetahui cara melakukan perhitungan setting relay diferensial pada

trafo tenaga 150 kV / 20 kV. Alasan dilaksanakannya penelitian ini adalah untuk

mengetahui hasil dari perhitungan setting relay diferensial sebelum diterapkan pada alat

relay diferensial, mengingat apabila salah dalam melakukan perhitungan setting relay

diferensial maka akan terjadi masalah pada trafo tenaga. Metode yang digunakan dalam

penelitian ini adalah menyimulasikannya hasil perhitungan setting relay diferensial

menggunakan software ETAP 12.6. Hasil yang di dapat dari penelitian ini untuk setting

relay diferensial sudah optimal dan dapat diterapkan. Karena, aat terjadi gangguan pada

dearah proteksi trafo tenaga, arus yang mengalir lebih besar dari arus setting maka relay

diferensial bekerja. Namun, saat terjadi gangguan diluar daerah proteksi trafo tenaga nilai

arus yang mengalir lebih kecil dari arus setting, maka relay diferensial tidak bekerja.

(2)

Iqbal Dinoer Aditama, 2016

Analisis Setting Relay Diferensial pada Trafo Tenaga 60 Mva di Gardu Induk Cigereleng 150 kV / 20 kV

Universitas Pendidikan Indonesia | repository.upi.edu | perpustakaan.upi.edu

ANALYSIS OF DIFFERENTIAL RELAY SETTING THE POWER TRANSFORMER 60 MVA IN SUBSTATION CIGERELENG 150 kV / 20

kV

IQBAL DINOER ADITAMA

E5051.1100106

ABSTRACT

This research took place at PT PLN (Persero) Central Java Transmission APP Bandung with the subject raised was the calculation of the differential relay setting 60 MVA power transformer in the substation Cigereleng 150 kV / 20 kV. The purpose of this research is to know how to perform calculations on a transformer differential relay setting power 150 kV / 20 kV. The reason the implementation of this research is to find out the results of the calculation of differential relay setting before it is applied to the differential relay apparatus, because until one in calculating the differential relay setting, there will be problems in the power transformer. The method used in this study is menyimulasikannya differential relay setting calculation results using ETAP software 12.6. The results obtained from this study for setting differential relay is optimal and can be applied. Because, aat an interruption in power transformer protection strip, the current that flows greater than the current setting of the differential relay work. However, when the interference occurs outside the area of protection of power transformer rated current that flows is smaller than the current setting, then the differential relay is not working.

Referensi

Dokumen terkait

Pada Gardu Induk 150 kV sumber AC dipasok dari Trafo pemakaian sendiri (PS) sedangkan pada GITET 500 kV, selain Trafo PS dilengkapi juga dengan Generator Set

ANALISIS KOORDINASI RELAI DIFERENSIAL DAN RELAI OCR-GFR PADA TRAFO 7 DI GARDU INDUK CIGERELENG.. Universitas Pendidikan Indonesia | repository.upi.edu | perpustakaan.upi.edu

4.1.4 Simulasi Setting Relay Diferensial terhadap Gangguan Internal dan Gangguan External pada Trafo Tenaga Menggunakan Software ETAP

ESTIMASI PEMBEBANAN TRANSFORMATOR GARDU INDUK GARUT 150 KV Universitas Pendidikan Indonesia | repository.upi.edu | perpustakaan.upi.edu..

Setelah dilakukan scanning koordinasi rele jarak pada penghanatar saluran transmisi 150 kV Gardu Induk Bandung Selatan ke GI didepannya, untuk koordinasi GI

Gardu Induk Sungguminasa terdapat satu buah trafo tenaga dengan tegangan kerja 150/20 kV. Dimana trafo tenaga tersebut berkapasitas 60 MVA. Karena pada trafo

1) Pada area trafo tenaga 1 Gardu Induk 150 KV Jepara Gangguan yang terjadi pada area trafo tenaga 1 di Gardu Induk 150 KV Jepara yang menyebabkan sistem proteksi

Keandalan relai jarak (Distance Relay) sebagai pengaman utama bay penghantar 150 kV Jember dan Banyuwangi di gardu induk Genteng salah satunya bergantung pada