Insulation Coordination
Fundamentals
Definition of Insulation Coordination
Simple Definition
Insulation coordination is the selection of the insulation strength of a system. (Hileman)
Better One
Insulation coordination is the process where the
insulation characteristics of all components of the power system are determined, specified and
coordinated to avoid failure due to expected internal and externally occurring surges. (Hileman)
Arrester
Insulator
Types of Insulation Coordination Studies
Transformer Protection
Substation Protection Open Air and GIS
Line Protection
Distribution and Transmission
Breaker Protection
Generator Protection
Determine clearances
Determine Separation Distances
Determine Arrester Energy and Voltage Ratings.
And on and on and on
Types of Insulation Coordination Studies
Deterministic
This is the conventional method where the minimum strength of the insulation is equal or greater than the maximum surge stresses.
. Transformer insulation is not
statistical in nature. It has
one lightning withstand
value and one switching
withstand value. Therefore
a deterministic analysis is all
that we can do.
Types of Insulation Coordination Studies
Probabilistic
This type of analysis consists of selecting the insulation level and clearances based on specific reliability criterion. Since the insulation strength of air is statistical in nature, we can only determine its probability of Flashover for a given surge.
Studies of transmission line performance is based on a flashover rate per year per 100km, and because the flashover
parameter is statistical, resulting levels are probabilistic.
Studies of substation performance is also probabilistic for the
same reason. For this type of study we base the performance
on MTBF (Mean Time Between Flashover). More later on this.
Types of Insulation Coordination Studies
Lightning Surge Studies
This type of study deals strictly with lightning surges and backflash over surges. Is completed for all system voltage levels.
Switching Surge Studies
This type of study is usually for systems above 240kV since it is this type of system that can produce switching surges of relevance.
If a lower voltage system has large cap banks, then a switching
study is justified.
Parameters of Importance in Studies
• Purpose of Study
• The Lightning Flash
• Ground Flash Density
• Shield Failure rate if known
• Types of Insulation
• BIL and CFO
• MTBS and MTBF
• Location and Altitude of Study
• Cable and Isophase specs
• Incoming Surge Steepness
• Backflash Rate (BFR)
• Calculating BFR
• Tower Configurations
• Circuit Physical Dimensions
• The Transformer Ratings and Capacitance
• The Arrester
• VI Curve
• Selecting the Rating
Purpose of Insulation Coordination Studies
Can be to design proper insulation and arrester location from scratch
Can be to validate chosen insulation levels
(Very common) Can be to determine where to locate arresters
Can be to determine cause of failure of equipment
(After an incident) Can be to determine the Width of a ROW
(Switching Study) Can be to provide assurance that equipment is protected properly
Can be to put in the file for future reference
Can be to fulfill a requirement
Can be to …………. and more……
Examples of Lightning Studies
Simple Substation from Chapter 12 of “Insulation Coordination of Power Systems”.
500kV Line-Substation-Generator
69kV Line Study
Breaker Disconnect
Switch
CT or CCVT
Station Arresters
Power
Transformer Overhead Shield Wire
Basic Substation Lightning Study
Incoming Surge
Surge at Trans
Complex Study
Complex Insulation Coordination Study
Incoming Line
Switchyard with no transformers
Cross over line to Generator
Station
3 generator step up Transformers
Three generators
69kV Sub
69kV Sub Transmission Line Study
69kV Sub Transmission Line Study
69kV Sub Transmission Line Study
Insulator that flashes over at a specific
voltage
Underbuilt Circuit
System Fundamentals Relative to Insulation Coordination
1. Insulation
2. Traveling Waves and Reflections, Backflash, and Separation Distance 3. Tower Grounds and
Station Grounds 4. Corona
5. Steepness of Surges 6. Clearances
7. Physical Dimensions 8. Ground Flash Density 9. OHGW
10. Ground Flash Density
External Insulation
The distance in open air or across the surfaces of solid
insulation in contact with open air that is subjected to dielectric stress and to the effects of the atmosphere. Examples are porcelain or polymer shell of a bushing, support insulators, and disconnecting switches.
Self-restoring Insulation Insulation that completely recovers insulating properties after a disruptive discharge (flashover) caused by the
application of a voltage. This is generally external insulation.
Self restoring Insulator
Terminator with Self-restoring Insulation on outside and non-self-restoring
on inside
Underground Cable with Non-Self Restoring
Insulation
Internal Insulation
The internal solid, liquid, or
gaseous parts of the insulation of equipment that are
protected by equipment
enclosures from the effects of the atmosphere. Examples are transformer insulation, internal insulation of bushings, internal parts of breakers and internal part of any electrical
equipment.
Non-self-restoring Insulation
Insulation that loses insulating properties or does not recover completely after a disruptive discharge caused by the
application of voltage.
Generally internal insulation.
