• Tidak ada hasil yang ditemukan

The contents of the thesis will remain confidential for years

N/A
N/A
Nguyễn Gia Hào

Academic year: 2023

Membagikan "The contents of the thesis will remain confidential for years"

Copied!
98
0
0

Teks penuh

The undersigned acknowledge that they have read and re-communicate to the Graduate Program for acceptance of this assignment to meet the requirements for said degree. State-of-the-art facilities and in-house know-how paved the way for the completion of this study. Preliminary simulations using Vapcyc and CoilDesigner software show an improvement in cooling efficiency as well as an improvement in the dehumidification performance of the air conditioning system.

Piping and components of the evaporator-condenser system Schematic of the nozzle air flow measuring apparatus Adjustment of the air enthalpy test method.

Figure 4.3  Figure 4.4  Figure 4.5  Figure 4.6  Figure 4.7  Figure 4.8  Figure 4.9  Figure 4.10  Figure 4.11A  Figure 4.11B  Figure 4.11 C  Figure 4.12  Figure 4.13
Figure 4.3 Figure 4.4 Figure 4.5 Figure 4.6 Figure 4.7 Figure 4.8 Figure 4.9 Figure 4.10 Figure 4.11A Figure 4.11B Figure 4.11 C Figure 4.12 Figure 4.13

INTRODUCTION

Justification for the Research

However, regulation of relative humidity along with temperature control is not available in conventional air conditioners. With these drawbacks in mind, the purpose of this research is to investigate the possibility of incorporating humidity control into an existing air conditioning system. The method of introducing humidity control is by adding a reheat coil to the unit which is connected in series before the evaporator coil.

Humidity control can be achieved using an electronic expansion valve to regulate the refrigerant temperature at the reheat coil.

Objectives of Study

Scope of Study

LITERATURE REVIEW

  • Chapter Overview
  • Thermal Comfort
  • Opportunities for Research
  • Chapter Overview

The air to be cooled and dehumidified first enters the desiccant wheel, where the wheel pre-cools and humidifies the air. The cooling capacity is calculated from point I to point 2 and does not take the heating of the air into account. Methods related to the control of the internal air conditioning system can also be used for humidity control.

Desiccant wheels • Improves lower COP compared to conventional air-cooled dehumidification.

Figure 2.1: Acceptable ranges of operative temperature and humidity based on a  I 0%
Figure 2.1: Acceptable ranges of operative temperature and humidity based on a I 0%

METHODOLOGY

System Circuit Design

Refrigerant at point 3 will then expand again at EXV2 to the working pressure of the evaporator at point 5. The potential increase in performance comes from the lower quality of the refrigerant absorbing more heat in the evaporator due to a higher latent heat requirement. The heating of the air from the reheat coil is intended to bring the relative humidity of the cooled air within the comfort range.

This balancing simulation is performed to obtain the cooling performance of the system without reheating. The cooling performance of the system can be estimated by calculating the enthalpy difference between the inlet and outlet air. The air enthalpy is a function of the air dry bulb, DB, and the humidity ratio, W.

The theoretical compressor power was obtained from the enthalpy difference between the outlet and inlet of the compressor. Referring to Figure 3.3, the points representing the inlet and outlet of the compressor are state points 5 and 6, respectively. This section describes the specifications of the modified indoor unit YCC60C, components related to the indoor unit.

The function of the expansion device in an air conditioning system is to regulate the working pressure of the evaporator. Due to space constraints, most of the system components are placed on the outside of the indoor unit.

Figure 3.1: Layout of the YCC60C
Figure 3.1: Layout of the YCC60C

Measuring Equipment

The indoor unit airflow rate is measured with a nozzle chamber designed in accordance with ASHRAE Standard 41.2 [41]. The calculation method for determining the cooling performance of the unit is based on indoor test data using the loop air enthalpy test method. This section explains the steps to perform the experimental study of the evaporator-condenser system.

