• Tidak ada hasil yang ditemukan

Design of the SVC Voltage Regulator

Dalam dokumen TRANSMISSION SYSTEMS (Halaman 169-178)

Concepts of SVC Voltage Control

5.2 VOLTAGE CONTROL

5.2.5 Design of the SVC Voltage Regulator

154 CONCEPTS OF SVC VOLTAGE CONTROL

KN c VS Vb

Bb BS

V2b V2b c VS

Vb

QSVC BSVSVb

Vb VS

(5.27)

or

KN c VSQSVC VbSc Vb

VS

(5.28)

where Scc the short-circuit power

c the base voltage . the short-circuit current c Vb. (BSVS)

AssumingVS

/

Vb is close to unity, which is usually the case in power systems, the per-unit system gain is expressed as

KN c DVSVC

BSVC c QSVC Sc

pu (5.29)

It should be noted that the system gain will change with variations in network configuration, line switchings, and any event that may change the system short- circuit level at the SVC bus.

VOLTAGE CONTROL 155

dc-Side Filters

Voltage- Magnitude Transducer

ac-Side Filters Vac

SVC HV Bus

XT

Vmeas (pu)

per-unit TCR Conduction

BTCR XTCR BCTSC

XTSC BTSC1

BTSC2 BTSC3 Bmin

Bmax Vref (pu)

TCRTSC Logic KR BTOT

1+sTR

where

Bmin= BSVC at the TCR only Bmax= BSVC at all TSCs only BTOT= Bmax Bmin

+

BSVC 0 Ve

BCTSC

XTSC BCTSC

XTSC Σ

+ Other Control Inputs

KR= the static gain (full range for the voltage change of 1/KR)

TR= the regulator time constant

BSVC 0= the net susceptance at the SVC HV bus BTSCTOT

ISVC

Figure 5.6 Basic elements of SVC voltage-regulation control with TSC.

KSLc the current droop (pu)

TRc the regulator time constant (s) An additional term-transient gain,KT, is defined as

KT c KR

TR (5.31)

In the integrator–current-droop model, the voltage regulator is described as an integratorGR(s), with the following explicit current-feedback loop:

GR(s)c 1 sRR

(5.32) where RR cthe response rate (ms

/

pu)

The regulator time constant,TR, and the response rate,RR, are related as TRc RR

KSL

(5.33) 5.2.5.1 Simplistic Design Based On System Gain This design method- ology, proposed in ref. [11], considers a proportional–integral (PI) controller with an explicit current feedback similar to that described in the previous sec- tion. This method is calledsimplisticbecause it models the power system by a

156 CONCEPTS OF SVC VOLTAGE CONTROL

(c) 1 sRR VSL

Bref

KSL Vmeas Vref

Σ

Bmin Bmax Ve

+

ISVC

(b) 1

sRR Bref

VSL

KSL Vmeas

Vref

Bmin Bmax Ve

+ Σ

(a) Vmeas

Vref

Bref KR

1 + sTR

Σ

Bmin Bmax Ve

+

Figure 5.7 Alternate voltage-regulator forms: (a) a gain–time constant; (b) an integra- tor with susceptance-droop feedback; and (c) an integrator with current-droop feedback.

pure reactance or equivalent gain and does not account for the effect of genera- tor dynamics on controller performance. This method is, however, highly impor- tant, as it explains very clearly the influence of system strength and current- droop on the speed of controller response.

The block diagram of an SVC-compensated power system is shown in Fig.

5.8(a). It is assumed that

1. the change in system voltageDV caused by the SVC is small;

2. the SVC bus voltage is very close to the nominal-rated voltage, that is, VSVC1pu; and

3. the variations in the SVC reference voltage are also quite small.

VOLTAGE CONTROL 157

Vref Σ Measurement

HI

Measurement HV

Regulator

GR GY

YC YL

I V Power System Disturbances Slope

KSL

Vadd Variable Admittance

YLmin < YL < YLmax

Σ Σ

+ + +

+ +

+

(a)

Variable Admittance YLmin < YL < YLmax

Σ

Measurement HM

Regulator

GR GY

YL= IL

Power System GN

Disturbances

+ Σ

+ + V0

VZ Σ

+

Vref

∆V

Vadd

∆V

+

Slope KSL

(b)

Figure 5.8 (a) A block diagram of the system voltage controller incorporating an SVC and (b) a simplified block diagram of the system voltage controller forV−∼Vrated.

