A. DATA TANAH
DATA HASIL PENGUJIAN LABORATORIUM (DATA BOR TANAH) SONDIR SPT
No Kedalaman Jenis
c
ug j q
f Nilai SPTz1 (m) z2 (m) Tanah (kN/m2) (kN/m3)
( ... ▫ )
(kN/m2)N
1 0.00 5.00 lempung 23.00 9.962 0 5.60 5
2 5.00 10.00 lempung 30.00 9.962 0 12.30 12
3 10.00 15.00 lempung 52.00 9.962 0 18.40 27
4 15.00 20.00 lemp. padat 61.00 10.372 0 22.60 35
5 20.00 25.00 lemp. pasir 63.00 11.683 12 27.30 42
B. DATA BAHAN
Jenis tiang pancang : Beton bertulang
Dimensi tiang pancang,
D =
0.30 mPanjang tiang pancang,
L =
4.00 mKuat tekan beton tiang pancang,
f
c' =
25 MPaBerat beton bertulang,
w
c=
24 kN/m3C. TAHANAN AKSIAL TIANG PANCANG 1. BERDASARKAN KEKUATAN BAHAN
Luas penampang tiang pancang,
A = p / 4 * D
2=
0.0707 m2Berat tiang pancang,
W
p= A * L * w
c=
6.79 kNKuat tekan beton tiang pancang,
f
c' =
25000 kPaKapasitas dukung nominal tiang pancang,
P
n= 0.30 * f
c' * A - 1.2 * W
p=
522kN
Faktor reduksi kekuatan,
f =
0.60Tahanan aksial tiang pancang,
f * P
n=
313.20kN
A. PERHITUNGAN KEKUATAN TIANG PANCANG
BAB IV PERHITUNGAN KEKUATAN TIANG PANCANG DAN PONDASI
( Tabel IV. A.1 Data Tanah )
2. BERDASARKAN DATA BOR TANAH (SKEMPTON)
a. Tahanan ujung
Tahanan ujung nominal dihitung dengan rumus :
P
b= A
b* c
b* N
cA
b=
Luas penampang ujung bawah tiang (m2),c
b=
Kohesi tanah di bawah dasar tiang (kN/m2),N
c=
Faktor daya dukung.Dimensi tiang pancang,
D =
0.30 mLuas tampang tiang pancang,
A
b= p / 4 * D
2=
0.0707 m2Kohesi tanah di sekitar dasar tiang,
c
b=
55.00 kN/m2Faktor daya dukung menurut Skempton,
N
c=
9Tahanan ujung nominal tiang pancang :
P
b= A
b* c
b* N
c=
34.989 kNb. Tahanan gesek
Tahanan gesek nominal menurut Skempton :
P
s= S [ a
d* c
u* A
s] a
d=
faktor adhesic
u=
Kohesi tanah di sepanjang tiang (kN/m2)A
s=
Luas permukaan dinding tiang (m2).Faktor adhesi untuk jenis tanah lempung pada tiang pancang yang nilainya tergantung dari nilai kohesi tanah, menurut Skempton, diambil :
→ a
d= 0.2 + [ 0.98 ]
cuDiameter tiang pancang,
D =
0.300m
Luas permukaan dinding segmen tiang,
A
s= p * D * L
1L
1=
panjang segmen tiang pancang yang ditinjau (m).Perhitungan tahanan gesek nominal tiang
No Kedalaman
L
1A
sc
ua
dP
sz1 (m) z2 (m) (m) (m2) (kN/m2) (kN)
1 0.00 5.00 5.0 4.7124 23.00 0.83 89.780
2 5.00 10.00 5.0 4.7124 30.00 0.75 105.390