Therefore, all joints in the system must be checked individually with a soapy solution. If bubbles form on the soap solution, this means that there is a leak in the system and the assembly needs to be repaired or replaced. The system is switched on and the EXV is adjusted until the compressor discharge temperature is 75°C.

Then 3.9 kg of R410a refrigerant is charged into the system and the test is repeated at a discharge temperature of 80 °C. Low superheat suction means there is a chance for liquid refrigerant to enter the compressor, reducing compressor reliability. After determining the optimal charge for the cooling system, the refrigerant is released from the system.

To test the effect of the reheat coil in the system, a reheat EXV is used to expand the refrigerant entering the reheat coil to a predetermined temperature. Next, a simulation method using Vapcyc and Coi!Designer is shown to determine the performance of the evaporator-condenser system.

Figure 3.14:  Schematic of the nozzle airflow measuring apparatus
Figure 3.14: Schematic of the nozzle airflow measuring apparatus

Chapter Overview

Implications of the Balancing Simulation

While the evaporating temperature does decrease when the evaporator-condenser performance is simulated, the refrigerant mass flow rate remains unchanged during the simulation process. A consequence of the lower evaporation temperature is the higher rate of moisture removal from the evaporator, as discussed in Chapter 2.

Table 4.1:  Simulation Results
Table 4.1: Simulation Results

Performance and Moisture Removal

Due to the performance loss in the system with reheat, the moisture removal is expected to be less than that without reheat. However, the test results show that the absolute humidity is lower with the reheat coil, indicating that the moisture removal has increased. . By comparing the removal of latent heat and sensible heat at different reheat coil inlet temperatures as shown in Figure 4.3, it is seen that although the total capacity decreases, the latent heat removal increases. A higher value of latent heat removal implies that more moisture is removed from the air.

Figure 4.1:  Effect of reheat coil entry temperature on total capacity and absolute  humidity
Figure 4.1: Effect of reheat coil entry temperature on total capacity and absolute humidity

Coefficient of Performance

As expected, the COP is lower as the reheat coil inlet temperature increases due to the lower total system capacity.

Figure 4.5:  Coefficient of performance against reheat coil entry temperature  Figure  4.5  shows  the  COP  at  different  reheat  coil  entry  temperatures
Figure 4.5: Coefficient of performance against reheat coil entry temperature Figure 4.5 shows the COP at different reheat coil entry temperatures

Relative Humidity

The exit air dry bulb temperature is also higher compared to the case without reheat, as shown in Figure 4.7. As the dry bulb temperature increases, the maximum amount of moisture the air can hold increases.

Figure 4. 7:  Air leaving dry bulb temperature
Figure 4. 7: Air leaving dry bulb temperature

Comparing Simulation Results and Test Results

Due to the limitations of the Vapcyc to simulate the evaporator-condenser system, it was necessary to make certain assumptions. To simplify the simulation, the coolant mass flow rate was assumed to be the same for both systems with and without the reheat coil. However, the addition of the reheat coil and its EXV increased the internal resistance of the system.

This causes a reduction in the mass flow of the coolant, which in turn will reduce cooling performance. The enthalpy difference of the refrigerant is considered as the difference between the enthalpies at the inlet and outlet pipes of the evaporator. However, the enthalpy at the inlet of the evaporator is difficult to measure due to the quality of the refrigerant, which could not be measured directly in the experiment.

At fixed compressor power, the additional pressure drop in the EXV and the additional reheat coil result in a lower refrigerant mass flow rate. In order to achieve a higher cooling efficiency, an increase in the mass flow rate of the refrigerant must be taken into account. One way to increase the refrigerant mass flow rate is to lower the compressor discharge temperature from 85 °C.

Calculation of system mass flow rates at various reheat temperatures is summarized in Appendix C. This is because the compressor compression ratio is a fixed value and cannot be changed.