Self Restoring Insulation Non-Self Restoring
Insulation
Basic Lightning Impulse Insulation Level (BIL)
The BIL level is the Dry insulation withstand strength of insulation expressed in kV. Is commonly used to describe substations and distribution system voltage
withstand characteristics.
Statistical BIL is used for insulators means there is a 10% probability of flashover and is used for self- restoring insulation
Conventional BIL is used for Transformers and Cable
is the voltage level where there is a 0% probability of Flashover and is applied to non selfrestoring insulation
Insulator BIL is directly proportional to the strike distance of an insulator
BIL ≈ 15kV x S(inches) And is affected by Altitude
Note 1: Arresters do not have a BIL rating since their external insulation is self
protected by the internal MOV disks. In a sense they have an infinite BIL.
Note 2: Arresters close to an insulator give the insulator infinite BIL.
Basic Switching Impulse Insulation Level (BSL)
The BSL level is the switching surge withstand level of the insulation in terms of kV.
BSLs are universally tested under Wet conditions.
Statistical BSL of Insulators
apply to self restoring insulation and represents a 10%
probability of flashover.
Conventional BSL of Transformers and solid dielectrics
apply to non-self-restoring insulation and represents a 0% probability of flashover
BSL is proportional to the strike distance of an insulator
BSL= 1080e((0.46 x Strike Distance) + 1)
And is affected by Altitude
Note 1: Arresters do not have a BSL
rating since their external insulation is self protected by the internal MOV disks. In a sense they have an infinite BSL.
Note 2: Arresters close to an insulator give the insulator infinite BSL.
Power Frequency Withstand Voltage This is the highest power frequency voltage an insulator can withstand under wet conditions (low level of contamination).
It is affected by creepage distance and strike distance.
Note 2: Arresters will go into conduction if the AC voltage across the unit reaches a 1.25 pu MCOV and above. However they cannot sustain this condition for very long or they will over heat and fail.
Note 3: If the housing is highly contaminated, the housing may flashover at levels below the turn-on voltage of the arrester.
Note 4: In highly contaminated areas, extra creepage distance insulators are used to overcome this potentially low flashover voltage. The same policy should be applied to arresters.
Note 1: Insulator withstand voltages are often >2-3 times their operating
voltage.
Critical Flash Over (CFO) Self Restoring insulation only
This is the voltage with a 50% probability of flashover of the insulator. It applies to both lightning and switching. It is used to quantify insulation used on transmission and distribution lines.
Typically CFO is 4-6% higher than Statistical BIL on an insulator.
Chopped Wave Withstand (CWW)
This is a withstand level of equipment. A standard lightning impulse is used but the surge is chopped at 3us, which means the stress is applied for a much shorter time than a standard lightning impulse test and must flashover near the crest of the wave instead of on the tail as it can in BIL tests. The value of this characteristic is about 1.10 times BIL for power
transformers and 1.15 times BIL for bushings.
Caused by insulator flashover just past crest.
Can cause winding to winding stress in some transformers
CWW
Chopped Wave Withstand
BIL
Basic Impulse Withstand Level
BSL
Basic Switching Impulse Withstand Level
Typical Values 70-1500kVp
Another form of Lightning withstand is CFO
Critical Flashover Voltage
The Backflash
When the OHGW on a transmission line is hit by lightning, a rapid series of events takes place.
If the system is grounded well than the surge is transferred to earth and there is no effect on the phase conductors.
But occasionally a backflash will occur, this series of slides will show you a close up view of the sequence of events.
The Backflash
Time = 0
The first event is the strike. Of course there was already a great deal of activity just to connect this line to the cloud, but that is for another
sequence.
When the strike pins to the wire, it sets up a voltage surge that travels in both directions down the line. (1-50 million volts)
This is all happening at nearly the speed of light and until the surge actually finds ground, there is little current flow.
The Backflash
Time = 1
In a few Nano-seconds, the voltage front meets the down ground and travels toward earth at the tower bottom. While at the same time it is inducing a voltage on to the phase conductors
When it reaches earth, the current begins to flow.
The voltage along the tower increases rapidly due to ground potential rise.
This potential rise is caused by the resistance of the ground rod of the tower.
This tower voltage rises as the current begins to flow.
Induced
Induced
The Backflash
Time = 2
The voltage at the base of the base of the insulators and on the phase conductors
increases as the surge increases in amplitude
If the voltage at the base of the insulator increases at a faster rate than the induced voltage on phases, it can reach the CFO of the insulator
The Backflash
Time = 3
The voltages continue to
increase across all components as the surge crests.
The Backflash
Time = 4 (.5-2 µsec)
If the voltage across the insulator exceeds the CFO, it can flashover from the pole down ground to the phase.
This is the backflash……
It flashes from the base to the conductor which is intuitively backward since the down ground spends its entire life except for these few microseconds at ground potential.