3 10.00 15.00 5.0 4.7124 52.00 0.55 134.713
4 15.00 4.00 -11.0 -10.3673 55.00 0.53 -301.738
Tahanan gesek nominal tiang, 28.145
P
s= S a
d* c
u* A
s=
28.145kN
c. Tahanan aksial tiang pancang
Tahanan nominal tiang pancang,
P
n= P
b+ P
s=
63.13kN
Faktor reduksi kekuatan,
f =
0.60Tahanan aksial tiang pancang,
f * P
n=
37.88kN
( Tabel IV. A. 2 Perhitungan Tahanan Gesek Nominal Tiang Pancang )
3. BERDASARKAN HASIL UJI SONDIR (BAGEMANN)
a. Tahanan ujung
Tahanan ujung nominal dihitung dengan rumus :
P
b= w * A
b* q
cw =
faktor reduksi nilai tahanan ujung nominal tiang,A
b=
luas ujung bawah tiang (m2),q
c=
tahanan penetrasi kerucut statis yang merupakan nilai rata-rata dihitung dari 8.D di atas dasar tiang sampai 4.D di bawah dasar tiang (kN/m2),Dimensi tiang pancang,
D =
0.30 mLuas tampang tiang pancang,
A
b= p / 4 * D
2=
0.0707 m2 Tahanan penetrasi kerucut statis rata-rata dari 8.D di atas dasar s.d. 4.D di bawah dasartiang pancang,
q
c= 42
kg/cm2→ q
c=
4200 kN/m2Faktor reduksi nilai tahanan ujung nominal tiang,
w =
0.50Tahanan ujung nominal tiang pancang :
P
b= w * A
b* q
c=
148.440 kNb. Tahanan gesek
Tahanan gesek nominal menurut Skempton dihitung dg rumus :
P
s= S [ A
s* q
f] A
f=
Luas permukaan segmen dinding tiang (m2).A
s= p * D * L
1q
f=
tahanan gesek kerucut statis rata-rata (kN/m).No Kedalaman
L
1A
sq
fP
sz1 (m) z2 (m) (m) (m2) (kN/m2) (kN)
1 0.00 5.00 5.0 4.7124 5.60 26.39
2 5.00 10.00 5.0 4.7124 12.30 57.96
3 10.00 15.00 5.0 4.7124 18.40 86.71
4 15.00 4.00 -11.0 -10.3673 19.50 -202.16
P
s= S [ A
s* q
f] =
-31.10c. Tahanan aksial tiang pancang
Tahanan nominal tiang pancang,
P
n= P
b+ P
s=
117.34kN
Faktor reduksi kekuatan,
f =
0.60Tahanan aksial tiang pancang,
→ f * P
n=
70.40kN
( Tabel IV. A. 3 Perhitungan Tahanan Gesek Nominal Tiang Pancang )
4. BERDASARKAN HASIL UJI SPT (MEYERHOFF)
Kapasitas nominal tiang pancang secara empiris dari nilai N hasil pengujian SPT menurut Meyerhoff dinyatakan dengan rumus :
P
n= 40 * N
b* A
b+ Ň * A
s(kN)
dan harus £
P
n= 380 * Ň * A
b(kN)
N
b=
nilai SPT di sekitar dasar tiang, dihitung dari 8.D di atas dasar tiang s.d 4.D di bawah dasar tiang,Ň =
nilai SPT rata-rata di sepanjang tiang,A
b=
luas dasar tiang (m2)A
s=
luas selimut tiang (m2)Berdasarkan hasil pengujian SPT diperoleh data sbb.