Table 4.2  System performance of the evaporator-condenser system  Reheat coil entry  Change compared to system with reheat(%)
Table 4.2 System performance of the evaporator-condenser system Reheat coil entry Change compared to system with reheat(%)

P-h Diagram Comparison

This is due to the test condition where the discharge temperature is maintained at 85°C by adjusting the cooling coil EXV. The proposed evaporator-condenser system is similar to the thermosyphon heat exchanger (THX) and desiccant wheel system due to the reheating of air to the cooling coils. Therefore, it is appropriate to make a comparison between the current results of the evaporator-condenser system with those of the THX and desiccant wheel systems.

The experimental results of the evaporator-condenser system show that there is a decrease in the cooling performance, while the moisture removal is improved and the relative humidity is lowered. The results shown in Table 4.2 follow the trends obtained in the desiccant wheel experiment for moisture control conducted by Subramanyam et a!. The relative humidity was lower with the THX system compared to the conventional system as shown in Figure 4.13.

Several advantages are present in the evaporator-condenser system compared to the THX and desiccant wheel systems. The amount of space required to install a desiccant wheel system or THX is quite large compared to the evaporator-condenser system. This is because the size of the desiccant wheel and the THX are both larger compared to just adding a reheat coil to the existing cooling system.

Additionally, using an EXV to control the reheat coil coolant temperature provides a better method of varying the amount of moisture removal required. Using the evaporator-condenser system proves beneficial due to its relative simplicity, ability to control humidity, and smaller space required for installation.

Figure 4.11 A:  P-h diagram for reheat coil entry temperature of21.0°C  I I I I I I
Figure 4.11 A: P-h diagram for reheat coil entry temperature of21.0°C I I I I I I

Chapter Summary

Conclusions

CONCLUSIONS

The evaporating temperature is an important aspect in the air conditioning system in determining its performance. 34;Handbook-HVAC Systems and Equipment", American Society of Heating, Refrigeration and Air-conditioning Engineers, Atlanta, GA, USA, 2008. 34;Application of desiccant wheel to control humidity in air-conditioning systems", Applied Thermal Engineering 24, p.

34;Application of Heat Pipe Heat Exchangers to Humidity Control in Air Conditioning Systems" Applied Thermal Engineering Vol17 No 6, pp. 34;A New Control Algorithm for Direct Expansion Air Conditioning Systems for Improved Indoor Humidity Control and Energy Efficiency" Energy Conversion and Management 49, pp . 34;The Optimal Design of Refrigerant Mixtures for a Two Evaporator Refrigeration System." Computers in Chem Engng, Vol.

34;Performance simulation of a two-evaporator refrigerator-freezer loaded with pure and mixed refrigerants." International Journal of Refrigerant, Vol 14, pp. 34;Optimization of vapor compression systems via simulation." In The International Compressor Engineering Conference and Refrigeration and Air-Conference Conference, Purdue, Paper529,2002. 34;Standard 37 methods of testing for rating electrically driven unit air conditioning and heat pump equipment." Atlanta, GA, USA, 2005.

34;Study on a wickless heat pipe for humidity control." I Proceedings of the 91h International Heat Pipe Symposium, Kuala Lumpur, s. 34;Feasibility Study on a Two-Evaporator System for Control of Thermal Comfort", Energy Conversion and Management ( Under gennemsyn).

Gambar

Figure 4.3  Figure 4.4  Figure 4.5  Figure 4.6  Figure 4.7  Figure 4.8  Figure 4.9  Figure 4.10  Figure 4.11A  Figure 4.11B  Figure 4.11 C  Figure 4.12  Figure 4.13
Figure 2.3:  Relative humidity control by auxiliary heater
Figure 2.4:  Schematic diagram of ll desiccant wheel in an air-conditioning system [19]
Figure 2.5:  Schematic diagram of a heat pipe heat exchanger in an air conditioning  system
+7

Referensi

Dokumen terkait

Metode penelitian yang digunakan adalah percobaan dengan mengamati kualitas semen segar yang meliputi; volume, konsentrasi, motilitas individu, total spermatozoa motil dan jumlah

LIST OF FIGURES Figure 2-1 Classification of natural fibers derived from plants 7 Figure 2-2 Structure of natural fibers 8 Figure 2-3 The repeat unit of polyethylene 8 Figure 2-4