This is the part of the event that we are interested in with insulation coordination studies. What effect this surge will have the substation.
But its not over yet…..
The Backflash
Time = 5 (20-50 µsec)
The lightning stroke is over and the voltages on the lines revert back to their pre-strike levels.
But the air around the insulator is seeping with ions and still highly conductive.
When the AC voltage reaches a high enough level, it now flashes forward from the phase conductor to the down ground.
The Backflash
Time = 6 (50 µsec to 200ms)
When the insulator flashes over for a second time, power frequency
current flows to ground and a fault is now underway on the circuit and will remain there until a breaker interrupts the event.
At that point the event is over
assuming no damage occurred on the insulator.
AC Follow current causing a Line to Ground Fault
Until breaker interrupts
The Backflash
The surge that is transferred onto the phase conductor has entered the station within a few µsec, even before the fault was initiated.
This is the impulse that becomes the concern of insulation coordination in substations.
Note the voltage at the transformer is clamped by the arresters.
Arresters
CCVTs
Arresters Note the voltage at the
transformer is higher than at the arresters. This is due to traveling wave reflection
Red = Voltage @ Arrester
Green = Voltage @ Transformer 3 m separation
30 m separation
Separation Distance
Arresters
the other half of Insulation
Coordination
Arrester Definition
• Polymer Housing
• Metal Oxide Varistor (MOV)
• Conductive Spacer
• Strength Member (Fiberglass)
• Spring for Compression
• Rubber Seals
• End Vents and Diaphragms
VI Characteristics of an Arrester or Disk is the essence of the MOV. The resistance of the MOV disk is a function of the voltage stress across the terminals.
Example 50kV MCOV
Arrester
Typical Varistor/Arrester V-I Characteristics
|--- Breakdown Region----|
Pre-Breakdown Region
|---|
High Current Region
|---|
Leakage Current Region V1ma or Reference Voltage
Region
TOV Region
Switching Surge Region
Lightning Impulse
Region
Normal Operating Region
20C
200C
Physicists Terminology
Engineering Terminology Vref or Uref
V10kA or U10kA
MCOV or UC (peak) Rated V or Ur peak
SPL LPL
Arrester Discharge Voltage Curve
Fast Front Voltage
10kA Lightning Protective Level
LPL Switching Surge Protective Level
SPL Faster Front Surges Slower Front Surges
Insulation Withstand Curve
Arrester Discharge Voltage Curve
Chopped Wave Withstand CWW
Front of Wave Voltage
FOW
BSL BIL
10kA Lightning Protective Level
LPL
Switching Surge Protective Level
SPL
MP1= (CWW/FOW)-1
MP2= (BIL/LPL)-1
MP3= (BSL/SPL)-1
IEEE recommends > .15 or 15%
IEEE recommends >.15 or 15%
IEEE recommends >.20 or 20%
Clearances and Altitude
Phase to phase and phase to ground
clearances are often the purpose of a study.
They are easily calculated once the
maximum voltage on a line is determined.
With arresters, the NEC clearances can be reduced near the arrester and along ROW if studies are completed.
For example,
Lightning Impulse withstand of Air at STP is a linear
function at 450kV/m
Clearance and Altitude/Elevation
0,600 0,650 0,700 0,750 0,800 0,850 0,900 0,950 1,000
0 2000 4000 6000 8000 10000 12000
Ratio of Altitude to Sea Level
Elevation in Feet
Change in
Withstand voltage
'δ=e-A/26710
All external insulation is affected by altitude.
Specifically in this case, the clearance between lines needs to be
increased to attain the same withstand voltage at sea level.
Physical Dimensions
V V
30 0m NC
V
25 meters
V
2 m AFram
LineA
5 ohms
LCC R(i) R(i)
Sourc
V
2uh 2 meters 5 ohms L_imp H
L_Imp
LCC
I V
R(i)
I
230kV
200 m
NC
20 m 2 m
Ej 230/13.8
BCT Y
Et
V
Ea
R(i) R(i)
R(i)
I
6.3nF 3m
Eb
V
Chapter 12
Insulation Coordination of Power Systems by Andrew Hileman
Line Entrance
Arrester Transformer
Arrester
Flashover of C-Phase close to substation
6000ft 2000 ft 2000 ft
Surges travel at ~980ft per µs on an overhead line.
In this elongated station, It can be seen here that the surge first appears at the metered points at different times based on the distance from the initial surge.
Backflash 6000 ft out on the line
At Station Entrance
BreakerAt
ArresterAt
Elongated Substation
Ground Flash Density
Ground Flash Density
Is used to calculate the
• Backflash rate on a line
• The challenge rate to a line
• The outage rate of lines
• Steepness of a surge on a line
• The MTBF of a substation
The Insulation Coordination Study Report