No Kedalaman Nilai SPT
L
1L
1* N
z1 (m) z2 (m)
N
(m)1 0.00 5.00 5 5.0 25.0
2 5.00 10.00 12 5.0 60.0
3 10.00 15.00 27 5.0 135.0
4 15.00 4.00 30 -11.0 -330.0
4.0 -110.0
Nilai SPT rata-rata di sepanjang tiang,
Ň = S L
1*N / S L
1= -27.50
Nilai SPT di sekitar dasar tiang (8.D di atas dasar tiang s.d 4.D di bawah dasar tiang),
N
b=
30.00Dimensi tiang pancang,
D =
0.30 mPanjang tiang pancang,
L =
4.00 mLuas dasar tiang pancang,
A
b= p / 4 * D
2=
0.0707m
2Luas selimut tiang pancang,
A
s= p * D * L =
3.7699 m2P
n= 40 * N
b* A
b+ Ň * A
s=
-18.8495559 kNP
n> 380 * Ň * A
b=
-738.67 kNKapasitas nominal tiang pancang,
P
n=
-738.67 kNFaktor reduksi kekuatan,
f =
0.60Tahanan aksial tiang pancang,
→ f * P
n=
-443.20kN
5. REKAP TAHANAN AKSIAL TIANG PANCANG
No Uraian Tahanan Aksial Tiang Pancang
f * P
n1 Berdasarkan kekuatan bahan 313.20
2 Berdasarkan data bor tanah (Skempton) 37.88
3 Berdasarkan hasil uji sondir (Bagemann) 70.40
4 Berdasarkan hasil uji SPT (Meyerhoff) -443.20
Daya dukung aksial terkecil,
f * P
n=
-443.20 kNDiambil tahanan aksial tiang pancang,
→ f * P
n=
-440.00 kND. TAHANAN LATERAL TIANG PANCANG
1. BERDASARKAN DEFLEKSI TIANG MAKSIMUM (BROMS)
Tahanan lateral tiang (H) kategori tiang panjang, dapat dihitung dengan persamaan :
H = y
o* k
h* D / [ 2 * b * ( e * b + 1 ) ]
dengan, b
= [ k
h* D / ( 4 * E
c* I
c) ]
0.25D = Dimensi tiang pancang (m),
D =
0.30 mL = panjang tiang pancang (m),
L =
4.00 mk
h=
modulus subgrade horisontal (kN/m3),k
h=
26720 kN/m3E
c=
modulus elastis tiang (kN/m2),E
c= 4700 * Ö f
c' * 10
3=
23500000 kN/m2I
c=
momen inersia penampang (m4),I
c= p / 64 * D
4=
0.000398 m4 e = Jarak beban lateral terhadap muka tanah (m),e =
0.20 my
o=
defleksi tiang maksimum (m).y
o=
0.010 mb =
koefisien defleksi tiang, b= [ k
h* D / ( 4 * E
c* I
c) ]
0.25=
0.68052445 mb * L =
2.72 > 2.5 maka termasuk tiang panjang (OK) Tahanan lateral nominal tiang pancang,H = y
o* k
h* D / [ 2 * b * ( e * b + 1 ) ] =
51.84 kNFaktor reduksi kekuatan,
f =
0.60Tahanan lateral tiang pancang,
→ f * H
n=
31.10kN
( Tabel IV. A. 4 Rekap Tahanan Aksial Tiang Pancang )
2. BERDASARKAN MOMEN MAKSIMUM (BRINCH HANSEN)
Kuat lentur beton tiang pancang,
f
b= 0.40 * f
c' * 10
3=
10000 kN/m2Tahanan momen,
W = I
c/ (D/2) =
0.00265 m3Momen maksimum,
M
y= f
b* W =
26.51 kNmKohesi tanah rata-rata di sepanjang tiang
No Kedalaman
L
1c
uc
u* L
1z1 (m) z2 (m) (m) (kN/m2)
1 0.00 5.00 5.0 23.00 115.00
2 5.00 10.00 5.0 30.00 150.00
3 10.00 15.00 5.0 52.00 260.00
4 15.00 17.00 2.0 63.00 126.00
S L
1=
17.0Sc
u*L
1=
651.00Kohesi tanah rata-rata,
č
u= S [ c
u* L
1] / S L
1=
38.2941176 kN/m2f = H
n/ [ 9 * č
u* D ]
pers.(1)g = L - ( f + 1.5 * D )
pers.(2)M
y= H
n* ( e + 1.5 * D + 0.5 * f )
pers.(3)M
y= 9 / 4 * D * č
u* g
2 pers.(4) Dari pers.(1) :f =
0.009672* H
nDari pers.(2) :