Then, the currents IL, in the TCR, and IC, in the TSC, are given by IL cYLVSVCYL in pu (5.34) IC cYCVSVCYC in pu (5.35) An equivalent circuit of the SVC-compensated system is depicted in Fig.

5.8(b). The following simplifications are made:

1. The voltage- and current-measurement systems are considered identical.

2. The TSC switchings are ignored, and the droop effect of the capacitive current is merged withVref.

158 CONCEPTS OF SVC VOLTAGE CONTROL

3. The only variable considered is the inductive currentIL, which reduces the system bus voltage by DV as given by Eqs. (5.18)–(5.20). The effect of constant-capacitive SVC current on the SVC bus voltage is incorporated in V0. The influence of any power-system disturbance,Vz, is neglected.

The thyristor phase control is denoted byGY, as already explained in Chapter 4, and is given by

GY(s)c es Td

1+s TY (5.36)

where Tdc the thyristor dead time (cone-twelfth cycle time) TY c the thyristor firing-delay time caused by the sequential

switching of thyristors (one-quarter cycle time)

A PI controller that gives the fastest stable response for the weakest system configuration having gainKNmax is determined [11] as

GR(s)cKp

{

1+ s T1Y

}

c 2(KSL+1KNmax)

{

1+ s T1Y

}

(5.37)

The overall closed-loop transfer function, GW(s), of the control system for incremental variations is given by

GW(s)c DV(s) DVref(s)

c KNGRGY 1+ (KSL+KN)GRGYHM

(5.38) where HMc the transfer function of the measurement system

To obtain the response time of the control system only, the largest time con- stants are considered. Thus

GW(s) KN

(KSL+KN) s TW

1+s TW (5.39)

where

TW c2冢KSLKSL++KNKNmaxTY (5.40)

Hence for a change in the reference voltageDVref, the SVC bus voltage varies as

VOLTAGE CONTROL 159

DVc KN

KSL+KN DVref(1−et/TW) (5.41) The following conclusions are drawn from the foregoing analysis:

1. A change in the DVref causes the SVC bus voltage to vary by k . Vref because of the current droop, wherekcKN

/

(KSL+KN).

2. The fastest response is obtained whenKN cKNmax (i.e., for the weakest system state). In this case, the response time constant,TWopt, is obtained from Eq. (5.40) asTWoptc2Tyc8.33 ms for a 60-Hz system frequency.

The settling time (to 95% of the step change)3TWopt c 25 ms c 1.5 cycle time.

The voltage controller is expected to maintain stability under all reasonably realizable network configurations and to ensure a rapid response under those conditions. Hence the voltage controller is optimized for the lowest system short-circuit level.

Equation (5.36) can be rewritten as TW

2TY c TW

TWopt c KSL+KNmax KSL+KN

(5.42) Dividing the numerator and denominator on the right-hand side byKNmax, we get

TW

TWopt c

KSL KNmax

+ 1 KSL

KNmax + KN KNmax

(5.43)

From Eq. (5.29), it follows that

KNmaxc QSVC

Scmin (5.44)

Substituting Eqs. (5.29) and (5.44) in Eq. (5.43) gives

TW

TWopt c

KSL KNmax + 1 KSL

KNmax +Scmin Sc

(5.45)

A plot of the normalized-response time constant,TW

/

TWopt, as a function of the normalized-system short-circuit level,Sc

/

Scmin, is shown in Fig. 5.9. This

160 CONCEPTS OF SVC VOLTAGE CONTROL

1 2 3 4 5

Short - Circuit Level : SC SC min Danger

of Instability 1

2 3 4 5 6

ResponsetR tRopt

Optimal Regulator Setting for SC min: tR opt, Approximately 1.5 Cycles; No Overshoot

KSL= 0 KN max: All Values

KSL= 4% KN max = 0.2

KSL= 10% KN max = 0.2 KSL= 10% KN max = 0.1

6

Figure 5.9 Effect of the system short-circuit level on the SVC response time.

plot shows the influence of the network short-circuit level and current droop on the SVC response time.

For a given short-circuit level, the control response time increases (becomes slow) with decreasing values of the current slope. The response time is also enhanced as the system strength increases relative to the weakest network state.

If a larger current slope is chosen (of course, at the expense of voltage regula- tion), the increase in response time with system strength is comparatively lower.

If the weakest network states are chosen to be those with very low short-circuit levels, then the response time exhibits a much sharper increase with increasing system strength.