g =
3.55 -0.00967* H
ng
2=
0.000094* H
n2 -0.06867* H
n+
12.609 / 4 * D * c
u=
25.849 Dari pers.(3) :M
y= H
n* (
0.650 0.00484* H
n)
M
y=
0.00484* H
u2 0.65000* H
nDari pers.(4) :
M
y=
0.002418* H
u2 -1.7750* H
n 325.756 Pers.kuadrat : 0 = 0.00242* H
u2 2.4250* H
n -325.756 Dari pers. kuadrat, diperoleh tahanan lateral nominal,H
n=
119.979 kNf = 1.160 m
M
max= H
n* ( e + 1.5 * D + 0.5 * f ) =
147.599 kNmM
max> M
y→
Termasuk tiang panjang (OK) Dari pers.(3) :M
y= H
n* (
0.650 0.00484* H
n)
26.51
=
0.00484* H
n2 0.65000* H
uPers.kuadrat : 0 = 0.00484
* H
n2+
0.65000* H
n -26.51Dari pers. kuadrat, diperoleh tahanan lateral nominal,
H
n=
32.784 kNFaktor reduksi kekuatan,
f =
0.60Tahanan lateral tiang pancang,
→ f * H
n=
19.67kN
3. REKAP TAHANAN LATERAL TIANG
No Uraian Tahanan Lateral Tiang Pancang
f * H
n1 Berdasarkan defleksi tiang maksimum 31.10
2 Berdasarkan momen maksimum 19.67
Tahanan lateral tiang terkecil,
f * H
n=
19.67 kN Diambil tahanan lateral tiang pancang,→ f * H
n=
10.00 kNKODE FONDASI :
F9
DATA BAHAN PILECAP
Kuat tekan beton,
f
c' =
20 MPaKuat leleh baja tulangan deform ( Æ > 12 mm ),
f
y=
390 MPa Kuat leleh baja tulangan polos ( Æ ≤ 12 mm ),f
y=
240 MPaBerat beton bertulang,
w
c=
24 kN/m3DATA DIMENSI FONDASI
Lebar kolom arah x,
b
x=
0.60 mLebar kolom arah y,
b
y=
0.60 mJarak tiang pancang tepi terhadap sisi luar beton,
a =
0.40 mTebal pilecap,
h =
0.50 mTebal tanah di atas pilecap,
z =
0.90 mBerat volume tanah di atas pilecap,
w
s=
18.00 kN/m3Posisi kolom (dalam = 40, tepi = 30, sudut = 20)
a
s=
40( Tabel IV. B. 1 Data Bahan dan Dimensi Pile Cape )
B. PERHITUNGAN KEKUATAN FONDASI
( Tabel IV. A. 5 Rekap Tahanan Lateral Tiang Pancang )
DATA BEBAN FONDASI
Gaya aksial kolom akibat beban terfaktor,
P
uk=
1500.00 kNMomen arah x akibat beban terfaktor.
M
ux=
250.00 kNmMomen arah y akibat beban terfaktor.
M
uy=
220.00 kNmGaya lateral arah x akibat beban terfaktor,
H
ux=
150.00 kN Gaya lateral arah y akibat beban terfaktor,H
uy=
130.00 kNTahanan aksial tiang pancang,
f * P
n=
-440.00 kNTahanan lateral tiang pancang,
f * H
n=
10.00 kNDATA SUSUNAN TIANG PANCANG
Susunan tiang pancang arah x : Susunan tiang pancang arah y :
No. Jumlah
x n * x
2 No. Jumlahy n * y
2n (m) (m2) n (m) (m2)
1 3 1.00 3.00 1 3 1.00 3.00
2 3 0.00 0.00 2 3 0.00 0.00
3 3 -1.00 3.00 3 3 -1.00 3.00
n = 9
S x
2=
6.00 n = 9S y
2=
6.00Lebar pilecap arah x,
L
x=
2.80 mLebar pilecap arah y,
L
y=
2.80 m1. GAYA AKSIAL PADA TIANG PANCANG
Berat tanah di atas pilecap,
W
s= L
x* L
y* z * w
s=
127.01 kNBerat pilecap,
W
c= L
x* L
y* h * w
c=
94.08 kNTotal gaya aksial terfaktor,
P
u= P
uk+ 1.2 * W
s+ 1.2 * W
c=
1765.31 kN Lengan maksimum tiang pancang arah x thd. pusat,x
max=
1.00 m Lengan maksimum tiang pancang arah y thd. pusat,y
max=
1.00 m Lengan minimum tiang pancang arah x thd. pusat,x
min=
-1.00 m Lengan minimum tiang pancang arah y thd. pusat,y
min=
-1.00 m Gaya aksial maksimum dan minimum pada tiang pancang,p
umax= P
u/ n + M
ux* x
max/ Sx
2+ M
uy* y
max/ Sy
2=
274.48 kNp
umin= P
u/ n + M
ux* x
min/ Sx
2+ M
uy* y
min/ Sy
2=
117.81 kNSyarat :
p
umax≤ f * P
n274.48
>
-440.00→
BAHAYA (NG)( Tabel IV. B. 2 Data Beban Pondasi dan Susunan Tiang Pancang )
2. GAYA LATERAL PADA TIANG PANCANG
Gaya lateral arah x pada tiang,
h
ux= H
ux/ n =
16.67 kN Gaya lateral arah y pada tiang,h
uy= H
uy/ n =
14.44 kN Gaya lateral kombinasi dua arah,h
umax= Ö ( h
ux2+ h
uy2) =
22.05 kNSyarat :
h
umax≤ f * H
n22.05
>
10.00→
BAHAYA (NG)3. TINJAUAN GESER ARAH X
Jarak pusat tulangan terhadap sisi luar beton,
d' =
0.100 mTebal efektif pilecap,
d = h - d' =
0.400 mJarak bid. kritis terhadap sisi luar,
c
x= ( L
x- b
x- d ) / 2 =
0.900 mBerat beton,
W
1= c
x* L
y* h * w
c=
30.240 kNBerat tanah,
W
2= c
x* L
y* z * w
s=
40.824 kNGaya geser arah x,
V
ux= 3 * p
umax- W
1- W
2=
752.371 kN Lebar bidang geser untuk tinjauan arah x,b = L
y=
2800 mmTebal efektif pilecap,
d =
400 mmRasio sisi panjang thd. sisi pendek kolom,
b
c= b
x/ b
y=
1.0000 Kuat geser pilecap arah x, diambil nilai terkecil dari Vc yang diperoleh dari pers.sbb. :V
c= [ 1 + 2 / b
c] * √ f
c' * b * d / 6 * 10
-3=
2504.396 kNV
c= [ a
s* d / b + 2 ] * √ f
c' * b * d / 12 * 10
-3=
3219.938 kNV
c= 1 / 3 * √ f
c' * b * d * 10
-3=
1669.597 kNDiambil, kuat geser pilecap,
® V
c=
1669.597 kNFaktor reduksi kekuatan geser,
f =
0.75Kuat geser pilecap,
f * V
c=
1252.198 kNSyarat yang harus dipenuhi,
f * V
c≥ V
ux1252.198
>
752.371®
AMAN (OK)4. TINJAUAN GESER ARAH Y
Jarak pusat tulangan terhadap sisi luar beton,
d' =
0.100 mTebal efektif pilecap,
d = h - d' =
0.400 mJarak bid. kritis terhadap sisi luar,
c
y= ( L
y- b
y- d ) / 2 =
0.900 mBerat beton,
W
1= c
y* L
x* h * w
c=
30.240 kNBerat tanah,
W
2= c
y* L
x* z * w
s=
40.824 kNGaya geser arah y,
V
uy= 3 * p
umax- W
1- W
2=
752.371 kN Lebar bidang geser untuk tinjauan arah y,b = L
x=
2800 mmTebal efektif pilecap,
d =
400 mmRasio sisi panjang thd. sisi pendek kolom,
b
c= b
x/ b
y=
1.0000 Kuat geser pilecap arah y, diambil nilai terkecil dari Vc yang diperoleh dari pers.sbb. :V
c= [ 1 + 2 / b
c] * √ f
c' * b * d / 6 * 10
-3=
2504.396 kNV
c= [ a
s* d / b + 2 ] * √ f
c' * b * d / 12 * 10
-3=
3219.938 kNV
c= 1 / 3 * √ f
c' * b * d * 10
-3=
1669.597 kNDiambil, kuat geser pilecap,
® V
c=
1669.597 kNFaktor reduksi kekuatan geser,
f =
0.75Kuat geser pilecap,
f * V
c=
1252.198 kNSyarat yang harus dipenuhi,
f * V
c≥ V
ux1252.198
>
752.371®
AMAN (OK)5. TINJAUAN GESER DUA ARAH (PONS)
Jarak pusat tulangan terhadap sisi luar beton,
d' =
0.100 mTebal efektif pilecap,
d = h - d' =
0.400 mLebar bidang geser pons arah x,