On the basis of the preceding observations, it is concluded that a large value of slope should be chosen, preferably in the 3–5% range. Furthermore, the weakest network should also be identified judiciously. If an unduly weak sys- tem, especially that encountered while rebuilding a network after a major sys- tem collapse, is chosen as the weakest network state, the response time will be unusually longer when realistic system states are existent.

Example 5.1 An SVC connected to a 735-kV system has a reactive-power

VOLTAGE CONTROL 161 range of 350 MVAR production to 100 MVA absorption. The droop is set to 4%. The system short-circuit level is specified as follows:

The maximum short-circuit current: 50 kA.

The minimum short-circuit current under normal operating conditions: 5 kA.

The minimum short-circuit current during system restoration after loss of a transmission line: 500 A.

From these specifications,

1. Determine the per-unit regulator gain that ensures stable operation from 5kA to 50 kA system short-circuit current.

2. Show the change of voltage-control response for the system variation and regulator setting in item 1 of this sublist.

3. Determine the per-unit regulator gain for stable operation in the system short-circuit-level range 500 A to 50 kA.

4. Show the change of the voltage-control response for item 1.

Solution 5.1

Item 1 The system gain is given from Eq. (5.29) as KN c QSVC

Sc pu (5.46)

where Sc cf3VbIc

Scmincf3 . 735 . 103 . 5 . 103 c6365MVA (5.47) Scmaxcf3 . 735 . 103 . 50 . 103 c63653MVA (5.48) KNmaxc QSVC

Scmin c 350−(−100)

6365 c0.0707pu (5.49)

KNminc QSVC

Scmax c 350−(−100)

63653 c0.00707pu (5.50) The regulator is optimized forKNmax. Thus the proportional gain of the voltage regulator, as given from Eq. (5.37), is

Kpc− 1

2(KSL+KNmax) c− 1

2(0.04+ 0.0707) c−4.52 (5.51)

162 CONCEPTS OF SVC VOLTAGE CONTROL

Item 2 The variation in response speed is calculated as follows from Eq.

(5.42):

TW

2TY c KSL+KNmax

KSL+KN c 0.04+ 0.0707

0.04+KN c 0.111 0.04+KN

(5.52) For

KN cKNmaxc0.0707, TW

2TY c1 (5.53)

For

KN cKNmin c0.00707, TW

2TY c2.36 (5.54) This demonstrates that the SVC response can slow down by a factor of 2.36 if the system short-circuit current changes from 5 kA to 50 kA.

Item 3 If the weakest network state is chosen to correspond to a short-circuit current of 500 A,

KNmaxc QSVC

Scmin c 350−(−100)

f

3 . 735 . 0.5 c0.070pu (5.55) The proportional gain of the voltage regulator is

Kpc− 1

2(KSL+KNmax) c− 1

2(0.04+ 0.707) c−0.669 (5.56) Item 4 The change of response speed is

TW

2TY c KSL+KNmax

KSL+KN c 0.04+ 0.707

0.04+KN c 0.747

0.04+KN (5.57) For

KN cKNmaxc0.0707, TW

2TY c 0.747

0.04+ 0.707 c1 (5.58) For

KN cKNminc0.00707, TW

2TY c 0.747

0.04+ 0.00707 c15.86 (5.59) The system configuration with the 500-A short-circuit level is definitely

EFFECT OF NETWORK RESONANCES ON THE CONTROLLER RESPONSE 163 abnormal and should not be chosen as the weakest network state for optimizing the regulator parameters. Otherwise, a very slow response (approximately 16 times the optimum) would result during the strong system condition.

5.2.5.2 Design That Considers Generator Dynamics A technique often resorted to for designing the voltage regulator of the SVC, by including the impact of generator dynamics, consists of the following steps:

1. Deriving a system model linearized around an operating point.

2. Obtaining the stability range of parameters of the preselected voltage- regulator structure from eigenvalue analysis.

3. Determining the best regulator parameters within the stability range that result in a fast response with acceptable overshoot.

4. Validating of the voltage-regulator performance through a detailed non- linear simulation of the system.

A case study of voltage-regulator design for an SVC located at the mid- line in a single-machine infinite-bus (SMIB) system [12], [13] is presented in Appendix A of this book.

5.3 EFFECT OF NETWORK RESONANCES ON THE CONTROLLER

Dalam dokumen TRANSMISSION SYSTEMS (Halaman 169-178)